User Manual

REFERENCE TABLE 1 for LED indication Mode de nitions. Using a 1/8
diameter tool press and release the Test /Hush button. If the Detector is
operating properly you will hear 4 quick beeps followed by 5 seconds of
silence, followed by 4 more quick beeps. Red Led Blinks once a second
between Temporal patterns. After second beep CO detector will reset
back to Normal (standby) mode. It may take up to 30 seconds for CO
detector to properly reset and be ready to retest when programming
Silent Call receivers.
Testing Signal Strength:
This test should be performed before installation to determine a strong
communication path with the Silent Call Receiver and after installation
is complete. Also, the owner/user should test the unit’s signal strength
at least weekly.
1. Have someone monitor the Receiver you wish to alert.
2. Depress and hold the detector’s TEST/Hush button. If the detector
has not previously detected a low battery condition and it is within
proper sensitivity limits, the detector should immediately transmit
an alarm signal to the receiver. The built-in horn will start to sound
about 2.5 seconds after depressing the button.
3. The Silent Call Receiver shall annunciate a CO Alert in accordance
with speci c receiver used.
4. When the Silent Call Receiver has received the test signal, release
the TEST button. The horn will stop and approximately 16 seconds
after releasing the test switch the receiver will stop alerting CO.
5. If the receiver does not respond as noted, check the polarity of the
battery and be sure it is fresh. If this is an initial installation, try