8.5 Releasing Operations
This control panel supports two types of releasing, Double Interlock Zone, and Single
Interlock Zone. The Double Interlock Zone operation requires an interlock switch input in the
system, and the Single Interlock does not. An interlock switch is typically a dry-contact
pressure switch.
When a Single or Double Interlock Zone releasing is selected the system is will automatically
default the 5496 Intellingent Power Module in the following system parameters:
Note: The defaults created can be modified through programming if desired.
Output Group 2 is created. Output Group 2 will be defaulted as an "Alarm" output group
for all releasing zones. NAC [01:001] is assigned to Output Group 2.
Output Group 3 is created. Output Group 3 will be defaulted as an "Pre-Alert" output
group for all releasing zones. NAC [01:002] is assigned to Output Group 3.
Output Group 4 is created. Output Group 4 will be defaulted as a "Release" output group
for all releasing zones. NAC circuit [01:003] is assigned to Output Group 4.
Note: The installer must define which input points will be used for detectors, manual release switches, or inter-
lock/pressure switches.
Figure 8-4 Wiring Configuration for Solenoid
Important!
These releasing functions can only be done if the system has a 5496 intelligent power module included.
Manufacturer Part Number Rating
Asco
T8210A107 24 VDC
8210G207 24 VDC
Important!
Detectors must be installed at 0.7 times the linear spacing as described in NFPA 72, Chapter 2.
The Model 7641
Must be located
at the solenoid.