Data Sheet for Product

Ethernet Fiber Switches
3360
s Industry, Inc.
Building Technologies Division
s
Data Sheet
Fire Safety Products
FACP Accessories
Multi-Mode and Single-Mode
*
Ethernet Fiber Switch
Model SCALANCE X204-2 and SCALANCE X204-2LD
ARCHITECT AND ENGINEER SPECIFICATIONS
Product Overview
The SCALANCE X204-2series of Ethernet Fiber
Switches from Siemens
Fire Safety are used to
maintain a Class X (Style 7) ring configuration or
Class B (Style 4) wiring configuration for
communication between Siemens fire-alarm
control panels (FACPs) and the system-equipped
buildings within a campus that contain a Siemens
fire-with-voice network:
the Multi-Mode Switch is Model SCALANCE X204-2
the Single-Mode Switch
*
is Model SCALANCE X204-2LD
All required monitoring for ring-configuration
durability of FACPs on the network are monitored
via Style 7 and Style 4. Specifically, the Style 7
configuration will automatically restore the
Trouble
event condition, if the fault is corrected.
Any ring failure is immediately reported via the
Simple Network Management Protocol (SNMP).
Each Ethernet fiber switch, which obtains its
primary power from a 24-Volt,
UL Listed power
supply, provides connectors for the fiber cable -
as well as four (4) R
J45, 100Base-T ports.
Temperature and Humidity Range
The Ethernet Fiber Switches are UL 864 9
th
Edition Listed for indoor, dry locations within a
temperature range of 120
+
/
-
F (49
+
/
-
C) to 32
+
/
-
F (0
+
/
-
C) and a relative humidity of 93
+
/
-
2% at a temperature of 90
+
/
-
F (32
+
/
-
C).
Related Documentation
Product
Data Sheet Number
Network CC 5068
Desigo® CC 5082
Virtual Network Tunnel 6362
Cerberus
®
DMS
9300
PAD-4 NAC Extender 3363
PAD-3 NAC Extender 3362
Used for fiber-optic communications with Siemens
Management Stations and FireFinder® XLS/V systems
Virtual Network Tunnel (VNT) is the source in fiber-optic
communication for FireFinder XLS/V
Single-mode
*
Ethernet Fiber Switches are only for use with VNTs
Supervision to Siemens Management Stations and FireFinder®
XLS/V via the Simple Network Management Protocol (SNMP)
`Class X’ (Style 7) ring configuration or
`Class B’ (Style 4) wiring configurations
VNT Style 7 only
Four (4) Ethernet IP ports
Two (2) sets of fiber ports
Four connections total
Two connections (in / out) per port
Four (4) pin, plug-in terminal blocks for primary power
UL Listed as a System Control Unit Accessory
SCALANCE
X204-2 Series
*
NOTE: The Single-Mode Ethernet Fiber Switch,
Model
SCALANCE X204-2LD
, has only been tested for
use with the Virtual Network Tunnel (VNT).

Summary of content (2 pages)