User Manual
1/2
Building Technologies 02-01-010 E.doc
Fire Safety & Security Products
Weighing device for indicating loss of a critical mass of extinguishant ENGLISH
02-01-010
PED-category:
limit switch
WD2005-SWITCH
Index Description Date
Fluid group: 01.05.16
Product line
Sinorix ™
a NO / NC 01.04.17
CX ref. no.
SAP
A5Q00032144
The weighing device SBT WD2005 by SIEMENS indicates the loss of a critical mass of extinguishant from the
cylinders. With the limit switch A5Q00032144 this signal can be transmitted. Each device needs a switch.
S54476-S45-A1 = S54476-B45-A1 + S54476-B52-A4
S54476-S45-A2 = S54476-B45-A1 + S54476-B52-A5
Technische Daten / Technical data
Deutsch English
Endschalter position switch Siemens
CX Artikelnummer CX ref.no. 1562010
SAP SAP A5Q00032144
Typ type 3SE5 232-OHC05
Kabel cable nein / no
Kabel Zugentlastung cable strainrelief ja / yes
Schaltanschluss connection 1 NO + 1NC
Kapselung closure gekapselt / enclosed
Anschluss connection 48V, 1A, IP65
Konformitätserklärung EC Declaration of Conformity
Remote indication switches must be fixed to the bracket as follows:
Deutsch English
Schraube screw 2 x CX 507053 / A5Q00032190 M4x35
Mutter screw nut 2 x CX 180377 / A5Q00032183 M4
The cable connection is fitted via:
Deutsch English
Kabelverschraubung M20x1.5 cable screw connection m20x1.5 1 x A5Q00031978
Material for fixation of switch and cable gland are part of set S54476-S45-A1 / S54476-S45-A2.
Bracket for switch and flag are already factory mounted.