Procedure
1. Place the trapeze nut into the suspension rail, feed the trapeze spindle of the weighing device through the
hole in the suspension rail and screw the slightly greased trapeze spindle into the trapeze nut until it appears
at the end of the nut.
2. Secure the two trapeze nuts at the lower end of the spindle to each other (counter).
3. Bring the two thread rods (M10) into the weighing device and secure them flush in the 2 hut nuts.
4. Screw the neck ring onto the cylinder, orientating the slots with respect to the cylinder valve (in line with the
burst disc port) and locate the threaded rods of the weighing device into the slots on the neck ring
5. Turn the lower counter nut anti-clockwise. The cylinder is lifted up. Continue to turn it until the cylinder hangs
at least 2 cm above the floor. The cylinder can lifted up so high, that it is possible to place periodically a
external weighing device to check the filling quantity. It is also possible to lift up the cylinders with the CO2
weighing device tool S54476-B157-A15 with on site portable electrical drill with wrench AF/ SW30.
6. Align the weighing device trip mechanism and weight spindle so that they are parallel to the suspension rail.
7. Adjust the height of the cylinders so that the valve outlet ports are all at the same height.
8. Open the two counter nuts from each other and secure them at the lower and upper end of the trapeze
spindle to prevent the weighing device from being rotated
9. Remove the Tommy bar. The device with the fixed cylinder is now ready to adjust.
10. Replace of cylinder f.e. after a release same procedure in opposite way
Assembly instructions electrical remote indication switch
The weighing device is supplied with a bracket and trip plate fitted.
There is type of remote indication switch (optional).
· Siemens CX 1562010 / A5Q00032144 including all fixations, documentation 12-01-010
Technische Daten / Technical data
Deutsch English
Endschalter position switch Siemens
CX Artikelnummer CX ref.no. 1562010
SAP SAP A5Q00032144
Typ type 3SE5 232-OHC05
Kabel cable nein / no
Kabel Zugentlastung cable strainrelief ja / yes
Schaltanschluss connection 1 NO + 1NC
Kapselung closure gekapselt / enclosed
Anschluss connection 48V, 1A, IP65
Konformitätserklärung EC Declaration of Conformity 2011/65/EU
Remote indication switches must be fixed to the bracket as follows:
Deutsch English
Schraube screw 2 x CX 507053 / A5Q00032190 M4x35
Mutter screw nut 2 x CX 180377 / A5Q00032183 M4
The cable connection is fitted via:
Deutsch English
Kabelverschraubung M20x1.5 cable screw connection m20x1.5 1 x A5Q00031978
Switch and switch cable connection material are part of S54476-S45-A1 / S54476-S45-A2.