System information

Model 5700 Installation and Operation Manual
8-10 151295
8.4 Operation Mode Behavior
The control panel can be in one of seven conditions at any given moment: Normal, Alarm,
Prealarm, Supervisory, Trouble, Silenced, and Reset. Table 8-2 describes the behavior of the
panel in each of these modes.
Table 8-2: Operation Modes of FACP
Operation
Mode
Occurs When System Behavior In This Mode You Can
Normal No alarm or
trouble con-
dition exists and
menus are not in
use.
SYSTEM POWER LED is on.
The All Systems Normal display indicates
that the system is in normal mode.
The current date and time display on the
last line of the LCD.
Enter the appropriate code, or rotate the key to
activate the Main Menu.
Alarm A smoke
detector goes
into alarm or a
pull station is
activated.
The dialer seizes control of the phone line
and calls the central station.
The on-board annunciator sounds a loud,
steady beep (any notification devices
attached to the system will also sound).
GENERAL ALARM LED flashes.
The LCD displays a screen similar to this
one.
Press the down arrow to view the alarm. A screen
similar to this one displays.
Press and enter an access code (or activate
the key) to silence the annunciator (and any
notification devices attached to the system).
When the alarm condition clears, press and
enter a code (or activate the key) to restore the panel
to normal.
Supervisory The system
detects a
supervisory
condition.
The dialer seizes control of the phone line
and calls the central station.
The on-board annunciator sounds a loud,
pulsing beep in the sequence one second
on, one second off.
SUPERVISORY LED flashes.
The LCD displays a screen similar to this
one.
Press (down arrow) to view the supervisory
condition. A screen similar to this one displays.
Press and enter an access code (or activate
the key) to silence the annunciator.
Once the supervisory condition has been corrected,
the system will restore itself automatically.