User's Manual

Automation systems
Microbox automation system
10/5
Siemens ST PCS 7 · Update November 2008
10
Two Ethernet interfaces 10/100/1000 Mbit/s (RJ45) are inte-
grated in the SIMATIC PCS 7 AS RTX for plant bus communica-
tion with SIMATIC PCS 7 subsystems such as operator system,
engineering system or maintenance station.
ET 200M, ET 200ISP and ET 200S I/O stations can be linked
over a PROFIBUS DP interface to a comprehensive range of low-
cost signal/function modules as well as intelligent field/process
devices on the PROFIBUS PA.
The SIMATIC PCS 7 AS RTX is configured using the central en-
gineering system of the SIMATIC PCS 7 process control system.
The engineering system also administers the AS Runtime li-
censes of the SIMATIC PCS 7 AS RTX. The scope of delivery
of the SIMATIC PCS 7 AS RTX already includes an AS Runtime
license for 250 POs. This can be expanded by further AS Run-
time licenses for 100 POs. The process objects of additional
AS Runtime licenses are then added to process objects which
already exist.
Technical specifications
SIMATIC PCS 7 AS RTX
Design and equipment features
Design
DIN rail or wall mounting;
horizontal (preferred) or vertical
Degree of protection to EN 60529
(front/rear)
IP20
CPU
• Processor Intel Pentium M 1.4 GHz
• Front Side Bus
400 MHz
• Second Level Cache
2 MB
Chipset
Intel Alviso 910GML
Main memory
1 GB DDR2-SDRAM (SO-DIMM
modules)
Graphics
• Graphics controller Intel 2D/3D GMA900, integrated
in chipset
• Graphics memory
Dynamic video memory 8 to
128 MB
• Resolutions/colors/frequencies
-CRT Up to 1600 x 1200 / 32 bit colors /
60 to 120 Hz
- DVI
Up to 1600 x 1200 / 32 bit colors
Drives
• Flash drive For CompactFlash card, 2 GB
• CD-ROM / DVD-RW / diskette
Connectable via USB (not
included in scope of delivery)
Interfaces
• PROFIBUS/MPI 12 Mbit/s (electrically isolated,
CP 5611-compatible), 9-contact
Sub-D socket
• Ethernet
2 x 10/100/1000 Mbit/s (RJ 45),
two independent controllers
•USB
4 x USB 2.0/high-speed
• Serial
1 x COM1 (V.24), 9-contact Sub-D
connector
• Parallel
-
• Graphics connection
1 x DVI-I (DVI/VGA combined):
• DVI: digital
• VGA analog
• Keyboard/mouse
Connectable via USB (not
included in scope of delivery)
LED displays
• Power
• Watchdog
Operating system / basic software
Operating system
Windows XP Embedded prein-
stalled on CompactFlash card
(CF card) 2 GB, no activation
required
System-tested SIMATIC industrial
software
WinAC RTX
DiagMonitor
Monitoring/diagnostics functions
Watchdog
• Monitoring of program execution
• Restart can be parameterized
following faults
Monitoring time adjustable in the
software
Temperature Processor
• Motherboard
(via SIMATIC PC DiagMonitor and
SIMATIC PCS 7 Asset Manage-
ment)
Operating hours counter
(via SIMATIC PC DiagMonitor and
SIMATIC PCS 7 Asset Manage-
ment)
Safety
Protection class
Protection class I compliant with
IEC 61140
Safety directives
EN 60950-1; UL 60950;
CAN/CSA-C22.2 No. 60950-1;
UL 508; CAN/CSA-C22.2 No. 142
or CAN/CSA-C22.2 No. 14-05
Noise level
Operation
< 40 dB (A) to DIN 45635-1
Technical specifications
© Siemens AG 2008