Data Sheet for Product

Siemens
Smart Infrastructure Building Products
6
usa.siemens.com/fire
Multi-Mode Ethernet Module
The Multi-Mode Ethernet Module (Model VN2002-A1)
serves as a network connector between Siemens fire-only
FACPs and with intelligent voice-communication panels, via
multi-mode fiber-optic cables.
Model VN2002-A1 mounts in either or both of the
following:
Voice CPU Card, Model VCC2001-U1 [used in voice
systems]
Modular Ethernet Switch, Model FN2012-A1 [for
use in FACP-only connections]
Voice-Over-IP Module
The VOIP module (Model VCI2003-A1) is used to convert
audio signals between analog and digital Voice-over-IP
signals. This module is mounted to a connection point on
the voice CPU card (Model VCA2001), and is required for all
network voice applications.
For system configurations, the Voice CPU card provides
voice-network support to the following:
VoIP Module (Model VCI2003-A1)
[for Voice-over-IP conversion of audio signals]
up to four (4) CAT5 connections, via the Electric
Ethernet Module, Model VN2001-A1a single-mode
(Model VN2003-A1) or a multi-mode (Model
VN2002-A1) Ethernet module
Remote (‘Class B’) Terminal Board
The Remote (‘Class B’) Terminal Board (Model VTA2001-A1)
provides system support to the 24-Switch Option Module
(Model VTO2001-U3) and the Microphone Option Module
(Model VTO2004-U3) when the aforementioned option
modules function from a remote enclosure.
Model VTA2001-A1 terminal board, which mounts in a 1HU
enclosure, serves as a central station for audio output,
system communication and 24VDC power wiring from the
Cerberus PRO intelligent voice-communication FACP on its
network.
Plug-in connectors for the ribbon
cables used on the 24-Switch
Option Module (Model VTO2001-
U3) and the Microphone Option
Module (Model VTO2004-U3) are
also included on each ‘Class B’
board.
LED Driver and Tabular Annunciators
The LED Annunciator Driver, Model FT2007-U1, is the key
component for custom graphic annunciators on all Cerberus
PRO addressable fire panels. This optional system module
provides outputs for system status as well as zone status.
Model FT2007-U1 is supervised via a RS−485 interface. A
maximum eight (8) modules are allowed on each RS−485.
The Tabular Annunciators allow system events sent from
Cerberus PRO addressable panels to be displayed remotely in
real-time. Tabular annunciators are available in either red or
black. The Model FT2008 series of tabular annunciators has
16 zones, and the Model FT2009 series uses 32 zones.
Up to two (2) LEDs can be used per zone.
C-WEB Network Module
The C-WEB network module (Model FN2001-U1) is used to
network up to 32 FACPs and the Fire Terminal (Model
FT924), via the C-WEB system bus. The C-WEB network
module is plugged into a Standard Operating Unit or an
Operating Unit with LEDs. ‘Peer-to-peer’ networking is
supported by the C-WEB module on 252 / 504-point
addressable systems, as well as on a Fire Terminal Board
(Model FT924).
Model FN2001-U1 connects to system-bus inputs and
outputs. The network module has ground-fault monitoring,
as well as an integrated degrade-mode function.
Redundant networking is accomplished with one (1)
network module [simple loop trouble] per panel. There is
electrical isolation between the system bus and the FACP.
Leased-Line / City-Tie Module
The leased-line / city-tie module (Model FCI2020-U1) is used
as an optional module, providing a local-energy output for
municipal call-box connection. Model FCI2020-U1 also gives
a reverse-polarity output for leased-line connection. Model
FCI2020-U1 is installed on the periphery board for Cerberus
PRO FACPs, respectively.
When used for connection to a
municipal call box, the city-tie
function supports Alarm-event
transmission. When used for
leased-line connection, the
module supports two (2)
leased telephone lines for
transmitting Alarm, Trouble
and Supervisory events.
Cerberus PRO Fire Components
Voice System Components (cont.)
Model
FN2001-U1
Model
VCI2003-A1
Model
VN2002-A1
Model
FT2007-U1
Model
FCI2020-U1
Model
VTA2001-A1