User's Manual

Starter systems
SIMATIC PCS 7 BOX
SIMATIC PCS 7 BOX 416
3/9
Siemens ST PCS 7 · November 2007
3
Function
WinAC Slot 416 V4.0
Through use of the WinAC Slot 416 V4.0, it is possible for the au-
tomation program in the Slot CPU to execute completely auton-
omously from the SIMATIC Box PC and its Windows operating
system. Therefore the system can be restarted even if the
SIMATIC Box PC is switched off or faulty. 24 V DC from a sepa-
rate source is connected to the Slot CPU to provide a power sup-
ply independent of the PC. Neither software faults on the PC
side, nor a power loss, nor rebooting of the PC have an effect on
execution of the automation program in the Slot CPU.
If one of the following events occurs, the automation program is
immediately informed and can thus react accordingly, e.g. by in-
termediate storage of production data and transfer of the system
to a defined status:
Shutting-down of the Windows operating system
Fault in the Windows operating system ("blue screen")
Failure of PC-internal communication
Switching-off of the PC (Separate 24 V DC supply required)
With the SIMATIC PCS 7 BOX 416, the process I/O is connected
via the two PROFIBUS DP ports of the WinAC Slot 416 V4.0. In
conjunction with SIMATIC PCS 7 V7.0, the WinAC Slot 416 V4.0
also permits changes to the configuration during operation
(CiR). The type and scope of online modifications depend on the
process I/O used.
Since SIMATIC PDM can only access field devices on the
PROFIBUS DP via the onboard CP 5611 communications pro-
cessor, an additional link is required between the DP port and
the CP 5611. The plug required belongs to the scope of delivery
of the SIMATIC PCS 7 BOX 416.
Use with SIMATIC BATCH
SIMATIC PCS 7 BOX 416 systems can also be used for automa-
tion of batch processes with SIMATIC BATCH. The capacity of
SIMATIC BATCH is limited to 10 UNITs (instances of plant units)
in this case. The following SIMATIC BATCH option packages can
be executed on the SIMATIC PCS 7 BOX in addition to the SI-
MATIC BATCH Server Basic Package for up to 10 UNITs:
Batch Control Center
Recipe System
Batch Planning
Hierarchical Recipe
ROP Library
Separation Procedures/Formulas
Use with SIMATIC Route Control
SIMATIC PCS 7 BOX 416 systems are not only suitable for auto-
mation of batch processes with SIMATIC BATCH, but also for
control of material transports with SIMATIC Route Control. The
capacity of SIMATIC Route Control is limited to 30 simultaneous
material transports in this case. The SIMATIC Route Control
Server and SIMATIC Route Control Center runtime software is
then executed on the SIMATIC PCS 7 BOX 416. The Route Con-
trol Engineering is also possible on a SIMATIC PCS 7 BOX 416
all-in-one system.
Technical specifications
Basic hardware: SIMATIC Box PC 627B
Design and equipment features
Design Rack-mountable device with rug-
ged metal enclosure, suitable for
wall and portrait mounting
Degree of protection to EN 60529
IP20
CPU
• Processor Intel Core 2 Duo T7400 2.16 GHz
• Front Side Bus
667 MHz
• Second Level Cache
4 MB
Chipset
Intel 945 GM
Main memory
2 GB DDR2-667 SDRAM
(2 x 1 GB)
Graphics
• Graphics controller Intel 2D/3D GMA950, integrated
in chipset
• Graphics memory
Dynamic video memory 8 to
128 MB
• Resolutions/colors/frequencies
• VGA: Max. 1600 x 1200 /
32 bit colors / 85 Hz
• DVI: Max. 1600 x 1200 /
32 bit colors / 60 Hz
Drives
• Flash drive For CompactFlash card
• Hard disk
3.5" SATA, 160 GB
• Optical drive
DVD ± R/RW
• Diskette drive
Connectable via USB (not
included in scope of delivery)
Interfaces
• PROFIBUS/MPI 1 x 9-contact Sub-D socket,
12 Mbit/s (electrically isolated,
CP 5611-compatible)
• Ethernet
2 x 10/100/1000 Mbit/s (RJ 45)
•USB
4 x USB 2.0/high-speed
(2 x high-current)
•Serial
1 x COM1 (V.24), 9-contact
Sub-D connector
• Parallel
-
• Graphics connection
1 x DVI-I (DVI/VGA combined):
• DVI: digital
• VGA analog
• Keyboard/mouse
Connectable via USB (keyboard
not included in scope of deliv-
ery)
Operating system and
diagnostics software
Operating system Windows XP Professional MUI
preinstalled on hard disk and
enclosed on restore DVD, no
activation necessary
System-tested SIMATIC industrial
software
SIMATIC PC DiagMonitor
© Siemens AG 2007