Manual and User Guide
Table Of Contents
- TABLE 1
- Figure 1
- INSTALLATION CODES
- CODES D'INSTALLATION
- TO TURN GAS OFF TO APPLIANCE
- COMMENT COUPER L’ADMISSION DE GAZ
- L’APPAREIL
- The minimum vent system for horizontal termination must consist of:
- The maximum horizontal vent system consists of:
- The minimum vent system for horizontal termination must consist of:
- The maximum horizontal vent system consists of:
- The minimum vent system for horizontal termination must consist of:
- The maximum horizontal vent system consists of:
- The minimum vent system for horizontal termination must consist of:
- The maximum horizontal vent system consists of:
- The minimum vent system for horizontal termination must consist of:
- The maximum horizontal vent system consists of:
- The maximum vertical system consists of:
- Apply RTV high temperature
- sealant around male pipe.
- 3.3.9 PRIMARY AIR ADJUSTMENT / AJUSTEMENT DE L'AIR PRIMAIRE
- CORRECTIVE ACTION
- SYMPTOM
- 1. Weak or improperly located pilot flame
- 2. Defective thermocouple
- 3.Thermocouple not installed properly
- 4. Open wire connection in pilot circuit
- 5. Defective Valve
- 1. Loose or defective connections
- III. Main burner will not light
- 1. Valve control off
- 2. Blockage at the burner (line, orifice, or ports)
- 3. Defective remote
- 4. Defective wiring or connections
- 5. Defective Valve
- I. Soot deposits
- 1. Air inlet blocked or restricted
- 2. Vent system is restricted or inadequate
- 3. Logs are sooting up
- V. Flame burns blue and lifts off burner
- 1. Insufficient combustion air being supplied
- 2. Manifold pressure set too high
- 3. Vent system restricted
- VI. Main flame does not burn properly
- VII. Flames impinge on firebox top
- 1. Vent system is restricted or inadequate
- 2. Manifold pressure too high
- 8.0 LABEL INFORMATION
- WARNING
- Electrical Grounding Instructions
- APPENDIX A (AMERICAN FLAME VALVE INFORMATION)
- APPENDIX A (Continued)
- APPENDIX B (NG – LP CONVERSION KITS)
Page 22 of 54
Security Venting
The minimum vent system for horizontal termination must consist of:
Dura-Vent adapter Part # 0924N3 directly on top of unit
15” (305mm) vertical length of vent
90 degree elbow
15" (305 mm) horizontal length of vent
Wall thimble part #IMC1082A
Horizontal termination cap SV4CHC
The maximum horizontal vent system consists of:
Dura-Vent adapter Part # 0924N3 directly on top of unit
34' (10363 mm) vertical length directly on top of the stove
4 - 90 degree elbows
20' (6096 mm) maximum horizontal length
Wall thimble part# IMC1082A
Horizontal termination cap SV4CHC
The maximum vertical system consists of:
Dura-Vent adapter Part # 0924N3 directly on top of unit
Up to 34' (10363 mm) of vertical length
Fire stop
Flashing
Collar
Termination cap part # SV4CGV
Use a ceiling fire stop when penetrating a ceiling or floor. Use a wall thimble when penetrating an
inside or outside wall. Vent terminals shall not be recessed into a wall or siding.
Metal-Fab Venting
The minimum vent system for horizontal termination must consist of:
Metal-Fab adapter Part # 4DDA directly on top of unit
15” (305mm) vertical length of vent
90 degree elbow
15" (305 mm) length horizontally
Wall thimble part #IMC1082A
Horizontal termination cap 4DHT
The maximum horizontal vent system consists of:
Metal-Fab adapter Part # 4DDA directly on top of unit
34' (10363 mm) vertical length directly on top of the stove
4 - 90 degree elbows
20' (6096 mm) maximum horizontal length
Wall thimble part# IMC1082A
Horizontal termination cap 4DHT
The maximum vertical system consists of:
Metal-Fab adapter Part # 4DDA directly on top of unit
Up to 34' (10363 mm) of vertical length
Fire stop
Flashing
Collar
Termination cap part # 4DVT