Full Product Manual

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog
1-20
1
LOAD CENTERS &
CIRCUIT BREAKERS
Main Lug and Main Breaker with Copper Bus

100,000A IR
4–16 circuits, 100–225 Amperes 1-Phase, 3-Wire, SN 120/240 Volts AC
a
70 amp maximum breaker.
b
Will not accommodate 2-pole GFCI or circuit breaker with
shunt trip.
c
Can accommodate 2-pole GFCI breaker up to 50A. For
2-pole 60A GFCI, a restriction of #6 wire applies due to
wire bend space of the enclosure. Will not accommodate
circuit breaker with shunt trip.
d
100 amp maximum breaker.
e
Suitable for use as service entrance equipment when a main
breaker (125A maximum) is back-fed in a branch position and
used with main breaker retainer clip (Cat. No. ECMBR1).
Suitable for use as service entrance when not more than six
main disconnecting means are provided. Check local codes and
restrictions.
Two Q115 and one Q230 breaker included.
W0408L1125SPA50 provided with factory installed QF50 and
ground bar. W0408L1125SPA60 provided with factory installed
QF260 and ground bar.
Copper Bus load centers are recommended for those
applications where the environment may be severe
(i.e. farm and coastal areas).
2" HS Type hub provided.
Type QNR main breaker factory installed.
CSA Listed
Cover plate included
Features/Applications
EQ Load Centers with main lugs
feature a combination trim box in one
package.
n Interiors offer removal in seconds
n Single phase
n One piece bus bar construction
designed for use only with circuit
breakers
n UL Listed
n UL listed on 60/75°C conductors
(see equipment markings for
applications)
n Positive load side circuit breaker
hook rails
n Outdoor Type 3R devices use HS
Type hubs. See page 1-23.
Main Lugs with Aluminum Bus
100,000A IR
4–16 circuits, 100–125 Amperes 1-Phase, 3-Wire, SN 120/240 Volts AC
Branch Circuits Indoor Enclosure — NEMA Type 1 Outdoor Enclosure — NEMA Type 3R
Amp
Rating
Max.
1-Pole
No. of
Spaces
No. of
Circuits
QP
Max.
2-Poles
Catalog Number
Replace Suffix F
(Flush) with S for
Surface Mounting
Std.
Pkg.
Dimensions (inches)
Catalog
Number
Std
Pkg.
Dimensions (inches)
H W D H W D
100 12 24 6
E1224ML1100FG
a
1 14 3/4 12 3/8 3 7/8
125 4 8 2
E0408ML1125F
bde
5 12 5/8 6 5/8 3 1/2
W0408ML1125
bd
5 12 1/4 6 4 1/4
125 4 8 2
W0408L1125SPA50
cd
1 12 1/4 6 4 1/4
125 4 8 2
W0408L1125SPA60
cd
1 12 1/4 6 4 1/4
125 8 16 4
E0816ML1125F
e
1 14 3/4 12 3/8 3 7/8
Branch Circuits Indoor Enclosure — NEMA Type 1 Outdoor Enclosure — NEMA Type 3R
Amp
Rating
Max.
1-Pole
No. of
Spaces
No. of
Circuits
QP
Max.
2-Poles
Catalog
Number
Std.
Pkg.
Dimensions (inches)
Catalog
Number
Std.
Pkg.
Dimensions (inches)
H W D H W D
100 10 20 4
E1020MB1100FCGP
1 14 3/4 12 3/8 3 7/8
100 12 24 6
E1224ML1100FCU
1 14 3/4 12 3/8 3 7/8
125 8 16 4
E0816ML1125FCU
e
1 14 3/4 12 3/8 3 7/8
W0816ML1125CU
e
1 14 3/4 12 1/8 4 1/4
125 8 16 4
E0816ML1125SCU
1 14 3/4 12 3/8 3 7/8
225 4 6 2 1
W0406ML1225CU
b
1 23 10 4 1/8
200 4 4 2 1
W0404MB1200CT

1 20 11 1/8 4 3/4
150 4 4 2 1
W0404MB1150CTS

1 20 11 1/8 4 3/4
200 4 4 2 1
W0404MB1200CTS

1 20 11 1/8 4 3/4
Renovation Panel
Ideal for older home renova-
tion projects where the dis-
tance between the studs is
narrower than current
construction practices. The
narrower panel eliminates
the need to ‘notch’ out the
existing studs.
Spa Panels
Spa Panels are ideal for out-
door applications requiring
the use of ground fault pro-
tection, such as hot tubs. A
factory installed 2-Pole GFCI
breaker is provided, along
with 2 extra circuits.
Product Category RESI
Small Circuit Load
Centers
Ideal for subfeed
applications
EQ
®
Load Centers
Small Circuit Load Centers
1-Phase, 3-WIre SN, 120/240Volts AC

Summary of content (1 pages)