Owner's manual

Programming 151053-L8
6-5
Step 13 Relay Alarm Yes or No No
Press any numeric-digit to toggle the selection
from Yes to No.
Yes = Bell circuit activates during alarm
condition by the auxiliary relay.
No = Bell circuit activates during a dialer failed
condition.
Step 14 Relay Supervise Yes or No No
Press any numeric-digit to toggle the selection
from Yes to No.
Yes = Bell circuit is supervised (see Figure 3-
10).
No = Bell circuit in unsupervised (see Figure 3-
9).
Step 15 # of 5230 0 - 3 0
Sets the number of annunciators that will be
supervised.
0 = no supervision on any of the system
annunciators.
Step 16 Send Alarm #1 Yes or No Yes
Set priority for alarm reports. Press any
numeric-digit to toggle the selection from Yes
to No.
Yes = Priority phone number is #1.
No = Priority phone number is #2.
Step 17 Send Trouble #1 Yes or No Yes
Set priority for trouble reports.
Yes = Priority phone number is #1.
No = Priority phone number is #2.
Step 18 Send Test #1 Yes or No Yes
Set priority for manual and auto test reports.
Yes = Priority phone number is #1.
No = Priority phone number is #2.
Step 19 Report Sprnk #1 Yes or No Yes
Set how zone 1 will report. Press any numeric-
digit to toggle the selection from Yes to No.
Yes = If you want to report troubles and alarms
as a sprinkler (Supervisory), when using SIA
format.
No = If you want troubles and alarms to report
as fires (Alarm).
Note: Bells will only sound if "No" is select-
ed.
Step 20 Report Sprnk #2 Yes or No No
Set how zone 2 will report. Press any numeric-
digit to toggle the selection from Yes to No.
Yes = If you want to report troubles and alarms
as a sprinkler (Supervisory), when using SIA
format.
No = If you want troubles and alarms to report
as fires (Alarm).
Note: Bells will only sound if “No” is select-
ed.
Table 6-3: List of Programming Steps
Step # Task Choices Default