Data Sheet for Product

Siemens
Smart Infrastructure Building Products
7
usa.siemens.com/fire
Releasing Module
The releasing module (Model XCI2001-U1) is an optional
module that is connected to the peripheral boards (Models
FCI2016-U1, FCI2017-U1), providing two (2) circuits of
optional releasing, respectively.
Model XCI2001-U1 supports
activation of releasing valves in
pre-action / deluge systems
(including double-interlock pre-
action systems, or Sinorix
Engineered Fire Suppression
Systems). Model XCI2001-U1
supports two (2) ’Class B’ or one
(1) ‘Class A releasing circuits.
Remote Display Terminal (with RS485 interface)
The Remote Display Terminals (Models FT2014-U3 / R3 and
FT2015-U3 / R3) are LED / LCD units that show the existing
status of a Cerberus PRO 252 / 504-point system.
A LED will illuminate for any given Alarm, Supervisory and
Trouble Cerberus PRO-system event. A LCD screen will give
details of the event in alphanumeric form. The display
screen can be scrolled to reveal additional events. Optional
remote-system-control capabilities are also available.
When an event has been triggered to the Cerberus PRO
panel, the LCD screen will show the following:
Event type and zone
Time of the event [only possible in a menu-driven
function]
Custom message for that zone
Usage of the zone
‘Unacknowledged’ or ‘Acknowledged’ event
The display has a backlight feature that operates upon
receiving any event information or when any operator
buttons are pressed.
The Model FT2014-series display terminal has a button used
to silence the local sounder. Meanwhile, the Model FT2015-
series display terminal has three (3) control buttons for
‘acknowledging events, silencing audible circuits and
resetting the system. Additionally, there are three (3) user-
programmable buttons available. The Model FT2015-series
has a key switch that enables the control buttons to operate.
The remote display terminals are remotely connected to the
Cerberus PRO FACP, via the RS485 interface. Cerberus PRO
panels require the Model FCA2016-U1 RS485 module to
provide communication to the remote display terminals.
Model FCA2016-U1 supports Style 4 or Style 6 wiring.
Up to eight (8) modules can be supported on a RS485 bus.
Note: In compliance of Canadian fire code, the Model FHD2012-
U1 Inner Door must be ordered and used for housing the Remote
Display Terminal (Model FT201x-Series)
Single-Mode / Multi-Mode Fiber-Optic Module
The single-mode (Model FN2006-U1) / multi-mode (Model
FN2007-U1) fiber-optic interface module can be used to
transmit RS-485 communication for the Cerberus PRO FACP,
as well as the Model FT924 Fire Terminal.
The single-mode / multi-mode fiber-optic module provides
C-NET peer-to-peer network communication between the
Cerberus PRO 252-point and 504-point addressable systems.
Models FN2006-U1 / FN2007-U1 require 24 Volts DC
[nominal] power, and the networked Cerberus PRO panel
serves as the main source in meeting this power
requirement. Models FN2006-U1 / FN2007-U1 can also be
powered from any UL Listed, regulated 24VDC power supply,
such as the Siemens (Model PAD-series) Distributed Power
Module & NAC Extender.
Models FN2006-U1 / FN2007-U1 can be mounted in a
Cerberus PRO one-height-unit or two-height unit enclosure,
and can operate in a daisy-chain configuration.
Two (2), high-quality duplex 9/125 fiber-optic cables and ST-
style fiber connectors are used for connection between
single-mode fiber-optic modules. The duplex fiber-optic
cable has two (2) cables in a single shield that is similar to
an electrical zip cord. When using single-mode fiber, each
segment of the fiber network can be up to almost 10 miles
(16.1 km).
For ‘Class B’ installations, each FACP or terminal at either end
of the daisy chain use one (1) duplex cable for connection to
the next networked panel or terminal. FACPs or terminals
within the daisy chain require two (2) duplex cables: one (1)
duplex cable for connection to the previous FACP, and one
(1) duplex cable for connection to the next FACP.
For ‘Class A’ installations, each FACP or terminal requires two
(2) duplex cables: one (1) duplex cable for connection to the
previous FACP, and one (1) duplex cable for connection to
the next FACP.
Digital Alarm Communicator Transmitter
The Digital Alarm Communicator Transmitter (DACT) is used
to provide communication between a 252 / 504-point (FIRE
or IVC) addressable FACP and an off-premises monitoring
station.
Each DACT (Model FCA2015-U1) can also support additional
third-party Internet Protocol (IP) and Global System Mobile
(GSM) communication technologies, which include: Bosch,
Telguard and DSC. Consequently, Model FCA2015-U1 is UL
Listed as compatible with third-party IP and GSM dialers.
The Model FCA2015-U1 module mounts directly on the back
enclosure and connects to the periphery boards. The DACT
enables remote transmission of alarms and events via a
public telephone line.
Model FCA2015-U1 supports two (2) lines and four (4)
accounts, and can transmit serial information (including the
address of the event) to the monitoring station.
Model
FT2015-U3
Cerberus PRO Fire Components (cont.)
Model
XCI2001-U1
Model
FCA2015-U1