FocalPoint™ System Utilities User’s Guide — FocalPoint™ Receivers Gateway Installation & Operation Manual Copyright © 2009 All Rights Reserved Published in U.S.A. P/N: 53251 A ECN: 08-901 12 Clintonville Road, Northford, CT 06472, 203-484-7161, FAX 203-484-7118 www.gamewell-fci.
IMPORTANT INFORMATION This manual is designed for use by factory trained installers and operators of the Gamewell/FCI FocalPoint System. All illustrations, functional descriptions, operating and installation procedures, and other relevant information are contained in this manual. The contents of this manual are important, and the manual must be kept with the system at all times.
WIRING CONSIDERATIONS SYSTEM RE-ACCEPTANCE TEST A Gamewell/FCI fire alarm control panel contains powerlimited circuits. You cannot connect external sources of power to these circuits without invalidating their approval. Verify that wiring sizes are adequate for all initiating device and notification appliance circuits. Most devices cannot tolerate more than a 10% drop from the specified voltage.
LIMITATIONS OF FIRE ALARM SYSTEMS Gamewell/FCI recommends that smoke and/or heat detectors be located throughout the protected premises following the recommendations of the current edition of the National Fire Protection Association Standard 72, the National Fire Alarm Code (NFPA 72), manufacturer’s recommendations, State and local codes, and the recommendations contained in the Guide for the Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers.
Table of Contents Section 1 About Receivers Gateways..................................................................................... 7 1.1: FPT Receivers Gateway Description .............................................................................................................7 1.2: FPT Receivers Gateway System Architecture ...............................................................................................7 Figure 1.1 Receivers IP Network Architecture Diagram .........................
Table of Contents 2.5.6: VisorALARM Device Addressing and Supervision..........................................................................21 2.5.7: Device Addresses Reported ...............................................................................................................21 Section 3 Receivers Gateway Installation and Configuration ............................................ 23 3.1: Receivers Gateway Installation Overview..................................................................
Section 1 About Receivers Gateways 1.1 FPT Receivers Gateway Description The Receivers Gateway (FPT-DACR-GW) acts as a bridge between the supported digital alarm receivers and the FocalPoint system. A Receivers Gateway processes information coming from a connected receiver and passes the information to FocalPoint components. A FocalPoint Workstation on the system will annunciate events from control panels to receivers using a DACT.
About Receivers Gateways Agency Listings FocalPoint/ Receiver Gateway Telephone Digital Alarm Receiver Dialer FACP Ethernet Ethernet FocalPoint Components Figure 1.2 Receivers Telephone Architecture Diagram 1.3 Agency Listings NOTE: UL 864, 9th Edition—FocalPoint systems work with products that have been UL 864, 9th Edition listed as well as products that have not received UL 864, 9th Edition certification.
Environmental Requirements About Receivers Gateways Local • AHJ—Authority Having Jurisdiction National Fire Protection Association • NFPA 70—National Electrical Code • NFPA 72—National Fire Alarm Code • NFPA 101—Life Safety Code Underwriters Laboratories • UL-1076—In certified applications, the unit shall be installed in accordance with Proprietary Burglar Alarm Units and Systems, Fifth Edition Underwriters Laboratories Canada • CAN/ULC-S524-06—Standard for the Installation of Fire Alarm System
About Receivers Gateways 10 Related Documentation FocalPoint™ Receivers Gateway Installation & Operation Manual - P/N: 53251:Rev: A 9/8/09
Section 2 Digital Receivers Installation and Configuration 2.1 Digital Receiver Setup Guidelines The supported Digital receivers must be installed according to the following guidelines: • Receivers may be placed on a single Gateway or distributed among several. • A receiver may be attached to any available COM port on a Receiver Gateway capable UL or ULC listed computer, that is appropriate for use with fire protective signaling units.
Digital Receivers Installation and Configuration ADEMCO 685 Setup 2.2 ADEMCO 685 Setup 2.2.1 685 Cable Configuration NOTE: All connections must be no more than 20 feet in length and run in conduit. Use the following figure to configure the cable that connects the 685’s J103 port to a unused COM port on your Receiver Gateway capable Workstation computer. Figure 2.1 ADEMCO 685 Cable Connections 2.2.
ADEMCO 685 Setup Digital Receivers Installation and Configuration Once the ADEMCO 685 is connected to the Gateway, the Workstation will auto-create an icon for the 685 receiver. 685 site names will look similar to this: 685 DACR - #### (where #### is the account code for the panel that is dialing in). 685 panels generate a periodic test message. The Gateway uses that test message to supervise the site. 2.2.
Digital Receivers Installation and Configuration Radionics D6600 Setup 2.3 Radionics D6600 Setup Digital receivers must be installed according to the “Digital Receiver Setup Guidelines” on page 11. 2.3.1 D6600 Description The Receivers Gateway is the software interface between the Radionics receiver and the FocalPoint network monitoring system.
Radionics D6600 Setup Digital Receivers Installation and Configuration 2.3.3 D6600 Serial Communication Connection Use the following figure to configure the cable that connects the Radionics D6600’s COM3 port to a unused COM port on your Receiver Gateway capable Workstation computer. You can use a standard null modem cable to connect the Radionics D6600 to the Receivers Gateway.
Digital Receivers Installation and Configuration Radionics D6600 Setup Table 2.1 D6600/Receivers Gateway Configuration Settings D6600 Menu Item Menu Item Name/Description D6600 Value for WAS Configuration 6.3.7 Device 2 - Utilize COM3 RS-232 Automation 2.3.5 D6600 Configuration Device Addressing and Supervision The Receivers Gateway monitors digital alarm receivers for trouble conditions and reports these events to Workstations.
Silent Knight 9500/9800 Receiver Setup Digital Receivers Installation and Configuration 2.4 Silent Knight 9500/9800 Receiver Setup A Receiver Gateway capable Workstation is capable of monitoring 10 Silent Knight 9500/9800 digital alarm receiver’s devices reporting alarm and trouble information. Digital receivers must be installed according to the “Digital Receiver Setup Guidelines” on page 11. 2.4.
Digital Receivers Installation and Configuration Silent Knight 9500/9800 Receiver Setup 2.4.3 9500/9800 Receiver Settings Table 2.
Silent Knight 9500/9800 Receiver Setup Digital Receivers Installation and Configuration 2.4.7 9500/9800 Device IDs The Receivers Gateway reformats all devices reported by Silent Knight 9500/9800 receivers to fit the FocalPoint system format of an 8-character point ID. Since there is no actual node or sub-node located at the panel, the Gateway always pads the node/ sub-node position with zero spacers (001000). Each device ID reported through the receiver will begin this way.
Digital Receivers Installation and Configuration Teldat VisorALARM Receiver Setup 2.5 Teldat VisorALARM Receiver Setup VisorALARM is an IP Receiver which can receive event messages via IP networks from configured IP digital alarm control transmitters (IPDACTs). 2.5.1 VisorALARM Cable Configuration NOTE: All connections must be no more than 20 feet in length and run in conduit.
Teldat VisorALARM Receiver Setup Digital Receivers Installation and Configuration 2.5.4 VisorALARM Supported Formats The following format is supported: • ADEMCO Contact ID. 2.5.5 VisorALARM Communication Settings Recommended as Baud Rate=9600, Parity=N, Data Bits=8 and Stop Bits=1. 2.5.6 VisorALARM Device Addressing and Supervision Receivers Gateway monitors the VisorALARM for trouble conditions and reports them to connected Workstations.
Digital Receivers Installation and Configuration 22 Teldat VisorALARM Receiver Setup FocalPoint™ Receivers Gateway Installation & Operation Manual - P/N: 53251:Rev: A 9/8/09
Section 3 Receivers Gateway Installation and Configuration 3.1 Receivers Gateway Installation Overview NOTE: The Workstation and FPT Receivers Gateway must be logged into before any of its settings can be configured. A User that has the Security Option to configure settings needs to login to change an existing setting. The factory defined User “Admin” has such an Security Option.
Receivers Gateway Installation and Configuration Receivers Gateway Startup 3.3 Receivers Gateway Startup Step 1. Double click on the Receivers Gateway icon in the Windows system tray. The Receivers Gateway window displays. Step 2. From the Receivers Gateway window select File >Login. The User Login window displays. Step 3. Click on a User name in the Available Users list. Step 4. Type in the User’s password in the password field, and then click OK.
Receivers Gateway Network Communication Configuration Receivers Gateway Installation and Configuration 3.4.2 Receivers Gateway’s Port Configuration The Admin User creates a Network name and then adds a gateway. Network Names and gateway connections are created using the Configuration Tool which is launched from Workstation’s main menu Network Connection Configuration Procedure Step 1. Login to the Workstation. Step 2.
Receivers Gateway Installation and Configuration 26 Receivers Gateway Network Communication Configuration FocalPoint™ Receivers Gateway Installation & Operation Manual - P/N: 53251:Rev: A 9/8/09
Section 4 Receivers Gateway Reference Information 4.1 Layout of the Receivers Gateway Window The Receivers Gateway allows a FocalPoint Workstation to view events and other data originating from digital alarm control receivers. Events that occur on connected digital alarm control receivers’s devices will be reported to the Workstation and appear in the Events Box like any other FocalPoint system event.
Receivers Gateway Reference Information File Menu Descriptions 4.2 File Menu Descriptions 4.2.1 Login The Workstation or FPT Receivers Gateway software applications must be logged into before any of its settings can be configured. A User that has the Security Profile to change a password needs to login to change an existing User’s password or to add a User and their password. The factory defined User “Admin” has such an access level.
Appendix A: Radionics D6600 Internal Message Mapping The following table displays what messages will look like in the History Manager database: Table A.
Radionics D6600 Internal Message Mapping Table A.
Radionics D6600 Internal Message Mapping Table A.
Radionics D6600 Internal Message Mapping Table A.
Appendix B: Contact ID Reporting Formats The following table shows the Contact ID Reporting Formats for FocalPoint messages: Table B.
Contact ID Reporting Formats Table B.
Contact ID Reporting Formats Table B.
Contact ID Reporting Formats Table B.1 Contact ID Reporting Formats (Continued) 336 PRINT### G##PR### GROUP## Printer Local printer failure 337 ACPWR### G##AC### GROUP## Power Supply Exp. module DC loss - # 338 ACPWR### G##AC### GROUP## Power Supply Exp. module Low Batt - # 339 ACPWR### G##AC### GROUP## Power Supply Exp. module Reset - # 341 ACPWR### G##AC### GROUP## Power Supply Exp. module Tamper - # 342 ACPWR### G##AC### GROUP## Power Supply Exp.
Contact ID Reporting Formats Table B.1 Contact ID Reporting Formats (Continued) 384 RFBAT### G##RF### GROUP## Battery RF low battery - # 385 ZONE ### G##ZO### GROUP## Smoke Detector Smoke det. Hi sens - # 386 ZONE ### G##ZO### GROUP## Smoke Detector Smoke det. Lo sens - # 387 ZONE ### G##ZO### GROUP## Security Intrusion det. Hi sens - # 388 ZONE ### G##ZO### GROUP## Security Intrusion det.
Contact ID Reporting Formats Table B.
Contact ID Reporting Formats Table B.
Contact ID Reporting Formats Table B.
Contact ID Reporting Formats Table B.
Contact ID Reporting Formats 42 FocalPoint™ Receivers Gateway Installation & Operation Manual - P/N: 53251:Rev: A 9/8/09
Index A About 28 Ademco 685 Receiver 11 Cable Configuration - PC to 685 12 Communication Settings 12 Device Addressing 12 Device IDs 13 DIP Switch Settings 12 Jumper Settings 12 Parallel Printer 12 Site IDs 13 Supervision 12 Supported Formats 12 Architecture Gateway System 7 Shutting Down 24 S Shut Down Gateway 28 Silent Knight 9500/9800 Receiver 17 Cable Configuration 17 Device Addressing 18 Device IDs 19 Receiver Settings 18 Site IDs 18 Supervision 18 Supported Formats 17 V Version Information 28 E Ex
Index 44 FocalPoint™ Receivers Gateway Installation & Operation Manual - P/N: 53251:Rev: A 9/8/09
Manufacturer Warranties and Limitation of Liability Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that the Products manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free, under normal use and service, from defects in material and workmanship for a period of thirty six months (36) months from the date of manufacture (effective Jan. 1, 2009).
Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 USA 203-484-7161 fax 203-484-7118 www.gamewell-fci.