Specifications

Programming
151295 7-21
SLC Loop
(cont.)
SWITCH
(cont.)
RESET
System-level switch provides an alternate way to reset
the system; same effect as pressing the Reset key.
PAS_ACK
Positive acknowledge switch. This switch must be used
in zones programmed as Positive Alarm Sequence (see
Table 7-1).
If an acknowledge switch closes when an alarm or
trouble condition is not already in progress, a trouble
will occur.
You must use a UL listed normally open, momentary
switch type. The switch must be rated at 5V, 100 mA
(minimum) and be used with an EOL resistor for
supervision.
ZN_AUX1
Latching Use these switch types if you want to monitor special
zone-level conditions.
Non Latching
ZN_AUX2
Latching
Non Latching
SYS_AUX1
Latching Use these switch types if you want to monitor special
system-wide conditions.
Non Latching
SYS_AUX2
Latching
Non Latching
DETECT SW
Used to monitor conventional 4-wire detectors, a
contact closure will generate a detector alarm event.
TAMPER
Latching Performs identically to a supervisory switch, but will be
indicated as a tamper switch on the LCD annunciator.
Non Latching
MAN REL
Latching Manual release switch, typically a pull station.
Non Latching
ILOCK
Latching Interlock release switch input.
Non Latching
RELAY
OUTPUT PT Select Group
Output Point, a general use relay type. Use for
applications requiring a relay, such as elevator recall.
AUX RESET
Use for auxiliary power, resettable applications. See
Section 4.12.2.3 to learn how this option operates.
AUX DOOR
Use for auxiliary power, door holder applications. For
example, if you were using an auxiliary power supply
for door holders, you would use this option. See Section
4.12.2.1 for a description of how this option operates.
Table 7-4: Point Programming
Module Type
Type
Selection
Function
Latching
Option
Comments