Manual and User Guide
Table Of Contents
- TABLE 1
- Figure 1
- INSTALLATION CODES
- CODES D'INSTALLATION
- TO TURN GAS OFF TO APPLIANCE
- COMMENT COUPER L’ADMISSION DE GAZ
- L’APPAREIL
- The minimum vent system for horizontal termination must consist of:
- The maximum horizontal vent system consists of:
- The minimum vent system for horizontal termination must consist of:
- The maximum horizontal vent system consists of:
- The minimum vent system for horizontal termination must consist of:
- The maximum horizontal vent system consists of:
- The minimum vent system for horizontal termination must consist of:
- The maximum horizontal vent system consists of:
- The minimum vent system for horizontal termination must consist of:
- The maximum horizontal vent system consists of:
- The maximum vertical system consists of:
- Apply RTV high temperature
- sealant around male pipe.
- 3.3.9 PRIMARY AIR ADJUSTMENT / AJUSTEMENT DE L'AIR PRIMAIRE
- CORRECTIVE ACTION
- SYMPTOM
- 1. Weak or improperly located pilot flame
- 2. Defective thermocouple
- 3.Thermocouple not installed properly
- 4. Open wire connection in pilot circuit
- 5. Defective Valve
- 1. Loose or defective connections
- III. Main burner will not light
- 1. Valve control off
- 2. Blockage at the burner (line, orifice, or ports)
- 3. Defective remote
- 4. Defective wiring or connections
- 5. Defective Valve
- I. Soot deposits
- 1. Air inlet blocked or restricted
- 2. Vent system is restricted or inadequate
- 3. Logs are sooting up
- V. Flame burns blue and lifts off burner
- 1. Insufficient combustion air being supplied
- 2. Manifold pressure set too high
- 3. Vent system restricted
- VI. Main flame does not burn properly
- VII. Flames impinge on firebox top
- 1. Vent system is restricted or inadequate
- 2. Manifold pressure too high
- 8.0 LABEL INFORMATION
- WARNING
- Electrical Grounding Instructions
- APPENDIX A (AMERICAN FLAME VALVE INFORMATION)
- APPENDIX A (Continued)
- APPENDIX B (NG – LP CONVERSION KITS)
Page 31 of 54
J= Clearance to nonmechanical 6 in (15cm) for appliances ≤10,000 6 in (15cm) for appliances ≤10,000
air supply inlet to building or Btuh (3kW), 12 in (30 cm) for Btuh (3kW), 9 in (23 cm) for
the combustion air inlet to appliances >10,000 Btuh (3kW) and appliances >10,000 Btuh (3kW0 and
any other appliance ≤100,000 Btuh (30kW), 36 in (91 cm) ≤50,000 Btuh (15kW), 12 in (30cm)
for appliances >100,000 Btuh (30kW) for appliances >50,000 Btuh (15kW0
K= Clearance to a mechanical 6 ft (1.83 m) 3 ft (91 cm) above if within 10ft
air supply inlet (3 m) horizontally
L= Clearance above paved sidewalk 7 ft (2.13 m) †
or paved driveway located on
public property *
M= Clearance under veranda, 12 in (30 cm) ‡
porch deck or balcony *
0” 0”
3” 3”
1 In accordance with th
e current CSA B149.1,
Natural Gas and Propane Installation Code
2 In accordance with the current ANSI Z223.1 /
NFPA 54, National Fuel Gas Code
† A vent shall not terminate directly above a
sidewalk or paved driveway that is located
between two single family dwellings and
serves both dwellings
‡ Permitte
d only if veranda, porch, deck or
balcony is fully open on a minimum of two
sides beneath the floor
* For clearances not specified in ANSI Z223.1 /
NFPA 54 or CSA B149.1
one of the following
shall be indicated
a). A minimum clearance value determined by
testing in accordance with section 2.23.5, or:
b). A reference to the following footnote:
“Clearance in accordance with local installation
codes and the requirements of the gas supplier.”
24” 24”