Data Sheet for Product

5 / 18
Siemens 2- and 3-port valves with flanged connections, PN 25 CE1N4405en
Smart Infrastructure 2019-05-24
Equipment combinations
Product
number
Description
Stroke
Positioning
force
Operating
voltage
Positioning
signal
Spring
return time
Positioning
time
LED
Manual
adjuster
Auxiliary
functions
SAX31.00
S55150-A105
20 mm
800 N
AC 230 V
3-position
-
120 s
-
Push and
fix
1)
,
2)
,
SAX31.03
S55150-A106
30 s
SAX61.03
SAX61.03U
S55150-A100
S55150-A100-A100
AC/DC 24 V
0…10 V
4…20 mA
0…1000 Ω
3)
,
4)
SAX81.00
S55150-A102
3-position
-
120 s
-
Push and
fix
1)
,
2)
,
SAX81.03
SAX81.03U
S55150-A103
S55150-A103-A100
30 s
SKD32.21
SKD32.21
20 mm
1000 N
AC 230 V
3-position
8 s
Opening: 30 s
Closing: 10 s
-
Turn,
Position is
maintained
1)
,
2)
,
SKD32.50
SKD32.50
-
120 s
SKD32.51
SKD32.51
8 s
SKD60
SKD60
AC 24 V
0…10 V
4…20 mA
0…1000 Ω
-
Opening: 30 s
Closing: 15 s
3)
SKD62
SKD62U
SKD62
SKD62U
15 s
SKD62UA
SKD62UA
5)
SKD82.50
SKD82.50U
SKD82.50
SKD82.50U
3-position
-
120 s
-
1)
,
2)
,
SKD82.51
SKD82.51U
SKD82.51
SKD82.51U
8 s
SKB32.50
SKB32.50
20 mm
2800 N
AC 230 V
3-position
-
120 s
-
Turn,
Position is
maintained
1)
,
2)
,
SKB32.51
SKB32.51
10 s
SKB60
SKB60
AC 24 V
0…10 V
4…20 mA
0…1000 Ω
-
Opening:
120 s
Closing:10 s
3)
SKB62
SKB62U
SKB62
SKB62U
10 s
SKB62UA
SKB62UA
5)
SKB82.50
SKB82.50U
SKB82.50
SKB82.50U
3-position
-
120 s
-
1)
,
2)
,
SKB82.51
SKB82.51U
SKB82.51
SKB82.51U
10 s
SAV31.00
S55150-A112
40 mm
1600 N
AC 230 V
3-position
-
120 s
-
Push and
fix
1)
,
2)
,
6)
SAV61.00
SAV61.00U
S55150-A110
S55150-A110-A100
AC/DC 24 V
DC 0...10 V
DC 4...24 mA
0...1000
1)
,
3)
,
6)
,
7)
SAV81.00
SAV81.00U
S55150-A111
S55150-A111-A100
3-position
-
1)
,
2)
,
6)
SKC32.60
SKC32.60
40 mm
2800 N
AC 230 V
3-position
-
120 s
-
Turn,
Position is
maintained
1)
,
2)
,
SKC32.61
SKC32.61
18 s
SKC60
SKC60
AC 24 V
0…10 V
4…20 mA
0…1000 Ω
-
Opening:
120 s
Closing: 20 s
3)
SKC62
SKC62U
SKC62
SKC62U
20 s
SKC62UA
SKC62UA
5)
SKC82.60
SKC82.60U
SKC82.60
SKC82.60U
3-position
-
120 s
-
1)
,
2)
,
SKC82.61
SKC82.61U
SKC82.61
SKC82.61U
18 s
1)
Auxiliary switch (optional)
2)
Potentiometer (optional)
3)
Position feedback, forced control, selection of valve characteristic
4)
Optional: Sequence control, selection of acting direction
5)
Plus sequence control, stroke limitation, and selection of acting direction
6)
Stem heating element (optional)
7)