14.5 Option board with 2 serial outputs (24VDC power supply)
This option board does not require any programming. By default the time is
the local time dened in the Sigma, with 1.2-second impulses, and the line is
stopped.
Impulse generated from internal power (24V),
Connect the clock lines to the outputs A and B.
The current can be adjusted (from 50 to 100 mA) for each line, using the
potentiometer next to each terminal strip.
The (10 K) resistor on each output terminal strip is designed to prevent the
“line open” alarm message. It must be left if the line is not used.
Set the lines to “On” in the “Time outputs” technician menu (see page 36).
Output A
Output B
Résistor
(10 k)
Current setting
14.6 Option board with 2 serial outputs (48VDC power supply)
This option board does not require any programming. By default the time is
the local time dened in the Sigma, with 1.2-second impulses, and the line is
stopped.
Impulse generated from isolated external power 40-50V.
Connect the clock lines to the outputs A and B and, if needed, the power
supply to the external power input. The terminal block on the left side of the
card used to make the connection of the internal supply if other such option
cards are used.
The current can be adjusted (from 50 to 100 mA) for each line, using the
potentiometer next to each terminal strip.
The (10 K) resistor on each output terminal strip is designed to prevent the
“line open” alarm message. It must be left if the line is not used.
Set the lines to “On” in the “Time outputs” technician menu (see page 36).
Power supply
0
+48VDC
Output A
Output B
Power input/
output
Résistor
(10 k)
Current setting