Model 5104B Fire Communicator Installation and Operations Manual Document 151053-L8 05/05/2014 Rev: F3 P/N 151053-L8-F3 ECN: 14-0068
Installation Procedure Adherence to the following will aid in problem-free installation with long-term reliability: Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing.
Contents Section 1 Introduction .............................................................................................................................................. 1-1 1.1 1.2 1.3 Feature .....................................................................................................................................1-1 Accessory Devices ...................................................................................................................1-1 About This Manual ....................
3.11.2 Supervised Notification Appliance Wiring ......................................................................3-16 3.12 Telephone Line Connections ..................................................................................................3-17 3.13 Model 5230 Installation ..........................................................................................................3-18 3.13.1 Mounting the 5230 .........................................................................................
151053-L8 Section 1 Introduction The Model 5104 is a low-cost fire communicator that meets the requirements for NFPA 72, UL 864, MEA, CSFM, and FM. 1.1 Feature • Six supervised fire zones, consisting of one Class A (Style D) and five Class B (Style B) zones. • Current limited loop power output for the Class B zone inputs. • Ground fault detection. • Built-in piezo sounder for trouble and supervisory conditions. • Reset/Silence switch that performs the following: 1 Silences troubles and alarms.
Model 5104B Installation Manual 151053-L8 much as possible, we have tried to organize the manual chronologically by the tasks that need to be performed. Please let us know if the manual does not meet your needs in any way. 1.3.1 How to Use This Manual In this manual, the following conventions are used: • Pages of the manual are numbered by section. For example, a page numbered as 5-1 is page 1 of Section 5. • Text in this type face indicates a 5230 display message:System Normal.
151053-L8 Section 2 Agency Requirements This section list all the requirements for the 5104 by agency. Install and maintain in accordance with NFPA 72. Detector spacing shall be in accordance to NFPA 72. End-of line relays and resistors shall be placed within the electrical box located and the end of the initiating circuit. Testing and maintenance should be performed according to NFPA 72. 2.
Model 5104B Installation Manual 2.2 151053-L8 FCC Warning Warning This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions: (1) This device may not cause radio interference, and (2) This device must accept any interference received, including interference that may cause undesired operation. 2.3 UL Requirements The 5104 is UL listed as a Control Unit for use in Central Station Fire-Protective Signaling Systems (UL864, NFPA 72).
151053-L8 Section 3 Installation This section contains information necessary to install the 5104 Fire Communicator and accessories. 3.1 3.2 Electrical Specifications Primary AC 120 Vrms @ 60Hz, 374 ma Total DC load 1.3 Amp Accessory Power 12 VDC @ 750 mA Phone Line Voltage 2.75 VDC min. Smoke Power 12 VDC @ 750 mA Battery Charging Voltage 13.8 VDC Minimum Low Battery Detection 10.
Model 5104B Installation Manual 3.3 151053-L8 Wiring Specifications Induced noise (transfer of electrical energy from one wire to another) can interfere with telephone communication or even cause false alarms. To avoid induced noise, follow these guidelines: • Isolate input wiring from high current output and power wiring. Do not pull one multi-conductor cable for the entire panel.
Installation 3.4 151053-L8 Panel Description This section describes the 5104 board components, including terminal strips, LEDs, Switches and cable connectors. See Figure 3-2.
Model 5104B Installation Manual 3.4.1 151053-L8 Terminal Description Table 3-1 lists the terminals by number and describes the terminals use.
Installation 3.4.2 151053-L8 LED Descriptions This section describes what each LED indicates. The 5104 has a total of seven LEDs, three are visible externally and four are visible only if the cabinet door is open. See Section 8 for additional information on LED operation. 3.4.2.1 Externally Visible LEDs (L3, L4, & L5) This section describes the three LEDs (one green and two yellow) that are visible externally through the window on the 5104 cabinet door. Refer to Table 3-2 and Figure 3-2.
Model 5104B Installation Manual 151053-L8 3.4.2.3 Overcurrent LED Indicators (L1 & L2) The 5104 has two red LEDs which indicate if excessive current is being drawn by a device connected to either the Accessory Power or Smoke Power circuits. Table 3-4 lists the two overcurrent LEDs and gives a description of them. See Figure 3-2 for LED locations.
Installation 3.5 151053-L8 Calculating Current Draw and Standby Battery This section should be used to help you determine the current draw and standby battery needs for your installation. 3.5.1 Worksheet Requirements The following steps must be taken when determining the 5104 current draw and standby battery requirements. Fill in the Current Draw Worksheet (Table 3-6) in section 3.5.2. For the 5104, the worst case current draw is listed in Table 3-6 for the panel and accessory devices.
Model 5104B Installation Manual 3.5.2 151053-L8 Current Draw Worksheet Use this worksheet to determine current requirements during alarm/battery standby operation.
Installation 3.6 151053-L8 Mounting the 5104 Cabinet Read the environmental specifications in Section 3.2 before mounting the 5104 cabinet. This will ensure that you select a suitable location. The panel should be accessible to main drop wiring runs. It should be mounted as close to the center of the building as possible and located within a secured area, but should be accessible for testing and service. When mounting on interior walls, use appropriate screw anchors in plaster.
Model 5104B Installation Manual 3.8 3.8.1 151053-L8 AC Connection Standard Transformer Connections The AC transformer is factory mounted into the control panel and is plugged onto the control panel as shown in Figure 3-4. The ground and the primary side of the transformer should be wired as shown in Figure 3-4 by a certified electrician. Green Ground Wire AC Plug Red Transformer Wires Figure 3-4 AC Transformer Connections 3.
Installation 151053-L8 3.10 Detector Installation 3.10.1 Class A (Style D) Zones Zones 1 is for a class A (style D) zone. It is intended for use with non-powered devices such as waterflow switches. Do NOT use smoke or duct detectors on Class A zones. Each class A zone is a four-wire circuit that allows an alarm to be detected even after a single open or ground fault occurs.
Model 5104B Installation Manual 151053-L8 3.10.2 Class B (Style B) Zones Zones 2 through 6 are class B (style B) fire zones. Each class B zone consists of a two-wire circuit that will detect the occurrence of an open in the loop, but may not be able to detect an alarm after such an occurrence. The detection of an open will cause the audible trouble signal to sound and the 5104 will report the trouble to the central station. Figure 3-7 shows how to wire a class B (style B) loop.
Installation 151053-L8 3.10.3 Four-Wire Smoke Detector Connection 4-wire smoke detectors must use a power supervision module. Connect four-wire smoke detectors as shown in Figure 3-8.
Model 5104B Installation Manual 151053-L8 3.11 Supplemental Notification Appliance Installation The Supplemental notification circuit supplies a DC output that can be used to power a DC audible device during an alarm condition. Pressing the reset / silence switch will silence the output. Refer to section 6.2.7, Step 14, to program the notification circuit’s supervision properties. 3.11.
Installation 151053-L8 3.11.2 Supervised Notification Appliance Wiring When using a supervised notification device any open or shorted wiring condition will be reported as a trouble. Figure 3-10 illustrates how to wire a supervised notification device to the control panel. Refer to Section 6.2.7 Step 14 to program the notification circuit’s supervision properties. Wheelock Model MB-G10-12-R 12 VDC Bell Model 7628 4.
Model 5104B Installation Manual 151053-L8 3.12 Telephone Line Connections The 5104 control panel connects to the phone lines with a 7860 cable, which plugs into an RJ31X phone jack. The telephone company will install an RJ31X phone jack if you request them. Both telephone lines must be installed to comply with NFPA 72. Wire the phone lines as shown in Figure 3-11.
Installation 151053-L8 3.13 Model 5230 Installation The optional 5230 remote annunciator provides both trouble and alarm annunciation, and a convenient means of English-language programming the system. Figure 3-12 Model 5230 Remote Annunciator. 3.13.1 Mounting the 5230 When installing the 5230 as a permanent component of the system it must be mounted to a dual gang electrical box. All wire runs must use 12 to 18 AWG wire with a maximum length of 1000 feet. The annunciator must be supervised.
Model 5104B Installation Manual 151053-L8 toward you. See Figure 3-13. Restraining Tabs Restraining Tabs Orientation Mark Wire Access Hole Mounting Holes Figure 3-13 Rear Mounting Plate 3. Set the desired ID for the 5230 by setting the dip switches (on = up) as follows: ID Number Dip Switch 1 Dip Switch 2 Dip Switch 3 Dip Switch 4 0* On On On On 1 Off On On On 2 On Off On On 3 Off Off On On * Not supervised 4.
151053-L8 Section 4 Add-on Fire Communicator Application The 5104 can be used to communicate the status of a larger or pre-existing (referred to as Host panel in this manual) fire control system that does not have a digital communicator. To configure the 5104 as an add-on communicator wire it as shown in Figure 4-1.
151053-L8 Section 5 5230 Operation This section contains information about the operation of the 5104 through a 5230 remote annunciator. 5.1 5230 Display Messages If the 5104 is not reporting, being programmed, and if no functions are being entered, the LCD will display the event of the highest priority.
Model 5104B Installation Manual 151053-L8 Table 5-1: 5230 LCD Messages and Meanings Message Meaning Trouble Remote # (1-3) One or more 5230 annunciators are in trouble. The 5230 ID number is indicated in the # place. EEPROM Sum Error Error during program mode. Low Battery Battery voltage is less than 10.2 VDC. Trouble Smk Pwr Smoke loop power is less than 10 V or an overcurrent condition exists. Bell Trouble Trouble condition on the notification circuit.
5230 Operation 151053-L8 Table 5-2: Touchpad Keystrokes and Their Task or Function Task or Function Keystroke Step. SILENCE STEP Used to advance to a different programming step while followed by the desired step number. in programming mode. In reference to any Refer to Section 6 for programming information. programming tasks this key will be referred to as the “Step” key. Perform upload or download to a remote computer. LOAD ENTER 4 Display Troubles. DISPLAY TRBL.
151053-L8 Section 6 Programming This section contains information pertaining to the programming of the 5104 with the 5230 Remote Annunciator. All programming is stored in an EEPROM (Electrically Erasable Read-Only Memory) chip, which is nonvolatile memory storage. The various areas of programming are referred to as programming steps. These steps are covered in greater detail in Section 6.2.5. 6.
Model 5104B Installation Manual 1. 2. 3. 151053-L8 Press 7. Press ENTER. Enter the Installer Code. 6.2.4 How to Exit Program Mode To exit program mode press 6.2.5 SILENCE STEP SILENCE STEP CLEAR CLEAR Step Programming All programming, for the 5104, done through the 5230 is done in steps. Each step programs a set parameter of the 5104, such as phone numbers, reporting formats, and zone functions. 6.2.
Programming 151053-L8 Special Character and Functions Some phone number require special characters or functions to dial the central station correctly. Table 6-2 lists the special character used for dialing a phone number and CIC (Carrier ID Code) codes. Table 6-2: Special Characters for Dialing Sequence Character Touchpad Inputs Pause * # Look for second dial tone. 6.2.6.2 DISABLE SHIFT RESET ALARM DISABLE SHIFT CLEAR MEMORY DISABLE SHIFT DIAL.
Model 5104B Installation Manual 151053-L8 Table 6-3: List of Programming Steps Step # Task Choices Default Step 4 3/1 Test Code 0 - 9, A, B, C, D, E 9 Sets the 3/1 reporting format code sent for a "Test Code". Use the Shift key plus digits 1 - 5 for letters A - E. Step 5 Low AC Hours 0 - 30 hrs* 3 Set the number of hours the control panel will wait to report a loss of AC power to the central station.
Programming 151053-L8 Table 6-3: List of Programming Steps Step # Task Choices Default Press any numeric-digit to toggle the selection from Yes to No. Step 13 Relay Alarm Yes or No No Yes = Bell circuit activates during alarm condition by the auxiliary relay. No = Bell circuit activates during a dialer failed condition. Press any numeric-digit to toggle the selection from Yes to No. Step 14 Relay Supervise Yes or No No Yes = Bell circuit is supervised (see Figure 310).
Model 5104B Installation Manual 151053-L8 Table 6-3: List of Programming Steps Step # Task Choices Default Set how zone 3 will report. Press any numericdigit to toggle the selection from Yes to No. Step 21 Report Sprnk #3 Yes or No No Yes = If you want to report troubles and alarms as a sprinkler (Supervisory), when using SIA format. No = If you want troubles and alarms to report as fires (Alarm). Note: Bells will only sound if “No” is select- ed. Set how zone 4 will report.
Programming 151053-L8 Table 6-3: List of Programming Steps Step # Step 26 Step 27 Task Account #1 Attempts #1 Choices 6-digits Default 105104 Enter six-digits for an account number. For accounts shorter than 6-digits use leading zeros before you enter account number, so that all six places are filled. For example, if the format requires a shorter account number, such as 3/1 enter 000123.
Model 5104B Installation Manual 151053-L8 Table 6-3: List of Programming Steps Step # Step 37 Step 38 Task Computer CIC Computer Phone Choices 1 to 8-digits 1 to 16-digits Default None Carrier Identification Code is the prefix that needs to be dialed before a phone number to access a particular long distance carrier. Use special characters to add pauses, #, *, and “look for second dial tone” characters into the phone number. See Table 6-2 for special characters.
Programming 151053-L8 Table 6-3: List of Programming Steps Step # Task Choices Default Press any numeric-digit to toggle the selection from Yes to No. Step 49 Add-on Dialer Yes or No No Yes = If the 5104 is used as an add-on communicator for a host panel. This tells the 5104 not to test the battery or earth ground, which could cause interference with the host panel. No = The 5104 will test battery and earth ground.
151053-L8 Section 7 Reporting The 5104 can transmit information in 5 different formats. This section describes the five basic reporting formats of the 5104 and the codes that they send to a central station receiver. Of these 5 formats some of the formats offer a more specific selection for that format. For example, you can select a 3/1 format that requires a 1400 or 2300 Hz handshake, or SIA format that can handle 8 of 20 events per call.
Model 5104B Installation Manual 7.2 151053-L8 Reporting Codes Table 7-2 list the events sent by the 5104 and the code that is sent for that event by the type of reporting format used.
Reporting 151053-L8 Table 7-2: Event and Reporting Code by Format SIA8 & 20 SK4/2 3/1 1400 &2300 BFSK14 & 23 Trouble Phone Line #1 LT1 31 Trouble Code FB 1 351 000 Restore Phone Line #1 LR1 35 Restore Code EB 3 351 000 Trouble Phone Line #2 LT2 32 Trouble Code FC 1 352 000 Restore Phone Line #2 LR2 36 Restore Code EC 3 352 000 Communications Failure Line #1 YC1 31 Trouble Code FB 1 351 000 Communications Restore Line #1 YK1 35 Restore Code EB 3 351 000 Communication
151053-L8 Section 8 Troubleshooting This section contains trouble shooting information for servicing the 5104. The following is a list of LED indications, 5230 LCD messages, and their meaning. Along with this information are possible causes of these problems and some solution. LED Indications 5230 LCD Messages Trouble Zone # Meaning Cause and Correction Trouble condition exist on the zone or zones indicated by # The device connected to this zone is in trouble. EOL problem on this loop.
Model 5104B Installation Manual LED Indications 5230 LCD Messages 151053-L8 Meaning Cause and Correction Bell Trouble Trouble condition on the notification circuit. Over current draw on the notification circuit. Missing or incorrect EOL on a supervised notification circuit. L6 Flashes Trouble Com 1 Event reports, auto test or manual test unable to report on line 1. Phone line voltage is O.K. but the panel was unable to communicate on line 1.
Silent Knight Fire Product Warranty and Return Policy General Terms and Conditions • • All new fire products manufactured by Silent Knight have a limited warranty period of 36 months from the date of manufacture against defects in materials and workmanship. See limited warranty statement for details. This limited warranty does not apply to those products that are damaged due to misuse, abuse, negligence, exposure to adverse environmental conditions, or have been modified in any manner whatsoever.
Manufacturer Warranties and Limitation of Liability Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that the Products manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free, under normal use and service, from defects in material and workmanship for a period of thirty six months (36) months from the date of manufacture (effective Jan. 1, 2009).
Silent Knight 12 Clintonville Road Northford, CT 06472-1610 203-484-7161 Fax: 203-484-7118 www.silentknight.