4.14 Remote Station Applications
4.14.1 Keltron Model 3158 Installation
The control panel is compatible with Keltron Model 3158, used for direct connection to a
Keltron receiver. The 3158 reports alarms, supervisories, and troubles. The 3158 is intended
for connection to a polarity reversal circuit of a remote station receiving unit having
compatible ratings.
The steps for connecting the 3158 to the control panel. Refer to the 3158 installation
instructions for complete information.
1. Wire the 3158 to the control panel as shown in the connection list and Figure 4-33.
2. Wire the 3158 within 20 feet of the control panel. Wiring must be enclosed in conduit.
3. Program control panel Relay 2 for alarm.
4. Program NAC circuit 2 for alarm.
5. Program NAC circuit 1 for supervisory non latching.
Note: NACs must be programmed for continuous and non-silencing.
Figure 4-33 Keltron 3158 Connection to Control Panel
A 5496 Must Be Used
for NAC Circuits
Example
Intended for connection to a
polarity reversal circuit of a
remote station receiving unit
having compatible ratings.