System information

System Operation
151295 8-11
Trouble A system trouble
condition
occurs.
The dialer seizes control of the phone line
and calls the central station.
The on-board annunciator sounds a loud,
pulsing beep in the sequence one second
on, nine seconds off.
SYSTEM TROUBLE LED flashes.
The LCD displays a screen similar to this
one.
Press (down arrow) to view the trouble. A screen
similar to this one displays.
Press and enter an access code (or activate
the key) to silence the annunciator.
Once the trouble condition has been fixed, the
system will restore itself automatically.
Prealarm A single detector
trips in a 2-
Count zone. (2-
Count means
two detectors
must trip before
an alarm is
reported.)
Touchpad PZT beeps.
The LCD displays a screen similar to this
one.
Press (down arrow) to view the prealarm. A
screen similar to this one displays.
All system operations are available in this mode.
Reset
The
button is pressed
followed by a
valid code or
rotation of the
key.
All LEDs are on briefly then the LCD
displays "ALARM RESET IN
PROGRESS". If the reset process
completes normally, the date and time
normal mode screen displays.
Menus are not available during the reset process.
Silenced An alarm or
trouble
condition has
been silenced
but still exists.
To silence
alarms and
troubles, press
followed
by the Installer
or User Code or
rotate the key.
SYSTEM SILENCE LED is on. SYSTEM
TROUBLE, SUPERVISORY or
GENERAL ALARM LED (depending on
condition) is on. The annunciator (and any
notification devices attached to the
system) will be silenced.
Press (down arrow) to view the location of the
alarm or trouble. When the condition no longer
exists, the SYSTEM SILENCED and SYSTEM
TROUBLE LED, SUPERVISORY or GENERAL
ALARM LEDs turn off.
Table 8-2: Operation Modes of FACP
Operation
Mode
Occurs When System Behavior In This Mode You Can