- The minimum vent system for horizontal termination must consist of:
- The maximum horizontal vent system consists of:
- The minimum vent system for horizontal termination must consist of:
- The maximum horizontal vent system consists of:
- The minimum vent system for horizontal termination must consist of:
- The maximum horizontal vent system consists of:
- The minimum vent system for horizontal termination must consist of:
- The maximum horizontal vent system consists of:
- The minimum vent system for horizontal termination must consist of:
- The maximum horizontal vent system consists of:
- The maximum vertical system consists of:
- Apply RTV high temperature
- sealant around male pipe.
- 3.3.9 PRIMARY AIR ADJUSTMENT / AJUSTEMENT DE L'AIR PRIMAIRE
- CORRECTIVE ACTION
- SYMPTOM
- 1. Weak or improperly located pilot flame
- 2. Defective thermocouple
- 3.Thermocouple not installed properly
- 4. Open wire connection in pilot circuit
- 5. Defective Valve
- 1. Loose or defective connections
- III. Main burner will not light
- 1. Valve control off
- 2. Blockage at the burner (line, orifice, or ports)
- 3. Defective remote
- 4. Defective wiring or connections
- 5. Defective Valve
- I. Soot deposits
- 1. Air inlet blocked or restricted
- 2. Vent system is restricted or inadequate
- 3. Logs are sooting up
- V. Flame burns blue and lifts off burner
- 1. Insufficient combustion air being supplied
- 2. Manifold pressure set too high
- 3. Vent system restricted
- VI. Main flame does not burn properly
- VII. Flames impinge on firebox top
- 1. Vent system is restricted or inadequate
- 2. Manifold pressure too high
- 8.0 LABEL INFORMATION
- WARNING
- Electrical Grounding Instructions
- APPENDIX A (AMERICAN FLAME VALVE INFORMATION)
- APPENDIX A (Continued)
- APPENDIX B (NG – LP CONVERSION KITS)
Page 42 of 54
B. Defective safety circuit
1. Loose or defective connections
1. Check continuity, tighten wiring or
connections, and repair
III. Main burner will not light
A. Valve / Switches
1. Valve control off
1. Turn to “ON” position
2. Blockage at the burner (line,
orifice, or ports)
2. Check and clean
3. Defective remote
1. Conduct a continuity test or jumper wire
test and replace if defective, check
batteries
4. Defective wiring or connections 2. Conduct a test with a jumper wire and
repair as required
5. Defective Valve
3. Contact service technician
I. Soot deposits
1. Air inlet blocked or restricted
1. Clean air inlets
2.
Vent system is restricted or
inadequate
2. Confirm venting & termination are those
which are approved with the appliance
3. Logs are sooting up 3. Check manual for correct log placement
V. Flame burns blue and lifts
off burner
1. Insufficient combustion air being
supplied
1. Ensure that no foreign material blocks air
inlets. Ensure the vent is adequate
2. Manifold pressure set too high
2. Check manifold pressure
3. Vent system restricted
3. Check vent system
VI. Main flame does not burn
properly
1. Incorrect vent or termination
used.
1. Confirm venting & termination are those
which are approved with the appliance
VII. Flames impinge on firebox
top
1.
Vent system is restricted or
inadequate
1. Correct flue as required
2. Manifold pressure too high
2. Check manifold pressure as required