Manual and User Guide
Table Of Contents
- TABLE 1
- Figure 1
- INSTALLATION CODES
- CODES D'INSTALLATION
- TO TURN GAS OFF TO APPLIANCE
- COMMENT COUPER L’ADMISSION DE GAZ
- L’APPAREIL
- The minimum vent system for horizontal termination must consist of:
- The maximum horizontal vent system consists of:
- The minimum vent system for horizontal termination must consist of:
- The maximum horizontal vent system consists of:
- The minimum vent system for horizontal termination must consist of:
- The maximum horizontal vent system consists of:
- The minimum vent system for horizontal termination must consist of:
- The maximum horizontal vent system consists of:
- The minimum vent system for horizontal termination must consist of:
- The maximum horizontal vent system consists of:
- The maximum vertical system consists of:
- Apply RTV high temperature
- sealant around male pipe.
- 3.3.9 PRIMARY AIR ADJUSTMENT / AJUSTEMENT DE L'AIR PRIMAIRE
- CORRECTIVE ACTION
- SYMPTOM
- 1. Weak or improperly located pilot flame
- 2. Defective thermocouple
- 3.Thermocouple not installed properly
- 4. Open wire connection in pilot circuit
- 5. Defective Valve
- 1. Loose or defective connections
- III. Main burner will not light
- 1. Valve control off
- 2. Blockage at the burner (line, orifice, or ports)
- 3. Defective remote
- 4. Defective wiring or connections
- 5. Defective Valve
- I. Soot deposits
- 1. Air inlet blocked or restricted
- 2. Vent system is restricted or inadequate
- 3. Logs are sooting up
- V. Flame burns blue and lifts off burner
- 1. Insufficient combustion air being supplied
- 2. Manifold pressure set too high
- 3. Vent system restricted
- VI. Main flame does not burn properly
- VII. Flames impinge on firebox top
- 1. Vent system is restricted or inadequate
- 2. Manifold pressure too high
- 8.0 LABEL INFORMATION
- WARNING
- Electrical Grounding Instructions
- APPENDIX A (AMERICAN FLAME VALVE INFORMATION)
- APPENDIX A (Continued)
- APPENDIX B (NG – LP CONVERSION KITS)
Page 20 of 54
3.3.3 DIRECT VENT INFORMATION / DIRECT VENT D'INFORMATION
The unit must be connected to listed 2-ply aluminium venting, 4” flex vent on the exhaust side and
listed 7” flex vent on the air intake side or can be used with Security Venting, Dura-Vent 4” x 6-5/8”
with the use of Dura-Vent adapters part #’s 0924N3 & P574, Selkirk Direct-Temp Venting with
adapter Part #1604247B, ICC venting with adapter or Metal-Fab direct venting with the use of Metal-
Fab adapter part # 4DDA . Install the vent components according to the manufacturer's instructions
being sure to use spacers (see Figure 5) every 5’ to ensure correct spacing is maintained between air
intake and exhaust. Slope horizontal pipe at least 1/4" (6 mm) rise per foot of horizontal run away
from the fireplace. Allow 1" (25 mm) clearance to the vent. Refer to the graph for allowable vent
configurations. Be sure to ensure that termination area allows enough room for adequate combustion
and ventilation air and that the flow of combustion and ventilation air is not obstructed.
L'appareil doit être connecté à cotée 2 couches d'aluminium ventilation , 4 "flex évent sur le côté de
l'échappement et répertoriés 7 " flex évent sur le côté d'admission d'air ou peut être utilisé avec
sécurité ventilation , Dura-Vent 4 "x 6-5 / 8 " avec l'utilisation d'adaptateurs Dura -Vent 0924N3 &
P574 partie les # 's , Selkirk Direct -Temp évacuation avec adaptateur #1604247B, ICC évacuation
avec adaptateur ou Metal-Fab évacuation directe à l'utilisation de Metal-Fab adaptateur partie #
4DDA . Installez les composants de ventilation selon les instructions du fabricant en veillant à utiliser
des entretoises ( voir figure 5) tous les 5 ' pour assurer un espacement correct est maintenu entre
l'apport d'air et l'échappement. Pente tuyau horizontal d'au moins 1/4 " ( 6 mm ) par pied de course
horizontale loin du foyer . Laisser 1 " ( 25 mm) à l'évent . Reportez-vous au graphique de
configuration de l'évacuation admissibles . Veillez à ce que la zone de terminaison permet assez de
place pour combustion et l'air de ventilation et que le débit de combustion et de l'air de ventilation
n'est pas obstruée.
NOTE
If at any time the vent-air intake piping is dismantled, use the vent manufacturer’s
instructions and the sealing instructions for reassembly.
Si à tout moment de la tuyauterie d'admission d'air de ventilation est démontée, utilisez
la ventilation instructions du fabricant et les instructions d'étanchéité pour le
remontage
Figure 5
This appliance’s venting system is room sealed or Direct Vent. This means that it does not require
room air for combustion but draws air from outside the building.
USE OF COUPLERS – WITH FLEX PIPE
In the event of a puncture of the vent pipe or if an extension is needed couplers may be used. High
temperature sealant shall be applied to the ends of the coupler and the coupler shall then be inserted
into the flex vent. Use 3 #8 x ½” hex head sheet metal screws on each end of the joint to fasten the
coupler to the venting.