Pipe connection
Avoid leakage:
Install fittings as per ISO 7-1.
Do not use too much hemp or PTFE tape.
Do not tighten pipe threading to "the very end".
Flow direction
Make sure that the valve is mounted in the proper flow direction. A symbol is applied to the
valve body:
VVG44.. :
Flow direction:
VXG44.. :
Mixing
A / B to AB:
Diverting
AB to A / B:
Commissioning
The actuator must be properly mounted or manually adjusted before commissioning the
valve.
VVG44..
Turn the manual adjuster clockwise: Valve opening = Increasing flow
Turn the manual adjuster counter clockwise: Valve closing = Decreasing flow
VXG44..
Turn the manual adjuster clockwise: Through-put A – AB opens, bypass B closes
Turn the manual adjuster counter clockwise: Through-put A – AB closes, bypass B opens
Maintenance
Valves VVG44.. and VXG44.. are maintenance free.
Stem sealing gland
The stem sealing gland cannot be exchanged. The entire valve must be replaced in the
event of leakage. Contact your local Siemens office or branch for information.
Disposal
WARNING
Tensioned return spring
Opening the valve housing can release the tensioned return spring resulting in
flying parts that may cause injury.
Do not open the valve body.
The valve is considered electrical and electronic equipment for disposal in
terms of the applicable European Directive and may not be disposed of as
domestic garbage.
Dispose of the valve through channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.