INTELLIKNIGHT® 5600/5600C/ 5600HV Addressable Fire Control Panel Installation and Operations Manual Document 151450 03/08/2013 Rev: E2 151450:E2 ECN: 13-0232 ECN: 13-0232
Installation Procedure Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized.
These instructions must be followed to avoid damage to the control panel and associated equipment. FACP (Fire Alarm Control Panel) operation and reliability depend upon proper installation. Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled.
Contents Contents Section 1 Introduction ..................................................................................................................................................1 1.1 Overview of Basic System ........................................................................................................... 1 1.1.1 Hardware Features ............................................................................................................... 1 1.1.2 Software Features ....................
Installation Manual 4.1.3.1 Installing the Dead Front ............................................................................................. 2 4.1.3.2 Dead Front Removal ................................................................................................... 3 4.2 AC Power Connection ................................................................................................................. 4 4.2.1 AC Power Connection for UL 864 applications ..........................................
Contents 6.3.5 Installer Code ........................................................................................................................ 5 JumpStart AutoProgramming ...................................................................................................... 5 Modifying Panel Programming using a PC .................................................................................. 6 6.5.1 Connecting the panel to a PC ....................................................................
Installation Manual 7.9 7.10 7.11 7.12 7.13 Fire Drill ....................................................................................................................................... 2 Zone Disable Feature .................................................................................................................. 3 Disabling Notification Circuits ...................................................................................................... 3 Loss of AC power .........................
Contents Appendix A Compatible Devices ..........................................................................................................................
Installation Manual 6
Section 1 Introduction The 5600 Fire Alarm Control / Communicator is an addressable fire control system that meets the requirements of UL 864, ULC 527, and ULC 559. Unless otherwise indicated, all references to 5600 also refer to 5600C and 5600HV. 1.1 1.1.1 Overview of Basic System Hardware Features • The 5600 has one signaling line circuit (SLC) that supports 25 Honeywell Fire Systems (HFS) or SK SLC devices, and one SBUS circuit that supports two remote annunciators. • 2.
Model 5600 Installation and Operation Manual 1.2 About this Manual This manual is intended to be a complete reference for all installation and operation tasks for the 5600. Please let us know if the manual does not meet your needs in any way. We value your feedback! 1.2.
Introduction Limitations of Fire Alarm Systems Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer’s recommendations, State and local codes, and the recommendations contained in Guide for the Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers.
Model 5600 Installation and Operation Manual by arson, children playing with matches (especially within bedrooms), smoking in bed, violent explosions (caused by escaping gas, improper storage of flammable materials, etc.). • Heat detectors do not sense particles of combustion and are designed to alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Heat detectors are designed to protect property, not life.
Introduction continue to act prudently in protecting the premises and the people in their premises and should properly insure life and property and buy sufficient amounts of liability insurance to meet their needs.
Model 5600 Installation and Operation Manual 1-6 151450
Section 2 Agency Listings, Approvals, and Requirements Install and maintain in accordance with NFPA 72. Detector spacing shall be in accordance to NFPA 72. End-of -line relays and resistors shall be placed within the electrical box located and the end of the initiating circuit. Testing and maintenance should be performed according to NFPA 72. 2.
Model 5600 Installation and Operation Manual 4. The telephone company may make changes in its facilities, equipment, operations, or procedures that could affect the operation of the equipment. If this happens, the telephone company will provide advance notice to allow you to make the necessary modifications to maintain uninterrupted service. Warning This device has been verified to comply with FCC Rules Part 15.
Agency Listings, Approvals, and Requirements i) Connection to party line service is subject to state tariffs. Contact the state public utility commission, public service commission or corporation commission for information. j) If your home has specially wired alarm equipment connected to the telephone line, ensure the installation of this 5600 does not disable your alarm equipment. If you have questions about what will disable alarm equipment, consult your telephone company or qualified installer.
Model 5600 Installation and Operation Manual 2.2.2 Requirements for Central Station Fire Alarm Systems 1. Use both phone lines. Enable phone line monitors for both lines. 2. You must program a phone number and a test time so that the 5600 sends an automatic daily test to the central station. 3. The AC Loss Hours option must be set from 1-3 hours. 2.2.3 Requirements for Local Protected Fire Alarm Systems At least one UL listed supervised notification appliance must be used. 2.2.
Section 3 Before You Begin Installing This section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly, especially if you are installing a 5600 panel for the first time. 3.1 What’s in the Box? The 5600 ships with the following hardware: • A cabinet with all hardware assembled • Two keys for the front door • Installation and Operation manual P/N 151450. • Ten 4.
Model 5600 Installation and Operation Manual 3.3 Electrical Specifications Table 3-1 list the electrical specifications for the 5600 field wiring as well as a description of the each individual terminal and their respective electrical rating. For location of the terminals refer to 3.5. See also Section 4 for installation. Table 3-1: Terminal Descriptions Label Terminal Block Description Group TB 1 Rating SBUS Individual – Voltage Earth Ground Fault Impedance Current Ohms SBUS Power 27.
Before You Begin Installing 3.4 Wiring Specifications Induced noise (transfer of electrical energy from one wire to another) can interfere with telephone communication or cause false alarms. To avoid induced noise, follow these guidelines: • Isolate input wiring from high current output and power wiring. Do not pull one multi-conductor cable for the entire panel.
Model 5600 Installation and Operation Manual beads or by wrapping it around a ferrite toroid.
Before You Begin Installing 3.5 Board Assembly Diagram Slide-In Stand-offs On-board Annunciator Mounting screw AC Power Input Ethernet Programming Port Battery ConnectorAC Power 24VDC Input Mounting screws Battery Connector Location Mounting Pin SBUS SLC Out NAC/AUX Power Circuits Form C Trouble Form C Programmable Relays Phone Lines Figure 3-2 Model 5600 Assembly Figure 3-2 shows the 5600 circuit board stack.
Model 5600 Installation and Operation Manual 3.6 Calculating Current Draw and Standby Battery This section is for helping you determine the current draw and standby battery requirements (Table 3-2). 3.6.1 Worksheet Requirements The following steps must be taken when determining 5600 current draw and standby battery requirements. 1. For the 5600, the worst case current draw is listed for the panel and all addressable devices.
Before You Begin Installing 3.6.1.1 Current Draw Worksheet for 5600 for UL 864 Use Table 3-2 to determine amp-hour requirements during alarm/battery standby operation. (Copy the page if additional space is required.) You can install up to 25 SLC devices and two 5635 Remote Annunciator. Table 3-2: Current Calculation Worksheet for SLC Devices Device # of Devices For each device use this formula: devices.
Model 5600 Installation and Operation Manual Table 3-2: Current Calculation Worksheet for SLC Devices Device # of Devices Current per Device Standby Current Alarm Current E Total current ratings converted to amperes (line D x .001): A F Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5): H G Multiply lines E and F. H Alarm sounding period in hours. (For example, 5 minutes = .0833 hours) I Multiply lines E and H. Total alarm AH Add lines G and I.
Before You Begin Installing 3.6.1.2 Current Draw Worksheet for 5600 ULC Use to determine amp-hour requirements during alarm/battery standby operation. (Copy the page if additional space is required.) You can install up to 25 SLC devices and two 5635 Remote Annunciator. The maximum battery size for ULC installations is 18 Amp/hr. Table 3-3: Current Calculation Worksheet for SLC Devices for ULC Device # of Devices For each device use this formula: devices.
Model 5600 Installation and Operation Manual Table 3-3: Current Calculation Worksheet for SLC Devices for ULC Device # of Devices Current per Device F Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5): G Multiply lines E and F. H Alarm sounding period in hours. (For example, 5 minutes = .0833 hours) I Multiply lines E and H. Total alarm AH J Add lines G and I. 1 Total ampere hours required Total standby AH Standby Current Alarm Current H AH H AH AH 1.
Before You Begin Installing 3.6.2 Maximum Battery Standby Load for UL 864 Table 3-4 shows the standby load calculations for the 5600 based on 24 hours of standby. The standby load calculations of line D in the Current Draw Calculation Worksheet must be less than the number shown in Table 3-4 for the selected battery size, standby hour and alarm time. The numbers below have a built in 20% de-rating factor for the battery amp hour capacity.
Model 5600 Installation and Operation Manual 3-12 151450
Section 4 Control Panel Installation Caution! To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while installing or servicing. 4.1 Mounting the Control Panel Cabinet Read the environmental specifications in Section 3.2 before mounting the 5600 panel. The 5600 cabinet dimensions are: 12-3/4” W x 15-1/8” H x 3-3/8” D (32.39 cm W x 38.42 cm H x 8.57 cm D).
Model 5600 Installation and Operation Manual 4.1.3 Dead Front Installation and removal This section provides instructions to install and or remove the dead front for the control panel cabinet. 4.1.3.1 Installing the Dead Front Follow these steps to properly install the dead front panel into the control panel cabinet. 1. Remove the top two annunciator screws, do not discard them they will be reused. See Figure 4-1 for annunciator screw location. 2.
Control Panel Installation 4.1.3.2 Dead Front Removal Follow these steps to properly remove the dead front panel from the control panel cabinet. 1. Remove the two annunciator screws, do not discard them. See Figure 4-1. 2. Tilt the dead front forward to clear the top of the cabinet and left the dead front out of the cabinet. See Figure 4-1. 3. Reinsert the two annunciator screws. See Figure 4-1.
Model 5600 Installation and Operation Manual 4.2 AC Power Connection 4.2.1 AC Power Connection for UL 864 applications At installation, connect the AC terminals to the power source as shown in Figure 4-2. It may be necessary for a professional electrician to make this connection. Connect black and white wires from transformer to 120V power. Connect ground wire from 120V power to screw labeled G on the 5600 circuit board. The AC power input is rated at 120 VAC, 60 Hz, 1.
Control Panel Installation 4.2.2 AC Power Connection for Canadian Applications For Canadian applications, an AC terminal block is supplied standard with the 5600C. The AC terminal block is factory installed on the left of the circuit board chassis as shown in Figure 4-3.
Model 5600 Installation and Operation Manual 4.3 Battery Connection The control panel battery charge capacity is 7.0 to 33 AH or 18 AH for ULC installations. The main control cabinet can house batteries up to 7 AH, larger capacity batteries can be housed in a Remote Battery Box (P/N RBB). See Section 4.3.1 for details. Use 12V batteries of the same AH rating. Determine the correct AH rating as per your current load calculation (see Section 3.6). Maximum charging current for batteries is 3.1A @ 27 VDC.
Control Panel Installation 4.3.1 RBB Accessory Cabinet The Model RBB Accessory cabinet can be used when your backup batteries are too large to fit into the main control panel cabinet. The RBB cabinet holds batteries up to the 35 AH size. The RBB dimensions are 16" W x 10" H x 6" D (40.64 cm W x 25.4 cm H x 15.24 cm D). 4.3.1.1 Installing the RBB Accessory Cabinet and Batteries To properly install the accessory cabinet and backup batteries, follow these steps: 1. Mount the accessory cabinet.
Model 5600 Installation and Operation Manual 2. Connect the main control panel battery cables to the battery cable extenders as shown in Figure 4-6. Figure 4-6 Splicing Control panel Battery Cable to RBB Battery Cable Extenders 3. Run extended battery cable from control panel cabinet through conduit to RBB cabinet. See Figure 4-7.
Control Panel Installation 6. Align the cover plate mounting keyhole over the cover mounting screws. See Figure 4-8. Cover Plate Mounting Keyholes Figure 4-8 Cover Plate Mounting Keyholes and Cover Mounting Screws Alignment 7. Slide the cover into place and tighten the cover mounting screws. See Figure 4-8. 4.4 SBUS Wiring This section contains information on calculating SBUS wire distances and the types of wiring configurations (Class B). 4.4.
Model 5600 Installation and Operation Manual Table 4-1: Wire Distance Per Wire Gauge Using Copper Wire Wiring Distance: SBUS Modules to Panel Total Worst Case 22 Gauge Current Draw (amps) 18 Gauge 16 Gauge 14 Gauge 0.100 1852 ft. 4688 ft. * 6000 ft. * 6000 ft. 0.200 926 ft. 2344 ft. 3731 ft. 5906 ft. 0.300 617 ft. 1563 ft. 2488 ft. 3937 ft. 0.400 463 ft. 1172 ft. 1866 ft. 2953 ft. 0.500 370 ft. 938 ft. 1493 ft. 2362 ft. 0.600 309 ft. 781 ft. 1244 ft. 1969 ft. 0.
Control Panel Installation Wiring Distance calculation example: Suppose a system is configured with the following SBUS modules: 1 - Module 5635 Fire Annunciator The total worst case current is calculated as follows: 5635 Current Draw = 1 x .04 amps Total Worst Case Current Draw = .04 amps = .
Model 5600 Installation and Operation Manual 4.4.2 Wiring Configurations Figure 4-9 illustrates Class B configuration.
Control Panel Installation 4.5 5635 Remote Annunciator Installation The optional Model 5635R (red) and 5635W (white) Remote Annunciator is shown in Figure 4-10. Figure 4-10 Model 5635 Remote Annunciator, Front View 5635 installation involves the following steps: 1. Make sure power is off at the panel. 2. Mount the 5635 in the desired location (see Section 4.5.1). 3. Connect the 5635 to the panel (see Section 4.6). 4.
Model 5600 Installation and Operation Manual 4.5.1 Mounting the 5635 This section of the manual describes mounting the remote annunciator. Figure 4-11 shows the parts of the annunciator. Inside Cover LCD Display Back Box Figure 4-11 5635 Annunciator Parts The 5635 Series plastic enclosures can be surface or semi-flush mounted in a single, double or 4” square electrical box. To mount the 5635 Series enclosure: 1.
Control Panel Installation 4.6 Model 5635 Connection to the Panel Connect the 5635 to the panel as shown in Figure 4-12.
Model 5600 Installation and Operation Manual 4.7 Configuring Module This section describes how to configure the 5635 Annunciator that has been added to the system. Each SBUS device requires a unique address. 5635 Series DIP switch S21 is used to set the address. This address will be displayed on the LCD display as the Station ID number. 4.7.1 Assigning Module IDs When installing the 5635 you must use the DIP switches on the module to assign an ID# to the module.
Control Panel Installation 4.8 Telephone Connection Connect the telephone lines as shown in Figure 4-14. The Model 7860 phone cord is available from Silent Knight for this purpose.
Model 5600 Installation and Operation Manual 4.9 Notification Appliance/Auxiliary Power Circuits The two outputs of the 5600 FACP can be programmed to be used as NACs or as Aux power. This section of the manual explains how to install conventional notification appliances and how these terminals can be used for auxiliary power. 4.9.1 Conventional Notification Appliance Circuit The 5600 supports Class B (Style Y) configurations for notification appliance applications.
Control Panel Installation 4.9.2 Auxiliary Power Installation NAC Circuits 1 and 2 on the control panel can be used as auxiliary power circuits. The three types of auxiliary power available are: • Door Holder (see section 4.9.2.1) • Constant (see section 4.9.2.2) • Resettable Power (see section 4.9.2.3) Auxiliary power circuits are power limited. Each circuit can source up to 1.0A (total current for system must not exceed 2.0A). To install an auxiliary power circuit: 1.
Model 5600 Installation and Operation Manual 4.9.2.2 Constant Power Use constant power for applications that require a constant auxiliary power source. Power is always present at Constant circuits. 4.9.2.3 Resettable Power Resettable power is typically used to power beam detectors, flame detectors and conventional 4-wire smoke detectors. For circuits selected as Resettable, 24 volt power is always present at the terminals unless a system reset occurs.
Control Panel Installation 4.10 On-Board Relays (Conventional, Power Limited) The control panel has two built-in programmable relays and a built-in trouble relay. All relays are Form C rated at 2.5 A @ 24 VDC Resistive. 4.10.1 Common Trouble Relay The control panel has a dedicated Form C trouble relay built into terminals labeled TROUBLE. The relay provides a normally open and a normally closed contact. The trouble relay will deactivate under any trouble condition. Form C rated at 2.
Model 5600 Installation and Operation Manual 4.11 Remote Station Applications 4.11.1 City Box Connection Using the 5220 Module This section describes how to connect the control panel to a municipal fire alarm box or “city box” as required by NFPA 72 Auxiliary Protected Fire Alarm systems for fire alarm service.
Control Panel Installation It is not possible to reset the remote indication until you clear the condition and reset the control panel. Note: NAC Circuit 2 Used as an Example. Either NAC Circuit Can Be Used.
Model 5600 Installation and Operation Manual 4.11.2 NFPA 72 Polarity Reversal 4.11.2.1 Alarm, Supervisory and Trouble Reverse Polarity Outputs Three HFS-MR or SK-Relay modules are required to independently report alarm, supervisory and trouble. SLC addresses 141, 143, and 147 must be used as shown in Figure 4-18.
Section 5 SLC Device Installation Caution! To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while installing or servicing. 5.1 List of SLC Devices The following SLC devices can be used with the control panel. See the device installation instructions for more information (packaged with the device).
Model 5600 Installation and Operation Manual 5.3 Wiring Requirements for SLC Devices The following information applies to all SLC devices. Refer to the section that describes the type of device you are installing for details. 5.3.1 Wiring SLC in Style 4 (Class B) Configuration No special wire is required for addressable loops. The wire can be untwisted, unshielded, solid or stranded as long as it meets the National Electric Code 760-121 requirements for power limited fire protective signaling cables.
SLC Device Installation The following figures show how length is determined for out and back tap and T-Tap style wiring.
Model 5600 Installation and Operation Manual When using T-taps, the total length of all taps and the main bus must not exceed 40,000 feet. This requirement must be met in addition to the maximum distance requirements for the various wire gauges.
SLC Device Installation 5.4 Wiring SLC Detectors This section describes how to install heat and smoke detectors. All detectors ship with installation instructions. Refer to the detector’s installation instructions for more detailed information.
Model 5600 Installation and Operation Manual 5.5 Addressing SLC Devices All HFS/SK devices are addressed using the two rotary dials that appear on the device board. Use the ONES rotary dial to set the ones place in a one or two digit number, and use the TENS rotary dial to set the tens place in a two digit number. Example 1: To select device address 35, turn the ONES rotary dial to 5 and the TENS rotary dial to 3 as shown in Figure 5-4.
Section 6 Programming This section of the manual describes how to change the control panel programming options from the built-in web page of the control panel. All options described in this section are edited via the panel’s built in web page Important! Before any customized programming is done, JumpStart should be run first. After JumpStart is run, thoroughly test the system.
Model 5600 Installation and Operation Manual 6.2 Control Panel Programming The 5600 is an addressable control panel that has the characteristics of a 5 zone conventional fire alarm control panel. 6.3 Default Control Panel Configuration. The panel ships from the factory in a defaulted configuration that may allow the installer to use the panel without doing any custom programming. 6.3.
Programming 6.3.2 Mapping of SLC Inputs to Outputs. Table 6-2: Input Points INPUT POINTS Zone Input Point Types Function Qty Start End Description SLC ID SLC ID Zone 1 HFS-P. HFS-PT, HFS-D, Alarm HFS-T, SK-Photo, SK-Photo- Supervisory T, SK-Duct, SK-Heat, SKPull-SA, SK-Pull-DA, HFSMM, SK-Minimon 15 1 15 Alarm Zone 1 5 16 20 Supervisory Zone 1 Zone 2 HFS-P.
Model 5600 Installation and Operation Manual Table 6-3: Output Points OUTPUT POINTS Group Output Point Type Qt Start y SLC ID End SLC ID Output Activates For OPG 1 HFS-MR, HFS-MRA, SK-Relay 2 111 112 Zone 1 Alarm OPG 2 HFS-MR, HFS-MRA, SK-Relay 2 113 114 Zone 2 Alarm OPG 3 HFS-MR, HFS-MRA, SK-Relay 2 115 116 Zone 3 Alarm OPG 4 HFS-MR, HFS-MRA, SK-Relay 2 117 118 Zone 4 Alarm OPG 5 HFS-MR, HFS-MRA, SK-Relay 2 119 120 Zone 5 Alarm OPG 6 HFS-MR, HFS-MRA, SK-Relay 2 121 1
Programming 6.3.4 Maximum SLC address point count The 5600 control panel supports a maximum of 25 SLC points to be used within the 159 point address range. The points can be all inputs, all outputs or any combination of inputs and output points. When more than 25 SLC devices are added to the control panel, any excess points will indicate a trouble and not be recognized by the panel. 6.3.5 Installer Code The installer code is factory programmed as 123456.
Model 5600 Installation and Operation Manual 6.5 6.5.1 Modifying Panel Programming using a PC Connecting the panel to a PC Modifications to the default panel programming can only be done using the embedded web server of the control panel. There are two ways to connect to the panel for the purpose of programming. It can be connected through a DHCP (Dynamic Host Configuration Protocol) router or it can also be plugged in using a Standard CAT5e Ethernet cable without a router.
Programming 6.6 Panel Programming Options All customized programming options for the 5600 control panel are described in this section and are available to be edited using the embedded web server of the control panel. 6.6.1 System Options 6.6.1.1 Synchronized Strobes Active When Horns Silenced The default configuration for this option is No. If set to Yes, strobes will remain on when horns are silenced until a panel reset is issued. 6.6.1.
Model 5600 Installation and Operation Manual the central station. It is defaulted to 3 hours and must be within the range 0-30 hours. For U.L. 864 installation this option must be set within the range 1-3 hours. 6.6.1.8 Walk Test Reporting The default configuration for this option is No. If set to Yes, the panel generates a TEST report to the central station when the walk test begins.
Programming 6.6.2 Zone Programming 6.6.2.1 SLC Addresses Within Each Zone Each zone has 15 alarm SLC addresses and 5 supervisory SLC addresses assigned to it as described in table 6.1. For each SLC address within a zone, the SLC device type choices are Unused, Detector, Manual Pull Switch, Latching Water Flow Switch or Non-Latching Water Flow Switch. The default setting is that all points are unused. 6.6.2.
Model 5600 Installation and Operation Manual 6.6.4 Notification Appliance Circuit (NAC) Programming 6.6.4.1 Circuit Function The two notification circuits are both defaulted to activate the System Sensor synchronization pattern when any of the five zones are in alarm. You can define each of the notification circuits to be either a conventional notification circuit or an auxiliary power type circuit. 6.6.4.
Programming 6.6.5 Relay Programming Options The two on-board relays of the control panel can be programmed for Auxiliary Resettable and Auxiliary Door Holder applications. Relay 1 can be selected to activate for General Supervisory. Relay 2 can be selected to activate for General Alarm. See Figure 6-1. Figure 6-1 Relay Programming Option 6.6.5.1 General System Relay Silence Option This option defaults to silenceable.
Model 5600 Installation and Operation Manual 6.6.6.3 Line Monitoring Enabled (Y/N) This option is used to enable phone line voltage supervision. It defaults to No. 6.6.6.4 Dialing Option The dialer can use touch tone or pulse dialing when calling the central station. The options for dialing are touch tone only, dial pulse only or alternating touch tone/dial pulse when multiple attempts are used to connect with the central station. The default setting is touch tone only. 6.6.6.
Programming 6.6.7 Dialer Account programming Options Up to two accounts can be used for reporting events to the central station. A typical reason to use multiple reporting accounts might be to have one account for reporting alarms and a different account for reporting supervisories and troubles. The programming options for each account are described below. 6.6.7.1 Account Number Up to six digits allowed for SIA formats or up to four digits for contact ID format. Default account numbers are blank. 6.6.
Model 5600 Installation and Operation Manual 6-14 151450
Section 7 System Operation The operation of the 5600 control panel is similar to a conventional 5 zone Fire Alarm Control Panel. System status and control is segmented into zones even though the panel supports addressable SLC devices for input and output functions. Note: ULC version of the panel (5600C) has a built in Alarm Reset and Alarm Silence inhibit of 30 seconds 7.1 System Reset To reset the system press the RESET key once. All LEDs will light while the system is being reset.
Model 5600 Installation and Operation Manual 7.6 Viewing Active Supervisory Points When one or more SLC points within a zone are in supervisory alarm, the supervisory LED for that zone will blink and outputs will activate that are mapped to supervisories within the zone. To display the SLC address of an input point that is in supervisory, press the SUPERVS ID key once and use the PREV (previous) or NEXT key to scroll through the supervisory points.
System Operation 7.10 Zone Disable Feature To disable a zone, press the disable zone key that corresponds to the zone number you wish to disable. When a zone is disabled all alarm events that occur while the zone is disabled will be ignored. Zones that are disabled will be in trouble. The PZT will sound the trouble cadence. The trouble LED for the specific zone along with the general trouble LED will blink indicating that the zone is in trouble.
Model 5600 Installation and Operation Manual 7.14 Low Battery The battery voltage is continuously monitored during normal standby. When the battery is not present or the voltage is too low, the control panel will indicate a low battery trouble. Both the LOW BATTERY and GENERAL TROUBLE LED will blink when there is a low battery condition. The PZT will also sound the trouble cadence. If the silence key is pressed, the trouble LEDs will be continuously on and the PZT will silence. 7.
System Operation 7.20 Annunciator Description Operation of the Remote Annunciator is simple. See 5635 Installation instructions PN 53958 for more information. Figure 7-1: shows the Remote Annunciator. Figure 7-1: 5635 Remote Annunciator 7.20.1 LCD Displays The Remote Annunciator's LCD displays system messages, annunciates alarms, supervisories and troubles; provides status information; and prompts for input. These messages can be up to 80 characters, displaying over four lines of 20 characters each.
Model 5600 Installation and Operation Manual 7.20.2 Banner The banner is the message that displays on the Annunciator when the system is in normal mode (no alarm, trouble or supervisory condition exists). You can create a customized message that will display instead of the internal (default) message. See 6.6.1.13 for information on customizing the banner.
System Operation 7.21 Basic Operation 7.21.1 Conduct a Fire Drill 1. Activate the key by turning it to the ON position. 2. Press and hold the Drill key for 2 seconds. 3. The drill will begin after the key has been held down for 2 seconds. 4. Press the Reset key to end the Fire Drill. (If you do not press the Reset Key to end the Fire Drill manually, it will time out automatically after 10 minutes.) 7.21.2 Conduct an Indicator Test The indicator test checks the annunciator LEDs, PZT, and LCD display. 1.
Model 5600 Installation and Operation Manual 7.22 Operation Mode Behavior The remote annunciator can be in one of six conditions at any given moment: Normal, Alarm, Supervisory, Trouble, Silenced, and Reset. Table 7-1 describes the behavior of the Remote Annunciator in each of these modes. Table 7-1: Operation Modes of Remote Annunciator Operation Mode Normal Occurs When No alarm or trouble condition exists. System Behavior In This Mode You Can AC POWER LED is on.
System Operation Table 7-1: Operation Modes of Remote Annunciator Operation Mode Trouble Occurs When A system trouble condition occurs. System Behavior In This Mode You Can The dialer seizes control of the phone line and calls the central station. Press down arrow to view the trouble. A screen similar to this one displays. The remote annunciator sounds a loud, pulsing beep in the sequence one second on, nine seconds off. TROUBLE LED flashes. The LCD displays a screen similar to this one.
Model 5600 Installation and Operation Manual 7-10 151450
Section 8 Reporting This section lists receivers that are compatible with this control panel, and the reporting codes sent by the control panel for SIA and Contact ID formats. 8.1 Receivers Compatible with the Control Panel Table 8-1 shows receivers compatible with the control panel. Table 8-1: Receivers Compatible with the Control Panel Manufacturer Silent Knight 8.
Model 5600 Installation and Operation Manual Phone line 1 trouble restore Trouble System Event LR 1 3 351 00 001 Phone line 2 trouble restore Trouble System Event LR 2 3 352 00 002 Phone line 1 trouble detected Trouble System Event LT 1 1 351 00 001 Phone line 2 trouble detected Trouble System Event LT 2 1 352 00 002 Periodic test event – normal Test System Event RP 1 602 00 000 Periodic test event – off normal Test System Event RY 1 608 00 000 Initial power
Reporting Manual pull switch trouble Trouble Zone Event FT Zone 1 373 00 Zone Detector trouble Trouble Zone Event FT Zone 1 373 00 Zone Auxiliary power trouble Trouble Zone Event FT 0000 1 320 00 000 Notification trouble Trouble Zone Event FT 1000+ Group# 1 320 00 Group # User initiated a system reset Reset Zone Event OR 1 401 00 000 Water flow switch alarm Alarm Zone Event SA Zone 1 113 00 Zone Water flow switch alarm restore Restore Zone Event SH Z
Model 5600 Installation and Operation Manual 8-4 151450
Section 9 Trouble Shooting and Quick Tips 9.1 Troubleshooting This section of the manual offers suggestions for troubleshooting hardware problems. Please read this section if you encounter a problem when installing the control panel. If these suggestions do not solve your problem or if you encounter a problem that is not listed here, contact Silent Knight Technical Support for assistance. 9.1.1 JumpStart Jumpstart will learn all of the SLC devices and SBUS annunciators attached to the system.
Model 5600 Installation and Operation Manual 2. If Silence/Reset Inhibit Enabled is selected in programming, that button and the SYSTEM RESET button are ignored for the first 30 seconds of the first alarm or supervisory signal 9.1.6 To Initiate a Fire Drill 1. Press Drill until “DRL” is displayed 2. Press SYSTEM RESET to end the drill 9.1.7 For a Dialer Test Press JumpStart and Next at the same time 9.1.8 For a Lamp Test Press JumpStart and Prev at the same time 9.1.
Trouble Shooting and Quick Tips “rA1” indicates remote annunciator 1 trouble “rA2” indicates remote annunciator 2 trouble “gnd” indicates ground fault trouble “AC” indicates AC power supply trouble “nC1” indicates notification appliance circuit 1 trouble “nC2” indicates notification appliance circuit 2 trouble “tSt” indicates a trouble for the duration of a walk test Correct the fault and the trouble will restore 9.
Model 5600 Installation and Operation Manual 2. Click on yes option for Remote Annunciator Installed 1/ Remote Annunciator Installed 2 3. Click Accept Note: Remember to choose to Download to Panel after all of your changes are done 9.2.4 To add custom Zone name 1. Click on Zone Programming 2. Click on Zone Options. Enter custom Zone name (20 characters max) in the corresponding field 3. Click Accept Note: Remember to choose to Download to Panel after all of your changes are done 9.2.
Appendix A Compatible Devices A.1 Notification Appliances For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on each loop. All supervised notification appliances used with the control panel must be polarized. Note: Not all devices can use the Sync feature, be sure to check Table A-1 to ensure the device you have chosen will work with this feature. This control is UL listed for panel wide Synchronization.
Model 5600 Installation and Operation Manual Manufacturer Model Audio Visual GEC-24-15 X X Horn/Strobes GEC-24-30 X X Horn/Strobes GEC-24-60 X X Horn/Strobes GEC-24-75 X X Horn/Strobes GEC-24-177 X X Horn/Strobes GEC-24-110 X X Horn/Strobe GEC-24-15/75 X X Horn/Strobe GX91 X MiniHorn Steady Tone GX93 X MiniHorn Temporal Tone HG124 Horn HS24-15 X X Horn/Strobe HS24-30 X X Horn/Strobe HS24-60 X X Horn/Strobe HS24-75 X X Horn/Strobe HS24-110 X X Horn/
Manufacturer System Sensor 151450 Model Audio CHR X CHW X CHSR X Visual Type Chime Chime X 2-Wire Chime/Strobe CHSW X X 2-Wire Chime/Strobe HR X X Horn HW X Horn HRK X Horn P2R X X 2-Wire Horn/Strobe P2R-P X X 2-Wire Horn/Strobe PC2R X X 2-Wire Horn/Strobe PC2R-P X X 2-Wire Horn/Strobe P2RH X X 2-Wire Horn/Strobe High Candela P2RH-P X X 2-Wire Horn/Strobe High Candela PC2RH X X 2-Wire Horn/Strobe High Candela PC2RH-P X X 2-Wire Horn/Strobe High Can
Model 5600 Installation and Operation Manual Manufacturer Model PC4W 4 Visual X X Type 4-Wire Horn/Strobe P4WH X X 4-Wire Horn/Strobe High Candela PC4WH X X 4-Wire Horn/Strobe High Candela P4RK X X 4-Wire Horn/Strobe PC4RK X X 4-Wire Horn/Strobe P4RHK X X 4-Wire Horn/Strobe High Candela PC4RHK X X 4-Wire Horn/Strobe High Candela PC4RH X X 4-Wire Horn/Strobe High Candela X Strobe SR System Sensor Audio SR-P X Strobe SCR X Strobe SCR-P X Strobe SRH X Strobe
Manufacturer Model Audio X Horn AH-24 X Horn AH-12WP X Horn Weatherproof AH-24WP X AMT-241575W X AMT-241575W-NYC X Horn Weatherproof X Multi-Tone Horn Strobe X Multi-Tone Horn Strobe X Multi-Tone Horn Strobe AMT-12/24 X Multi-tone Horn AMT-12/24 NYC X Multi-tone Horn AS-121575W NH-12/24 151450 Type AH-12 AMT-24MCW Wheelock Visual X X Horn/Strobe Horn AS-241575W X X Horn/Strobe AS-24MCC X X Horn/Strobe AS-24MCCH X X Horn/Strobe AS-24MCW X X Horn/Strobe AS-
Model 5600 Installation and Operation Manual Manufacturer Model Audio CH90-24MCCH X HS-24 X HS4-241575W X Chime/Strobe Horn X Horn/Strobe X X Horn/Strobe HS4-24MCWH X X Horn/Strobe HS4-24MCC X X Horn/Strobe MIZ-24S X X Mini Horn Strobe X MultitoneHorn Strobe X Multitone Horn Strobe MT-24MCW X Multitone Horn Strobe MTWP-2475W X Multitone Horn Strobe X Multitone Horn Strobe X Multitone Horn Strobe MT-241575W X MTWP-2475C MTG-121575W 6 Type HS4-24MCW MT-121575W
Manufacturer Model Audio RSSR-2475W Wheelock (con’t) Visual X Strobe RSSR-2475C X Strobe RSSR-24110C X Strobe RSSA-24110W X Strobe RSSB-24110W X Strobe RSSG-24110W X Strobe RSSR-24110W X Strobe RSSA-24MCC X Multi-Cd Strobe RSSB-24MCC X Multi-Cd Strobe RSSG-24MCC X Multi-Cd Strobe RSSR-24MCC X Multi-Cd Strobe RSSWPA-2475W X Strobe Weatherproof RSSWPA-24MCCH X Strobe Weatherproof RSSWPG-24MCCH X Strobe Weatherproof RSSWPR-24MCCH X Strobe Weatherproof RSSWP-2475
Model 5600 Installation and Operation Manual A.
Smoke Detector/Base System Sensor4WT-B (12/24 Volt) System Sensor 4WTA-B (12/24 Volt) Detector Type Max Standby Current (mA) Alarm Current (mA) Photoelectric I3 w/Therm .05 23 .05 35 I3 Photo w/ Therm/ Sounder System Sensor 4WTR-B (12/24 Volt) I3 Photo w/ Therm/Relay .05 35 System Sensor 4WTAR-B (12/24 Volt) I3 Photo w/ Therm/ Sounder/Relay .05 50 System Sensor 4WITAR-B (12/24 Volt) I3 Photo w/ Isolated Therm/Sounder/Relay .05 50 I3 Loop Test/Maintenance Mod. .
Model 5600 Installation and Operation Manual A.3 Door Holders (UL Listed) Table A-3 list door holders that are compatible with the fire control panel. Table A-3 Compatible Door Holders MANUFACTURER A.
A.
Model 5600 Installation and Operation Manual 12 151450
Silent Knight Fire Product Warranty and Return Policy General Terms and Conditions • All new fire products manufactured by Silent Knight have a limited warranty period of 36 months from the date of manufacture against defects in materials and workmanship. See limited warranty statement for details. • This limited warranty does not apply to those products that are damaged due to misuse, abuse, negligence, exposure to adverse environmental conditions, or have been modified in any manner whatsoever.
Advanced Replacement Policy • Silent Knight offers an option of advance replacement for fire product printed circuit boards that fail during the first 6 months of the warranty period. These items must be returned with transportation charges prepaid and must be accompanied by a return authorization. • For advance replacement of a defective board, contact your local Silent Knight distributor or call Silent Knight at 800-328-0103 to obtain a RMA (Return Authorization) number and request advanced replacement.
Manufacturer Warranties and Limitation of Liability Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that the Products manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free, under normal use and service, from defects in material and workmanship for a period of thirty six months (36) months from the date of manufacture (effective Jan. 1, 2009).
Model 5600/5600C/5600HV Basic Operating Instructions These Instructions must be framed and displayed next to the5600 panel in accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems. Test the system in accordance to NFPA 72. Refer to Installation Manual P/N 151450 for more information regarding this control panel.
Silent Knight 12 Clintonville Road Northford, CT 06472-1610 203-484-7161 Fax: 203-484-7118 www.silentknight.