System information

System Operation
151295 8-5
8.3.5 Conduct an Indicator Test
The indicator test checks the annunciator LEDs, PZT, and LCD display.
1. From the Main Menu, press for System Tests.
2. Press for Indicator Test. The system turns on each LED several times, beeping the
PZT as it does so. At the same time it scrolls each available character across the LCD. A
problem is indicated if any of the following occurs:
An LED does not turn on;
You do not hear a beep;
All four lines of the LCD are not full.
This test takes approximately 15 seconds to complete. You can press any key to end manually
while the test is still in progress. When the test ends, you will be returned to the <Test Menu>.
8.3.6 Conduct a Walk Test
1. From the Main Menu, press for System Tests.
2. Select for Walk Test-No Rpt. The LCD will display "WALK TEST STOPPED" on
Line 1 and "ENTER = start test" on Line 2. If you select this option, central station report-
ing will be disabled while the test is in progress.
Select for Walk Test-with Rpt. The LCD will display "WALK TEST STOPPED" on
Line 1 and "ENTER = start test" on Line 2. If you select this option, central station report-
ing will occur as normal during the walk test.
The panel generates a TEST report to the central station when the walk test begins. During
a walk test, the panel’s normal fire alarm function is completely disabled, placing the
panel in a local trouble condition. All zones respond as 1-Count zones (respond when a
single detector is in alarm) during a walk test. Each alarm initiated during the walk test
will be reported and stored in the event history buffer.
3. Enter the number of seconds you want the notification appliance circuits to sound. From 6
to 180 seconds.
4. Press to end the walk test. The system will reset. The panel will send a "TEST
RESTORE" report to the central station.
If you do not end the walk test manually within 60 minutes, it will end automatically. If an
alarm or pre-alarm condition is occurring in the system, you will not be able to enter the walk
test.
Note: the panel does not do a full 30 second reset on resettable power outputs. As soon as the device is back to
normal, the panel is ready to go to the next device.
IMPORTANT!
If any alarm verification zones are being used, the user will be asked if they wish to
disable alarm verification during walk test. This occurs for either walk test option.