MODEL 5496 Intelligent Power Module Installation and Operations Manual Document 151276 08/12/10 Rev: E1 P/N 151276:E1 ECN: 10-484
Contents Section 1 Overview 1.1 1.2 1.3 1.4 ...................................................................................................................................................... 1-1 5496 Description ...................................................................................................................................... 1-1 Agency Requirements ..............................................................................................................................
Model 5496 Intelligent Power Module Installation and Operation Manual Appendix A Compatible Devices .....................................................................................................................
Section 1 Overview 1.1 5496 Description The Model 5496 Intelligent Power Module provides additional power and notification circuits to a Silent Knight addressable FACP. The 5496 can power all IntelliKnight compatible notification appliances and auxiliary power modules. The 5496 is capable of performing single or dual interlocking operations for pre-action and deluge releasing systems. See Section 8.6 of FACP installation manual.
Model 5496 Intelligent Power Module Installation and Operation Manual 1-2 151276
Section 2 Before You Begin Installing 2.1 What’s in the Box? The Model 5496 ships with the following hardware: • A cabinet with all hardware assembled • Two keys for the 5496 front door • Ten 4.7K ohm end-of-line resistors Note: For UL installations Model 7628 4.7k end-of-line resistor (ordered separately) must be used. • A battery wiring harness and jumper to wire batteries in series 2.2 Environmental Specifications It is important to protect the 5496 control panel from water.
Model 5496 Intelligent Power Module Installation and Operation Manual 2.4 5496 Board and Terminal Strip Description Figure 2-1 shows the 5496 circuit board including location of terminals and the dipswitch for setting the module ID. To AC All Circuits Supervised Power limited, except Battery and AC which are supervised non-power limited.
Before You Begin Installing Table 2-1 describes the 5496 connections and provides electrical ratings where appropriate. Table 2-1: Terminal Strip Description and Electrical Ratings Rating Terminal # and Label B 1 2 3 4 5 6 7 8 9 10 11 12 13 14 W + + + + + + A B Description Voltage Current AC input (hot) 120 VAC, 60 Hz 2.7 A Earth ground N/A N/A AC input (neutral) 120 VAC, 60 Hz 2.7 A Battery Battery 24 VDC 0.75 A I/O 4* Output circuit 24 VDC 3.
Model 5496 Intelligent Power Module Installation and Operation Manual 2.6 Calculating Current Draw and Standby Battery This section is for helping you determine the current draw and standby battery needs for your installation. 2.6.1 Worksheet Requirements Follow the steps below to determine 5496 current draw and standby battery requirements. Filling in the Current Draw Worksheet Refer Table 2-4 in Section 2.6.2 to complete the following steps. 1.
Before You Begin Installing 2.6.2 Current Draw Worksheet For each 5496 in the installation, use this worksheet to determine current requirements during alarm/battery standby operation. (Copy this page if additional space is required.
Model 5496 Intelligent Power Module Installation and Operation Manual 2.6.3 Wire Routing You must follow power-limited wiring techniques, which include maintaining one-quarter inch spacing between power-limited and non-power limited circuits and separating high and low voltage circuits.
Section 3 Hardware Installation 5496 installation involves the following steps: • Connect AC power (Section 3.1) and backup battery (Section 3.2). • Make physical connection to a Silent Knight addressable FACP (see Section 3.3). • Set an ID for the 5496 (Section 3.3.1). • Make physical connection to any outputs that will be powered by this 5496. See Section 3.4 for notification appliance wiring information.
Model 5496 Intelligent Power Module Installation and Operation Manual 3.2 Battery Connection The 5496 battery charge capacity is 7.0 AH not to exceed 35.0 AH. Use 12V batteries of the same AH rating. It is recommended that you replace batteries every five years. Determine the correct AH rating per your current load calculation (see Table 2-4). Note: If you require the power of back up batteries that are too large for the 5496, you can use the RBB cabinet.
Hardware Installation 3.3 Connecting the 5496 to the FACP 1. Connect the 5496 to the appropriate SBUS. The 5496 is connected directly to a Silent Knight addressable FACP. 2. Use the on-board dipswitch to assign an ID number to the 5496. (See Section 3.3.1) Figure 2-1 shows the location of the dipswitches on the 5496 board. 3. Configure the 5496 module by adding it to the system (through JumpStart or manually). You can also assign a name to the module.
Model 5496 Intelligent Power Module Installation and Operation Manual 3.3.1 Setting the Device ID All SBUS modules in the system must have a unique number (1-31) to identify them to the FACP. Use the DIP switch on the 5496 board to set the module ID number. Figure 2-1 shows the location of the dipswitch on the board. Figure 3-4 shows dipswitch setting and the corresponding module ID numbers.
Hardware Installation 3.4 Notification Appliance Wiring Note: Not all devices can use the Sync feature. Be sure to check Table A-1 in Appendix A to ensure the device you have chosen will work with this feature. 3.4.1 Class A Supervised Wiring Figure 3-5 shows how to wire for Class A output supervision. Use in/out wiring methods for proper supervision. Refer to Section 4 for notification appliances compatible with the 5496.
Model 5496 Intelligent Power Module Installation and Operation Manual 3.4.2 Class B Supervised Wiring Figure 3-6 shows how to wire for Class B output supervision. Use in/out wiring methods for proper supervision. Refer to Section 4 for notification appliances that must be used with the 5496. Class B Output Notification Circuits Figure 3-6 shows four, 1.5 amp devices wired as Class B circuits. Place a 4.
Hardware Installation 3.4.4 Auxiliary Power Configuration Output circuits 1-4 on the control panel can be used as auxiliary power circuits. The three types of auxiliary power available are: • Door Holder (see Section 3.4.4.1 for description) • Constant (see Section 3.4.4.2 for description) • Resettable (see Section 3.4.4.3 for description) Auxiliary power circuits are power limited. Each circuit can source up to 3A (total current for all output circuits must not exceed 6 A).
Model 5496 Intelligent Power Module Installation and Operation Manual 3.4.4.1 Door Holder Power Door holder is intended for fire door applications. When there are no alarms in the system and the panel has AC power, door holder circuits have 24-volt power present at their terminals. Any alarm will cause power to discontinue. Power will be re-applied when the system is reset. If AC power is off for more than 15 seconds the auxiliary door holder power will be discontinued to conserve the battery backup power.
Appendix A Compatible Devices For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on each circuit. All supervised notification appliances used with the IFP-FFT must be polarized. A.1 Notification Appliances Note: Not all devices can use the Sync feature, be sure to check A.1 to ensure the device you have chosen will work with this feature. This control is UL listed for single circuit synchronization.
Model 5496 Intelligent Power Module Installation and Operation Manual Table A-1: Compatible Notification Appliances Manufacturer Faraday A-2 Model Audio Visual Type 446 Vibrating Bell 476 Vibrating Bell 477 Single Stroke Bell 2700 -M.
Compatible Devices Table A-1: Compatible Notification Appliances Manufacturer Faraday con’t 151276 Model Audio Visual Type 5510 Strobe 5511 Strobe 5512 Strobe 5516 Strobe 5517 Strobe 5518 Strobe 5519 Strobe 5521 4” Square Sync Strobe 5522 4” Square Sync Strobe 6120 Horn 6140 Horn 6223 Horn 6226 Horn/Strobe 6227 Horn/Strobe 6228 Horn/Strobe 6243 Electron-Mechanical Horn 6244 Electron-Mechanical Horn 6245 Electron-Mechanical Horn 6246 Electron-Mechanical Horn/Strob
Model 5496 Intelligent Power Module Installation and Operation Manual Table A-1: Compatible Notification Appliances Manufacturer FCI FCI Federal Signal A-4 Model Audio Visual Type S2415-FC Strobe S241575-FC Strobe S2430-FC Strobe 130-3117C Mini Horn 130-3147C Mini Horn BLV-6 Vibrating Bell BLV-10 Vibrating Bell BLVCH Vibrating Chime H12/24-FC Horn H12/24W-FC Horn H12/24K-FC Horn HC12/24-FC Horn HC12/24W-FC Horn HC12/24K-FC Horn P2415-FC Horn/Strobe P2415W-FC Horn/Str
Compatible Devices Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual GEC-24-15 Horn/Strobes GEC-24-30 Horn/Strobes GEC-24-60 Horn/Strobes GEC-24-75 Horn/Strobes GEC-24-177 Horn/Strobes GEC-24-110 Horn/Strobe GEC-24-15/75 Horn/Strobe GX91 MiniHorn Steady Tone GX93 MiniHorn Temporal Tone HG124 Gentex Horn HS24-15 Horn/Strobe HS24-30 Horn/Strobe HS24-60 Horn/Strobe HS24-75 Horn/S
Model 5496 Intelligent Power Module Installation and Operation Manual Table A-1: Compatible Notification Appliances Manufacturer Model Visual Type CHR Chime CHW Chime CHSR 2-Wire Chime/Strobe CHSW 2-Wire Chime/Strobe HR Horn HW Horn HRK Horn P2R 2-Wire Horn/Strobe P2R-P 2-Wire Horn/Strobe PC2R 2-Wire Horn/Strobe PC2R-P 2-Wire Horn/Strobe P2RH 2-Wire Horn/Strobe High Candela P2RH-P 2-Wire Horn/Strobe High Candela
Compatible Devices Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual PC4W 4-Wire Horn/Strobe P4WH 4-Wire Horn/Strobe High Candela PC4WH 4-Wire Horn/Strobe High Candela P4RK 4-Wire Horn/Strobe PC4RK 4-Wire Horn/Strobe P4RHK 4-Wire Horn/Strobe High Candela PC4RHK 4-Wire Horn/Strobe High Candela PC4RH 4-Wire Horn/Strobe High Candela SR Strobe SR-P Strobe SCR Strobe SCR-P Strobe SRH Strobe Hi
Model 5496 Intelligent Power Module Installation and Operation Manual Table A-1: Compatible Notification Appliances Manufacturer Model Audio Horn AH-24 Horn AH-12WP Horn Weatherproof AH-24WP AMT-241575W Horn Weatherproof Multi-Tone Horn Strobe Mutli-Tone Horn Strobe Multi-Tone Horn Strobe AMT-241575W-NYC AMT-12/24 Multi-tone Horn AMT-12/24 NYC Multi-tone Horn AS-121575W A-8 Type AH-12 AMT-24MCW Wheelock Visual Horn/Strobe NH-12/24 AS-241575W
Compatible Devices Table A-1: Compatible Notification Appliances Manufacturer Model Audio CH90-24MCCH Chime/Strobe HS4-241575W Horn/Strobe HS4-24MCW Horn/Strobe HS4-24MCWH Horn/Strobe HS4-24MCC Horn/Strobe MIZ-24S Mini Horn Strobe MultitoneHorn Strobe Multitone Horn Strobe MT-24MCW Multitone Horn Strobe MTWP-2475W Multitone Horn Strobe MT-241575W Horn Multitone Horn Strobe MTG-121575W Multitone Horn Strobe MTR-121575W
Model 5496 Intelligent Power Module Installation and Operation Manual Table A-1: Compatible Notification Appliances Manufacturer Wheelock con’t A-10 Model Audio Visual Type RSS-121575W Strobe RSS-241575W Strobe RSS-24MCC Strobe RSS-24MCCR Strobe RSS-24MCCH Strobe RSS-24MCCHR Strobe RSS-24MCW Strobe RSS-24MCWH Strobe RSSP-121575W Strobe RSSP-241575W Strobe RSSR-2415W Strobe RSSR-2415C Strobe RSSR-2475W Strobe RSSR-2475C Strobe RSSR
Compatible Devices Table A-1: Compatible Notification Appliances Manufacturer Wheelock con’t Model Audio Visual Type RSSWP-24MCWH Strobe Weatherproof ZRS-MCWH Strobe ZRS-24MCC Strobe ZRS-24MCCH Strobe MB-G6-24 Motor Bell MB-G10-24 Motor Bell MB-G6-12 Motor Bell MB-G10-12 Motor Bell MIZ-24-R Mini-Horn MT-12/24-R Multitone Horn MT4-12/24 Multitone Horn Strobe Multitone Horn Strobe ZRS-MCW MTWPR-24MCCH NH-12/24R Horn HSR Horn/Strobe HSW
Model 5496 Intelligent Power Module Installation and Operation Manual A-12 151276
Silent Knight Fire Product Warranty and Return Policy General Terms and Conditions • All new fire products manufactured by Silent Knight have a limited warranty period of 36 months from the date of manufacture against defects in materials and workmanship. See limited warranty statement for details. • This limited warranty does not apply to those products that are damaged due to misuse, abuse, negligence, exposer to adverse environmental conditions, or have been modified in any manner whatsoever.
or call Silent Knight at 203-484-7161 to obtain a RMA (Return Authorization) number and request advanced replacement, • A new or refurbished board will be shipped to the customer. The customer will initially be billed for the replacement board but a credit will be issued after the repairable board is received at Silent Knight. All returned products must comply with the guidelines described under “General Terms and Conditions”.
Manufacturer Warranties and Limitation of Liability Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that the Products manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free, under normal use and service, from defects in material and workmanship for a period of thirty six months (36) months from the date of manufacture (effective Jan. 1, 2009).
Silent Knight 12 Clintonville Road Northford, CT 06472-1610 203-484-7161 Fax: 203-484-7118 www.silentknight.