INTELLIKNIGHT 5820XL 5820XL-EVS Addressable Fire System Emergency Voice System Installation and Operations Manual Document LS10061-001SK-E 01/29/2015 Rev: F P/N LS10061-001SK-E:F ECN: 14-0574
Installation Procedure Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized.
Contents Section 1 Introduction ..................................................................................................................................................1 1.1 Overview of Basic System ........................................................................................................... 1 1.1.1 Addressable Fire Alarm Control/Communicator Hardware Features ................................... 1 1.1.2 5820XL-EVS Emergency Voice Hardware Features ...................................
Model 5820XL/ 5820XL-EVS Installation Manual 4.3 Battery Connection ...................................................................................................................... 2 4.3.1 RBB Accessory Cabinet ....................................................................................................... 3 4.3.1.1 Installing the RBB Accessory Cabinet and Batteries .................................................. 3 4.4 SBUS Wiring ...........................................................
4.14.5 Using a MR-201/T Control Relay From Air Products ........................................................ 35 4.14.6 Transmitter Activated by Dry Contacts ............................................................................. 37 Section 5 SK SLC Device Installation 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 List of SK SLC Devices ............................................................................................................... 1 List of SD SLC Devices ......................................
Model 5820XL/ 5820XL-EVS Installation Manual 7.2.4 View Module List .................................................................................................................. 3 Zone ............................................................................................................................................ 3 7.3.1 Edit Zone .............................................................................................................................. 3 7.3.1.1 Edit Zone Name ..........
.6.6.2 Daylight Saving Time Start and End ......................................................................... 30 7.6.7 Edit Banner ......................................................................................................................... 31 7.6.8 SLC Family ......................................................................................................................... 32 7.7 JumpStart Autoprogramming .............................................................................
Model 5820XL/ 5820XL-EVS Installation Manual 8.5.16.1 Reset Dialer ............................................................................................................... 7 8.5.16.2 Reset DSP USB ......................................................................................................... 7 8.5.17 Communicating with a Remote Computer .......................................................................... 8 8.5.18 Working with a Printer ................................................
.7.1 Adding an Amplifier .............................................................................................................. 9 9.7.2 Editing an Amplifier ............................................................................................................... 9 9.8 Event Priority ............................................................................................................................. 10 9.8.1 System Control ...............................................................
Model 5820XL/ 5820XL-EVS Installation Manual Section 12 Installation Records ..........................................................................................................................1 12.1 Detector and Module Point Record ............................................................................................. 1 12.2 Conventional Output Point Record .............................................................................................. 5 Appendix A Compatible Device ........
LS10061-001SK-E Section 1 Introduction The IntelliKnight 5820XL Fire Alarm Control/Communicator is an addressable fire control system that meets the requirements of UL 864. The 5820XL/EVS integrates an Emergency Voice System that meets the requirements of UL 864 and UL 2572. 1.1 Overview of Basic System The IntelliKnight 5820XL and 5820XL-EVS base system is packaged as an assembled stack of 3 circuit boards mounted to an aluminum housing. 1.1.
Model 5820XL/ 5820XL-EVS Installation Manual • • • Up to 32 mappable speaker circuits using a combination of EVS-50W, EVS-100W, EVS-125W, EVSINT50W and EVS-CE4's. Supports 25 Vrms or 70.7 Vrms speaker circuits using EVS-50W or EVS-100W. Supports 25 Vrms speaker circuits using EVS-125W. 1.1.
LS10061-001SK-E 1.3 Introduction Compatible Products Table 1-1 lists the products available from Silent Knight for use with the 5820XL and 5820XL-EVS. Table 1-1: 5820XL/EVS Compatible Products Type of Device Model Description SK Addressable SLC Devices See Section 5.1 for a list of compatible devices. SD Addressable SLC Devices See Section 5.2 for a list of compatible devices. 5815XL SLC Expander Allows an additional 127 SD devices or 99 SK detectors and 99 SK modules to be added to the system.
Model 5820XL/ 5820XL-EVS Installation Manual LS10061-001SK-E The following modems have been tested by Silent Knight for compatibility with the IntelliKnight 5820XL and 5820XL-EVS and the Silent Knight Software Suite software packages: Table 1-2: Compatible Modems Manufacturer US Robotics Model 28.8 LifeStyle Motorola 28.8, 3400 series Premier 33.6 MultiTech 1.
LS10061-001SK-E • • • • • • • Introduction not disconnect the smoke detector; call a professional to analyze the situation and recommend a solution. Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially within bedrooms), smoking in bed, violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Model 5820XL/ 5820XL-EVS Installation Manual • • • • • • • LS10061-001SK-E It is recommended that more than one smoke detector shall be installed in a hallway if it is more than 30 feet long. It is recommended that there shall never be less then two smoke detectors per apartment or residence. It is recommended that smoke detectors be located in any room where an alarm control is located, or in any room where alarm control connections to an AC source or phone lines are made.
LS10061-001SK-E Section 2 Agency Listings, Approvals, and Requirements 2.1 1. Federal Communications Commission (FCC) The following information must be provided to the telephone company before the 5820XL or 5820XL-EVS can be connected to the phone lines: A Manufacturer: Silent Knight by Honeywell B Model Number: IntelliKnight 5820XL and 5820XL-EVS C FCC registration number: AC6USA-23901-AL-E Ringer equivalence: 0.
LS10061-001SK-E Agency Listings, Approvals, and Requirements or a qualified installer. Warning This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions: (1) This device may not cause radio interference, and (2) This device must accept any interference received, including interference that may cause undesired operation. 2.2 2.2.1 Underwriters Laboratories (UL) Requirements for All Installations General requirements are described in this section.
Model 5820XL/ 5820XL-EVS Installation Manual 2.2.3 LS10061-001SK-E Requirements for Local Protected Fire Alarm Systems At least one UL listed supervised notification appliance must be used. 2.2.4 Requirements for Remote Station Protected Fire Alarm Systems 1. Do not exceed the current draw load restrictions shown in Section 3.6. 2. The AC Loss Hours option must be set from 15-30 hours.
LS10061-001SK-E Section 3 Before You Begin Installation This section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly, especially if you are installing a 5820XL/EVS panel for the first time. 3.
LS10061-001SK-E 3.3 Before You Begin Installation Electrical Specifications Table 3-1: Terminal Descriptions and Electrical Specification Rating Terminal # and Label Description Voltage 1 L AC input (hot) 2 3 N 4 X 5 O 6 X 7 O 8 X 9 O 10 X 11 O 12 X 13 O 14 X 15 O 16 B 17 A 18 + 19 - 20 B 21 A 22 + 23 - 24 N.C. 25 C 26 N.O. 27 N.C. 28 C 29 N.O. 2.7 A N/A Earth ground N/A N/A N/A AC input (neutral) 120 VAC, 60 Hz 2.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Table 3-1: Terminal Descriptions and Electrical Specification Rating Terminal # and Label Description Voltage 35 SC- L2 36 SC+ SLC IN 37 Ring Phone Line 1 Telco Ring 38 Tip Phone Line 1 Telco Tip 39 Ring Phone Line 1 Premises Ring Current Used for Class A installations 0 N/A 0 N/A 0 40 Tip Phone Line 1 Premises Tip 41 Ring Phone Line 2 Telco Ring 42 Tip Phone Line 2 Telco Tip 43 Ring Phone Line 2 Premises R
LS10061-001SK-E Before You Begin Installation Figure 3-1 Wire Routing Example 3-4
Model 5820XL / 5820XL-EVS Installation Manual 3.5 LS10061-001SK-E Board Assembly Diagram On-board Annunciator To AC Chassis Mounting Nuts Chassis Mounting Nuts Key Switch Input Programming Ports Figure 3-2 Model 5820XL / 5820XL-EVS Assembly Figure 3-2 shows the circuit boards, metal housing and annunciator that attach the 5820XL / 5820XL-EVS assembly to the cabinet. If you should need to remove the board assembly for repair, remove the four mounting nuts which hold the assembly in the cabinet.
LS10061-001SK-E 3.6 Before You Begin Installation Calculating Current Draw and Standby Battery This section is for helping you determine the current draw and standby battery needs if you are using SK addressable devices (Table 3-2) or SD addressable devices (Table 3-3). 3.6.1 Current Draw Worksheet Requirements The following steps must be taken when determining 5820XL/5820XL-EVS current draw and standby battery requirements. 1.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Table 3-2 Current Draw Worksheet for SK SLC Devices Device # of Devices Standby Current Current per Device Alarm Current Addressable SLC Detectors SK-PHOTO mA mA SK-PHOTO-T mA mA SK-ION mA mA mA mA mA mA SK-ACCLIMATE mA mA SK-HEAT-ROR mA mA mA mA SK-HEAT Standby/Alarm: SK-HEAT-HT 5 SK-DUCT (includes PhotoR) (99 max/loop & 396 max/ panel)1 SK-BEAM (without integral test) SLC Aux.
LS10061-001SK-E Before You Begin Installation Table 3-2 Current Draw Worksheet for SK SLC Devices Device # of Devices Standby Current Current per Device Alarm Current SLC Modules Aux Pwr Standby: .50 mA Alarm: 35 mA SLC Standby .30 mA mA Aux Standby .50 mA mA Alarm (high vol) 35 mA SLC Standby .30 mA mA Aux Pwr Standby: 1 mA mA Alarm: 125 mA Aux Standby .55 mA Alarm (high vol) 140 mA SLC Standby .
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Table 3-2 Current Draw Worksheet for SK SLC Devices Device # of Devices Standby: EVS-INT50W Internal Amplifier Notification Devices (4 max.) Standby Current Current per Device 52 mA Alarm Current mA Alarm @ 25V: 275 mA mA Alarm @ 70V: 310 mA mA Refer to devices manual for number of devices and current rating.
LS10061-001SK-E 3.6.3 Before You Begin Installation Current Draw Worksheet for SD SLC Devices Use to determine current requirements during alarm/battery standby operation when SD SLC devices are installed. You can install up SD devices per loop (Max per panel). Copy this section if additional space is required.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Table 3-3: Current Draw Worksheet for SD SLC Devices Device 5883 Relay Interface # of Devices EVS-SW24 Switch Expander EVS-50W or EVS-125W Audio Amplifier with/without EVS-CE4 EVS-INT50W Internal Amplifier Notification Devices EVS-RVM Remote Voice Module * The EVS-RCU contains one EVS-RVM and must be added to the calculation here EVS-100W 100W Amplifier EVS-100WBU backup daughter card (4 max.) (4 max.) (4 max.
LS10061-001SK-E 3.6.4 Before You Begin Installation Maximum Battery Standby Load Table 3-4 shows the maximum battery standby load for the 5820XL/5820XL-EVS based on 24 and 60 hours of standby. The standby load calculations of line D in the Current Draw Calculation Worksheet (Table 3-2 for SK devices and Table 3-3 SD devices), must be less than the number shown in Table 3-4 for the battery size used and standby hours required. Table 3-4: Maximum Battery Standby Load Rechargeable Battery Size Max.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E See Sec. (for more info.) Task SLC Device Hardware Installation Perform these steps before running JumpStart. Connect device bases to the loop. SK 5.5 SD 5.7 Set device addresses. SK 5.6 SD 5.8 Physically connect detectors to their bases. Connect relay and contact monitor modules. 5.4 & see device install instructions JumpStart AutoProgramming JumpStart is for initial system programming.
LS10061-001SK-E Before You Begin Installation See Sec. (for more info.) Task Output Point Configuration Conventional notification circuits (circuits 1-6): Enable circuits used for notification appliances through programming (if necessary). (JumpStart enables circuits 1-6 as Notification.) 7.5 Conventional relay circuits (circuits 7-8): Select options for relay circuits, if desired.
LS10061-001SK-E Section 4 Control Panel Installation Caution! To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while installing or servicing. 4.1 Mounting the Control Panel Cabinet Read the environmental specifications in Section 3.2 before mounting the control panel cabinet. This will ensure that you select a suitable location. The panel should be accessible to main drop wiring runs.
LS10061-001SK-E 4.2 Control Panel Installation AC Connection At installation, connect the AC terminals to the power source as shown in Figure 4-1. It may be necessary for a professional electrician to make this connection. Warning To reduce the risk of electric shock, this product is provided with a grounding type power supply cord. Connect product to a grounded receptacle. The AC terminals are rated at 120 VAC, 60 Hz, 2.7A. Figure 4-1 120 VAC Power Connection for the 5820XL/EVS 4.
Model 5820XL / 5820XL-EVS Installation Manual 4.3.1 LS10061-001SK-E RBB Accessory Cabinet The Model RBB Accessory cabinet can be used when your backup batteries requirements use backup batteries that are too large to fit into the main control panel cabinet. The RBB cabinet holds batteries up to the 35 AH size. The RBB dimensions are 16" W x 10" H x 6" D (40.64 cm W x 25.4 cm H x 15.24 cm D). 4.3.1.
LS10061-001SK-E 3. Control Panel Installation Run extended battery cable from control panel cabinet through conduit to RBB cabinet. See Figure 4-5. RBB Cabinet Cover Screws Conduit Coupler Conduit - + + - RBB Cabinet Cover Screws Figure 4-5 Battery Connections in the RBB Cabinet Note: Figure 4-5 is an example of how the wire connections can be routed.
Model 5820XL / 5820XL-EVS Installation Manual 4.4.1 LS10061-001SK-E Calculating Wiring Distance for SBUS Modules The following instructions will guide you in determining the type of wire and the maximum wiring distance that can be used with control panel SBUS accessory modules. To calculate the wire gauge that must be used to connect SBUS modules to the control panel, it is necessary to calculate the total worst case current draw for all modules on a single 4-conductor bus.
LS10061-001SK-E Control Panel Installation These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet, regardless of gauge used. The formula used to generate this chart is shown in the note below. Table 4-1: Wire Distances Per Wire Gauge Using Copper Wire Wiring Distance: SBUS Modules to Panel Total Worst Case Current Draw (amps) 22 Gauge 18 Gauge 16 Gauge 14 Gauge 0.100 1852 ft. 4688 ft. * 6000 ft. * 6000 ft. 0.200 926 ft. 2344 ft. 3731 ft.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E The total worst case current is calculated as follows: 5860 Current Draw = 2 x .100 amps = .200 amps 5895XL Current Draw = 1 x .010 amps = .010 amps 5865 Current Draw = 1 x .200 amps = .200 amps 5824 Current Draw = 1 x .040 amps = .040 amps Total Worst Case Current Draw = .
LS10061-001SK-E Control Panel Installation Supervised Power Limited Figure 4-8 SBUS Class B Wiring 4.5 5860 Remote Annunciator Installation The optional Model 5860 Remote Annunciator, shown in Figure 4-9, performs the same functions as the onboard annunciator. It can initiate and end fire drills with a single key press and view event history by alarms, supervisories, or troubles. Up to 12 annunciators can be added to the IntelliKnight 5820XL / 5820XL-EVS system.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E 5860 installation involves the following steps: 1. Make sure power is off at the panel. 2. Mount the 5860 in the desired location (see Section 4.5.1). 3. Connect the 5860 to the panel (see Section 4.5.2). 4. Use the DIP switches on the back of the 5860 to assign an ID# to the 5860 (see Section 4.10.1). 5. The new 5860 module must be added to the system through programming. JumpStart will add the module automatically (see Section 6.2).
LS10061-001SK-E Control Panel Installation The 5860 comes from the factory fully assembled. You must disassemble it for mounting. To disassemble the annunciator, use a 5/64 hex wrench to remove the set screws, located on the bottom of the annunciator bezel. (See Figure 4-11 for location of the set screws). Holes for surface mounting. Stand-off (throughout) Holes for inserting wires for flush mounting (located in all corners). Knockout holes Screw for placement of mounting wires (top and bottom).
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E annunciator. Studs used with an electrical box must be two by fours (or larger). Electrical Box Placement Examples of Electrical Box Use wall Sheet rock studs annunciator back box (outline) Annunciator back box electrical box When flush-mounting using an electrical box, the box must be 1-3/8" from face of wall. Electrical box applications require 2 by 4 construction minimum.
LS10061-001SK-E Control Panel Installation 4.5.1.2 Surface Mounting The 5860 can be mounted directly to a surface or can be attached to a single, double, or four-square electrical box. The Model 5860TG/TR trim ring kit is available for use when surface mounting. 1. Drill holes in the surface to match the screw holes on the back box. 2. Fit the trim ring over the back box. 3. Attach the back box to the surface using screws provided. 4.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Figure 4-15 is a drawing of the 5815XL board, showing the location of terminals and DIP switches. Figure 4-15 5820XL Board 4.6.1 5815XL Connection to the Panel Connect the 5815XL to the control panel as shown in Figure 4-16. After the 5815XL is connected to the panel, it must be added to the system. This programming step is described in Section 4.10.
LS10061-001SK-E 4.7 Control Panel Installation 5824 Serial/Parallel Interface Module Installation The 5824 serial/parallel interface module allows you to connect a printer to the panel, so you can print a real-time log of system events, a report of detector status, and event history. Instructions for installing the 5824 appear below. The 5824 and the printer connected to the 5824 Parallel port is ancillary, the serial port can be used for primary fire signaling.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Model 5824 (with housing) To Parallel Printer To Serial Printer Figure 4-18 Printer Connection 4.7.1 Selecting 5824 Options Configuring the 5824 includes the following steps: • • • Add the module to the system. JumpStart will add the module automatically (see Section 6.2). You can also add it manually (see Section 7.2.2). Select a name, if desired (see Section 7.2.1.1). Select options for the printer and the output port. See below.
LS10061-001SK-E 7. Control Panel Installation If you are using a serial printer, use the next screen to select serial port options as required for your printer. Refer to your printer manual if you need more information. Option 4.8 Choices Baud Rate: 75 - 19200 Data Bits: 5-8 Stop Bits: .
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E connected to the panel, it must be added to the system. This programming step is described in Section 4.10.
LS10061-001SK-E 4.8.3 Control Panel Installation LED Wiring There are four 12-pin connectors on the 5880 board for connecting LEDs. Each LED gets its power from Pin 11. Internal resistors are sized so that there is approximately 10 mA of current for each LED, no series resistors are required. LED outputs can be mapped to output circuits. See Section 6 for programming details. Wire the LEDs as shown in Figure 4-22. On connector P1, Pin 12 is an open collector output for controlling a PZT.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E inputs. Supervised 4.
LS10061-001SK-E 4.9 Control Panel Installation 5865-3 / 5865-4 LED Annunciator Installation The 5865-3 and 5865-4 are LED annunciators. The 5865-4 has 30 mappable LEDs, remote silence and reset key switches, and a general system trouble LED. The 5865-3 has 30 mappable LEDs only. These are arranged as 15 pairs of red (typically used for alarm) and yellow (typically used for trouble) LEDs. Installation of the 5865-5 and 5865-4 is identical.
Model 5820XL / 5820XL-EVS Installation Manual 4.9.2 LS10061-001SK-E 5865 Mounting Mount the 5865-4 to a standard 4-gang electrical box. Mount the 5865-3 to a standard 3-gang electrical box. In Figure 4-26, the 5865-4 attached to a 4-gang box is used as an example. Figure 4-26 5865 Mounting Example The 5865 ships with a set of zone description labels that can be inserted into the 5865 board assembly. These labels can be used in a typewriter or can be written on by hand.
LS10061-001SK-E Control Panel Installation 4.10 Configuring Modules This section describes how to configure any system hardware modules that have been added to the system. 4.10.1 Assigning SBUS Module IDs When installing a hardware module (such as, 5815XL, 5824, 5860, 5496, 5895XL, 5865-3, 5865-4, EVS-50W, EVS-125W, EVS-100W, EVS-RVM, or EVS-VCM), you must use the DIP switches on the module to assign an ID# to the module.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E 4.11 Telephone Connection Connect the telephone lines as shown in Figure 4-29. The Model 7860 phone cord is available from Silent Knight for this purpose. A number of programmable options are available for customizing telephone lines. These options are described in Section 7.6. Figure 4-29 Connection of Telephone Lines 4.12 Flexputs™ I/O Circuits The six Flexput™ circuits are an innovative and versatile feature of the control panel.
LS10061-001SK-E Control Panel Installation 4.12.1.1 Class B Notification Wiring You must use an appliance from the list of compatible appliances in the Appendix A at the back of this manual. To install a circuit: 1. Wire Class B Notification appliances as shown in Figure 4-30. 2. Configure the circuit through programming (see Section 7.5). Alarm Polarity Shown. 4.7 kEOL Notification Wiring Max. Impedance: 1.5 Regulated 24 VDC Full Wave Rectified 27.
Model 5820XL / 5820XL-EVS Installation Manual 2. LS10061-001SK-E Configure the circuit for Class A in programming (see Section 7.5). Supervised Power Limited Regulated 24 VDC Full Wave Rectified 27.4 VDC, 3A per Circuit, 6A max Combined Figure 4-31 Class A Notification Appliance Circuit Configuration Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to refer to the circuit pair.
LS10061-001SK-E Control Panel Installation 4.12.2.1 Class B Inputs You can connect conventional Class B switches, such as waterflow switches and pull stations, directly to the Flexput circuits of the control panel. To install a Class B switch: 1. Wire the Class B switch as shown in Figure 4-32. 2. Configure the circuit through programming (see Section 7.5). Supervised Power Limited 4.7 kEOL Figure 4-32 Class B Input Switches 4.12.2.
Model 5820XL / 5820XL-EVS Installation Manual 2. LS10061-001SK-E Configure the circuit through programming (see Section 7.5). Supervised Power Limited Note: Flexput circuit 5 and 6 used as an example. Any Flexput point pairing could be used. Figure 4-33 Class A initiating Switches Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to refer to the circuit pair.
LS10061-001SK-E Control Panel Installation 4.12.3.2 Installing 2-Wire Class A Smoke Detectors To install a Class A two-wire smoke detector, wire as shown in Figure 4-35. Supervised Power Limited Note: Flexput circuit 5 and 6 used as an example. Any Flexput point pairing could be used. Figure 4-35 Two-Wire Class A Smoke Detector Connections Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to refer to the circuit pair.
Model 5820XL / 5820XL-EVS Installation Manual 3. LS10061-001SK-E Each loop gets smoke power from the even numbered Flexput circuit and the contact input is connected to the odd numbered Flexput circuit. Supervised Power Limited 4.7 kEOL Note: Flexput circuit 5 and 6 used as an example. Any Flexput point pairing could be used.
LS10061-001SK-E Control Panel Installation Note: In programming any point that uses multiple Flexput circuits are always referred to as the lowest Flexput circuit number used. For example, Figure 4-37 uses Flexput circuits 1, 2, 3 together and 4, 5, 6 together. In programming (1, 2, 3) would be referred to as point 1, and (4, 5, 6) would be referred to as point 4. 4.12.5 Auxiliary Power Installation Flexput Circuits 1-6 on the control panel can be used as auxiliary power circuits.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E 4.12.5.4 Sounder Sync Power Sounder Sync Power continuously outputs the System Sensor synchronization pattern and is intended for use with B200S sounder bases. 4.13 On-Board Relays (Conventional) The control panel has two built-in programmable relays and a built-in trouble relay. All relays are Form C rated at 2.5 A @ 24 VDC. Figure 4-39 Location of Conventional Relay Circuits 4.13.
LS10061-001SK-E 5. Control Panel Installation Program Flexput circuit 6 for supervisory non latching. Table 4-3: Keltron 3158 to Control Panel Connections Terminal # Connects To Terminal # Connects To 3158 Term. 1 To Keltron receiving equipment 3158 Term. 8 Control panel Term. 28 3158 Term. 2 To Keltron receiving equipment 3158 Term. 9 Control panel Term. 5 3158 Term. 3 Earth ground 3158 Term. 10 Control panel Term. 4 3158 Term. 4 Not used; no connection. Control panel Term.
Model 5820XL / 5820XL-EVS Installation Manual 4. LS10061-001SK-E Program the Flexput circuit used as a notification circuit, continuous and non-silencing. Refer to Section 7.5 for point programming, Section 7.5 for group settings, and Section 7.3 for zone settings and mapping. It is not possible to reset the remote indication until you clear the condition and reset the control panel. Note: Flexput Circuit 1 Used as an example. Any Flexput circuit could be used.
LS10061-001SK-E 5. Control Panel Installation If necessary, adjust loop current using the potentiometer (R10) on the 5220 board. Normal loop current is 2to-8 mA with a 1k ohm remote station receiving unit. Maximum loop resistance is 3k ohm. Note: Flexput circuit 1 and Relay 1 used as examples. Any Flexput circuit and either relay 1 or relay 2 could be used. All circuits power-limited. All wiring supervised. Jumper these terminals when City Box is not used.
Model 5820XL / 5820XL-EVS Installation Manual 4.14.4 LS10061-001SK-E Using the SD500-ARM Addressable Relay Module When the SD500-ARM is wired for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset. Wire the SD500-ARM as shown in Figure 4-44.
LS10061-001SK-E 1. Control Panel Installation Wire the MR-201/T as shown in Figure 4-45. Intended for Connection to a Polarity Reversal Circuit of A Remote Station Receiving Unit Having Compatible Rating. Figure 4-45 Wiring the MR-201/T 2. Program the Flexput circuit for non silence NAC circuit (see Section 7.5).
Model 5820XL / 5820XL-EVS Installation Manual 4.14.6 LS10061-001SK-E Transmitter Activated by Dry Contacts This section describes the connection of a UL 864 listed remote station transmitter to the 5820XL / 5820XL-EVS FACP dry contacts. The FACP contacts must be supervised by the remote station transmitter module using endof-line resistors (ELRs) with a value determined by the transmitter manufacturer. Power is also provided by the remote station transmitter manufacturer.
LS10061-001SK-E Section 5 SK SLC Device Installation Caution! To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while installing or servicing. 5.1 List of SK SLC Devices The following SK SLC devices can be used with the control panel. SK detectors include a 6" base. See the appropriate section number in this manual or the device installation instructions (packaged with the device) for more information.
LS10061-001SK-E SK SLC Device Installation SK Part Number Model Name/Description Installation Instruction PN B200S Sounder Base I56-3387-00 B201LP 6" mounting base I56-0595-00 B224BI 6" isolator base I56-0725-00 B224RB 6" relay base I56-3737-00 B200SR Sounder base I56-3392-00 B501 4" mounting base I56-0357-00 B200SR-LF Low Frequency Sounder Base I56-4152-00 B200S-LF Low Frequency Sounder Base I56-4151-00 5.
Model 5820XL / 5820XL-EVS Installation Manual 5.3 LS10061-001SK-E Maximum Number of Devices The 5820XL/5820XL-EVS supports SK or SD devices on one system. The maximum number of devices per system varies depending on device protocol and the number of 5815XL signaling circuit loop (SLC) expanders added to the system. Device support is as follows: • SK Devices–A system can support a total of 396 SK detectors and 396 SK modules. 99 devices can be added to 5820XL/5820XL-EVS control panel.
LS10061-001SK-E SK SLC Device Installation Figure 5-1 and Figure 5-2 show how wire length is determined for out & back tap and T-Tap style wiring. Figure 5-1 Calculating wire run length for a simple out and back When using T-taps, the total length of all taps and the main bus must not exceed 40,000 feet. This requirement must be met in addition to the maximum distance requirements for the various wire gauges.
Model 5820XL / 5820XL-EVS Installation Manual 5.4.2 LS10061-001SK-E Wiring 5815XL in Style 6 & 7 (Class A) Configuration The following figure illustrates how to wire the SLC loop for Style 6 or Style 7 Class A installations. Note: Style 6 does not use short circuit isolator devices. Note: Style 7 wiring requires an isolator module as the first device on the in and the out loops. Note: No t-taps allowed on class A SLC loops.
LS10061-001SK-E SK SLC Device Installation To wire SK detectors: 1. Wire device bases as shown in Figure 5-4. 2. Set the address for each device as described in Section 5.6. Caution: Do not loop wire under Terminal 1 or 2. Break wire run to provide supervision of connections. Figure 5-4 Heat and Smoke Detector Connection to the Panel. 5.6 Addressing SK SLC Devices All SK devices are addressed using the two rotary dials that appear on the device board.
Model 5820XL / 5820XL-EVS Installation Manual 5.7 LS10061-001SK-E Wiring SD SLC Detectors This section describes how to install SD heat and smoke detectors. All detectors ship with installation instructions. Refer to each detectors' installation instructions for more detailed information. This information applies to the following SD models: • SD505-AHS Heat Detector • SD505-AIS Ionization Smoke Detector • SD505-APS Photoelectric Smoke Detector To wire SD505-APS, SD505-AHS, or SD505-AIS detectors: 1.
LS10061-001SK-E 5.8 SK SLC Device Installation Addressing SD Devices This section explains how to address SD detectors and modules. 5.8.1 SD505-APS, SD505-AHS, and SD505-AIS The SD505-APS photoelectric smoke detector, SD505-AHS heat detector, and SD505-AIS ionization smoke detector are easily addressed at the FACP. An access code with the option to Set SLC Device Address enabled is required to perform this task. To address a SD505-APS, SD505-AHS, and SD505-AIS: 1.
Model 5820XL / 5820XL-EVS Installation Manual 5.8.2 LS10061-001SK-E SLC Devices with DIP Switches Input and relay module addresses are set using the DIP switches on the module board. The chart below shows the available addresses. For example, to select address 3, place DIP switches 1 and 2 in the up position. The range of valid addresses is 1-127. 0 is an invalid address.
LS10061-001SK-E Section 6 Programming Overview This section of the manual is intended to give you an overview of the programming process. Please read this section of the manual carefully, especially if you are programming the control panel for the first time. The JumpStart AutoProgramming feature automates many programming tasks and selects default options for the system. You should run JumpStart at least once when you are installing the system. See Section 6.2 for details.
LS10061-001SK-E 6.2.1 Programming Overview Input Points JumpStart will determine the number and type of input points (detectors or contact monitor modules) on each SLC loop. JumpStart assigns the correct detector type (heat, ionization or photoelectric), so the installer does not need to edit the device type for detectors. Any contact monitor modules on the system will be assigned type “Manual Pull.” The installer will need to manually change the switch type if manual pull is not correct.
Model 5820XL / 5820XL-EVS Installation Manual 6. LS10061-001SK-E Select one of the following options from the menu that displays. 1 - Review System Press 1 if you need to review the JumpStart configuration. 2 - Repeat JumpStart Press 2 if you need to rerun JumpStart for any reason. 1. If you are ready to make the JumpStart configuration permanent, select 3. 2. The system will ask you if the installation contains duct detectors. If there are none, select 2 for No and skip to Step 8.
LS10061-001SK-E 6.3 Programming Overview Mapping Overview This section of the manual is an overview of mapping. Details about how to select mapping options appear in the appropriate subsections in Section 7. Mapping is an important concept with the control panel. In general terms, mapping is assigning or linking events to outputs that should activate when events occur.
Model 5820XL / 5820XL-EVS Installation Manual 6.3.1 LS10061-001SK-E Input Point Mapping Input points are assigned to input zones, as the example in Figure 6-2 shows. Any input point can be assigned to any input zone. (Input points can be assigned to one zone only. An input point can be designated as “Unused,” which means it has not been assigned to a zone).
LS10061-001SK-E 6.3.2 Programming Overview Output Circuit Mapping Figure 6-3 is a simple example showing how to assign notification and relay output circuits to groups. For an example of a simple floor above/floor below application, see Figure 6-5.
Model 5820XL / 5820XL-EVS Installation Manual 6.3.3 LS10061-001SK-E Zone Event Mapping There are 11 types of events that can occur in zones (see below). For each event type, you can activate up to 8 output groups and patterns. If it is necessary to map to more than 8 output groups, an output group template may be used (see Section 7.4.5 for information on output group templates).
LS10061-001SK-E Programming Overview Figure 6-5 Example of Zone Events Mapped to Output Groups and Patterns 6-8
Model 5820XL / 5820XL-EVS Installation Manual 6.3.4 LS10061-001SK-E Mapping LED Points Figure 6-6 is a simple example showing how LED points are mapped to zones and output groups. Typically you would create two output groups for each zone, one for alarms and one for troubles. (LED points are available when Models 5865-3/4 and/or 5880 are used with the system.) Figure 6-6 Example of LED Points Mapped to Output Groups (Applies to Models 5865-3/4 and 5880) 6.
LS10061-001SK-E Programming Overview panel’s onboard USB or serial port or remotely using a modem. If you need to connect to an older control panel that does not have a USB port, and your laptop does not have a serial port, use a USB to serial converter. SKSS is available for download online. See the SKSS manual (PN 151240) for more information. *Modems not sold by Silent Knight. See Table 1-2 for a list of modems that have been tested for compatibility with the control panel and SKSS. 6.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E 6.5.1.1 Moving through the Menus Figure 6-8 shows how to move through Program Menu screens, using the System Options screen as an example. Figure 6-8 Moving through Program Menu 6.5.1.2 Selecting Options and Entering Data There are several ways to make programming selections using the control panel depending on which screen you are currently viewing. The chart below is a generic explanation.
LS10061-001SK-E Programming Overview 6.5.1.3 Editing Keys The keys shown in Figure 6-9 are available for use when you are in the program menu.
Model 5820XL / 5820XL-EVS Installation Manual 6.6 LS10061-001SK-E Programming Menu Quick Reference This section of the manual lists all Program Menu options in the order they appear on the sub-menus. Default settings are indicated in text or marked with an asterisk (*). The comments column provide quick information and a reference to a section (if applicable) which has more detailed information.
LS10061-001SK-E Programming Overview Table 6-1: Programming Quick Reference Table Menu Options/Defaults(*) CO Alarm (CO) Zone Outputs CO Supervisory (Sco) Edit Zone Select Zone to Edit Cadence Zone Fire Cadence Accessory Opt CO Cadence Local Zone Zone Add Zone Delete Zone View Zone Points 00, 01, *02, 23 SK Devices. Section 00, 01, 02, *23 7.3.1.4, Section 7.3.1.5 Y or *N Section 7.3.1.5 Section 7.3.2 Section 7.3.4 Silencing Options Select Group SD Devices. Section 7.3.1.4, Section 7.3.1.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Table 6-1: Programming Quick Reference Table Menu Options/Defaults(*) Edit Group Select Group Group Properties Group1 Voice EVAC Only Allow Override ECS Only *Y or N Voice Switch # *00 - 40 (Voice Section 7.4.1.2 Group: *01) Override Cadence Pattern *00-21, 23 Delay 05-60 minutes (*15) Add Group Point Comments Y or *N (Default Voice Group 2: *Y) Section 7.4.2 Delete Group Select Group to Delete Section 7.4.
LS10061-001SK-E Programming Overview Table 6-1: Programming Quick Reference Table Menu Options/Defaults(*) DETECTOR Point (cont.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Table 6-1: Programming Quick Reference Table Menu Options/Defaults(*) SUP DET Sensor Point # CO FIRE Point (cont.
LS10061-001SK-E Programming Overview Table 6-1: Programming Quick Reference Table Menu Options/Defaults(*) SYS_AUX1, SYS_AUX2 SWITCH Internal and External 5815XL, SK Device Module Point # STATUS PT Point (cont.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Table 6-1: Programming Quick Reference Table Menu Options/Defaults(*) Comments UNUSED PHOTO, ION, HEAT Point (cont.
LS10061-001SK-E Programming Overview Table 6-1: Programming Quick Reference Table Menu Options/Defaults(*) PHOTO, ION, HEAT Point (cont.) Internal and External 5815XL, SD Devices Point # SUP DET PHOT DUCT, ION DUCT 6-20 Comments *Latching (LA) or NonLatching (NL) *Silenceable (SI) or NonSilenceable (NS) Zone # (*001) *NO ACCESSORY, SDR BAS, RLY BAS Single/Multi Station: *NST, SST, MST Station Silenceable: *SIL, NSL Accessory Group # (*001) Point Name Section 7.5.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Table 6-1: Programming Quick Reference Table Menu Options/Defaults(*) SWITCH Point (cont.) Internal and External 5815XL, SD Devices Point # NOTIF RELAY SLC LED Comments *Silenceable (SI) or NonMAN_PULL, Silenceable PAS_ACK, DET SW, (NS) MAN REL, ILOCK, CO DET SW Zone # (*001) Point Name *Latching (LA) or NonLatching (NL) WATERFLOW, SUPERVSY, *Silenceable ZN_AUX1, ZN_AUX2, (SI) or NonTAMPER Silenceable (NS) Zone # (*001) Section 7.5.
LS10061-001SK-E Programming Overview Table 6-1: Programming Quick Reference Table Menu Options/Defaults(*) Comments UNUSED Point (cont.) Internal Pwr and External Power Group # (*001) Point Name Group # (*001) Point Name B NOTIF NOTIF OUT, CTRL CKT A NOTIF NOTIF OUT, CTRL CKT AUX PWR CONSTANT, AUX RESET, AUX DOOR, AUX SYNC B SWITCH *Silenceable (SI) or NonMAN _PULL, Silenceable PAS_ACK, MAN REL, (NS) ILOCK Zone # (*001) Point Name *Latching (LA) or NonLatching (NL) WATERFLOW, Section 7.5.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Table 6-1: Programming Quick Reference Table Menu Options/Defaults(*) A SWITCH B DETECTOR Internal Pwr and External Power 2WIRE SMK, 4WIRE SMK, CO 4WIRE Point # A DETECTOR Comments Same as B SWITCH 2WIRE SMK, 4WIRE SMK, CO 4WIRE *Silenceable (SI) or NonSilenceable (NS) Zone # (*001) Point Name *Silenceable (SI) or NonSilenceable (NS) Zone # (*001) Point Name Section 7.5.2 UNUSED Point (cont.
LS10061-001SK-E Programming Overview Table 6-1: Programming Quick Reference Table Menu Options/Defaults(*) Comments UNUSED NOTIF 5880 Point # SWITCH Point (cont.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Table 6-1: Programming Quick Reference Table Menu Options/Defaults(*) Reporting Accounts System Options Phone Lines Comments Account # (6-digit number, identifies Edit Account # *123456 account to central station) Section 7.6.1.1 Reporting Format (SIA, Edit Format *CID, S20, SIA S20, Contact ID) Section 7.6.1.1 Yes (Y), *No Report Alarms (N), or Must (M) Yes (Y), *No Rep. Alarm Restore (N), or Must Choose Edit Acct.
LS10061-001SK-E Programming Overview Table 6-1: Programming Quick Reference Table Menu Options/Defaults(*) Select Group (*None) Select Cadence (*None) Select Group (*None) Alarm Silence Select Cadence (*None) Select Group (*None) Trbl Silence Select Cadence (*None) Group Tr SBUS Com SBUS Pwr SLC Loop AC Loss Battery User Selected Gnd Flt Phone Ln Account Printer Aux Pwr Sys Sw Fire Drill 00-21, 23 Cadence System Aux1 00-21, 23 Cadence System Aux2 00-21, 23 Cadence Comments System Trouble Trouble Event
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Table 6-1: Programming Quick Reference Table Menu System Options (cont.) Jump Start AutoPrg Computer Account Options/Defaults(*) Y (Enabled) SYNC Strbs w/ Sil N (Disabled) Y (Enabled) Auto Display Oldest N (Disabled) Zone Misc.
LS10061-001SK-E Programming Overview Table 6-1: Programming Quick Reference Table Menu Options/Defaults(*) Comments Edit Name Edit Access Code Access Codes Select Profile (01-20) Panel Functions System Reset System Silence System ACK System Test Fire Drill Menu Indicator Test Walk Test no Report Walk Test with Report Dialer Test Clear History Buffer Point Functions Disable/Enable Point Point Status Set SLC Device Address SLC Device Locator SLC Mult-Device Locator I/O Point Control Event History Set
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Table 6-1: Programming Quick Reference Table Menu Options/Defaults(*) VCM Maintenance PC Connection Local Recording Edit Voice Commands Select Command Voice Options Enable EVS System EVS System Options Select Module Select Circuit Message/Tone Only Message 1-15 Select Tone Select 1-14 Repeats Continuous None 0 Initial Delay 3 4-28 (4 sec. increments) Inter Message 4-32 (4 sec.
LS10061-001SK-E Section 7 Programming This section of the manual describes how to manually program the control panel from the built-in annunciator. Each subsection discusses these menu options in detail. All options described in this section can be performed using 5660 Silent Knight Software Suite (SKSS). Important! Before any customized programming is done, JumpStart should be run first. After JumpStart is run, thoroughly test the system.
LS10061-001SK-E 7.2.1 Programming Edit Modules The features that can be edited when this option is selected are module ID, module name, class of wiring (Class A or Class B), or features that are specific to the module to be edited. To edit an existing module: 1. Enter the installer code. The panel will automatically go the main menu. 2. Select 7 for Program Menu. 3. Press 1 to enter module menu. 4. Press 1 to edit a module. 5. Use the 7.2.1.
Model 5820XL / 5820XL-EVS Installation Manual 5. From the next screen, use the Type> screen. or LS10061-001SK-E arrow to choose a module type to add from the screen where you can add additional modules if desired. You must save changes when you exit the Program Menu or the new module will not be added.
LS10061-001SK-E 7.3.1.1 6. Programming Edit Zone Name Press 1 to edit the selected zone’s name. A screen similar to the one shown in Figure 7-2 displays. Figure 7-2 Selecting Character for Zone Name 7. Select the characters for the zone name by pressing the or arrow until the desired character is shown then press the right arrow or see Appendix B of this manual for a list of available characters and their numeric designators. 8. Repeat step 8 until the name is complete. 9.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Table 7-1: Alarm Delay Characteristics Type of Delay Description 1-Count One Count (No Delay). When this option is enabled, an alarm occurs immediately when a single device of any of the following types goes into alarm: detector, manual pull, water flow, Zone AUX1 or Zone AUX2. This is considered the most typical operation and is the default for all zones.
LS10061-001SK-E Programming Mapping to Zone Events Eleven types of events can occur in zones. For each event type, you can activate up to 8 output groups or output group templates, specifying a pattern for each. The following is a list of all event types: Note: Abbreviations in the parenthesizes are the characters that are displayed in programming (see Figure 7-4). • • • • • • • • • • Manual Pull Alarm (MP) Water Flow Alarm (WF) Detector Alarm (DE). This applies to heat or smoke detectors.
Model 5820XL / 5820XL-EVS Installation Manual • LS10061-001SK-E Troubles would activate Output Group 2 using the zone-coded cadence pattern. To accomplish this you need to access the screen for each event and then select your output groups. Figure 7-5 shows how you would program this application. Figure 7-5 Zone Mapping Example 7.3.1.4 Cadence Patterns The cadence patterns shown in Figure 7-6 are available for use with the control panel.
LS10061-001SK-E Programming drills and any auxiliary system switches used with the system. Figure 7-6 Cadence Patterns Available with the Control Panel 7.3.1.5 Zone Accessory Options This option applies to detectors that are used with a Sounder base or Relay base. Fire Cadence:_ _ and CO Cadence:_ _ (choose from a subset of Cadence Patterns 00 to 23). Note: The B200S Sounder base is intended to be used along with the CO Cadence setting. Local Zone (choose Y or N, for Yes or No).
Model 5820XL / 5820XL-EVS Installation Manual 7.3.2 LS10061-001SK-E Add Zone To add a zone, follow these steps: 1. Enter the installer code. The panel will automatically go the main menu. 2. Select 7 for Program Menu. 3. Press 2 to enter zone menu. 4. Press 2 to add a zone. A zone of the next available zone number will be added. Options for this zone can now be programmed through the Zone Edit sub-menu. Up to 125 zones can be used. 7.3.3 Delete Zone To delete a zone, follow these steps: 1.
LS10061-001SK-E 7.4 Programming Group An output group is made up of output points that have been programmed to respond in the same way. Output groups simplify programming because you only have to program the output characteristics that are common to all of the group points once, instead of programming each individual point. Once you have defined the characteristics of output groups, you can assign each point to the appropriate group. All valid output points are assigned to only one output group.
Model 5820XL / 5820XL-EVS Installation Manual 7.4.1.2 1. 2. LS10061-001SK-E Edit Group Properties Follow steps 1-5 of section 7.4.1 To edit the group properties, press 2. The Edit Group Menu allows you to select options for each group for the following items: • • • • • Latching or non-latching outputs. Silencing operation. Reverse Polarity options. Operation with system switches. Define output group type as voice or non-voice and Allow Override. These options are for EVS Only. See Figure 7-9.
LS10061-001SK-E Programming Response with System-Wide Conditions You can select whether an output group will respond to various system-wide occurrences. (See Figure 7-9 for location of this field.) Table 7-3: Output Group Response Choices Option ManPull Description Manual Pull Activation. Select Yes if you want this group to activate for all manual pull alarms that occur in the system.
Model 5820XL / 5820XL-EVS Installation Manual 5. LS10061-001SK-E Select group to be deleted. Press ENTER to delete. A warning screen will display. If you want to proceed with deleting the group, select Yes. To cancel, select No. 7.4.4 View Group Points 1. Enter the installer code. The panel will automatically go to the main menu. 2. Select 7 for Program Menu. 3. Press 3 to enter group menu. 4. Press 4 to view group points. 5. Enter the group number, then press ENTER. 7.4.
LS10061-001SK-E 5. Programming Select output group number. See Figure 7-10. Yes = Include the selected output group in this template Output Group # No = Do Not include output group in this template Select the Cadence Pattern Figure 7-10 Output Group Template Programming Screen 7.5 Point You may need to change characteristics of individual input points (detectors and switches) even after using JumpStart.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E 10. Select the function of the device by pressing the ing “Function” for a list of choices. or arrows.
LS10061-001SK-E Programming Table 7-5: Point Programming Options for 5815XL Modules Module Type Type Selection Function Latching Option Latching WATERFLOW Non Latching Comments Use this switch type for monitoring water flow in a sprinkler system. Switch closure will cause a sprinkler alarm. Water flow switches can be programmed as latching or non-latching. You can program a delay of up to 90 seconds to be used with a water flow switch.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Table 7-5: Point Programming Options for 5815XL Modules Module Type Type Selection Function SYSTEM AUX1 SYSTEM AUX2 SWITCH (cont.) TAMPER RELAY SD SLC LED Latching Comments Use these switch types if you want to monitor special system-wide conditions (such as operation of a fan or damper). Non Latching Used to monitor conventional 4-wire detectors, a contact closure will generate a detector alarm event.
LS10061-001SK-E 7.5.2 Programming Point Programming For Internal or External Power Module To program for an internal or external power module points: 1. Enter the installer code. The panel will automatically go to the main menu. 2. Select 7 for Program Menu. 3. Press 4 to enter point menu. 4. Press the 5. Press ENTER. 6. Enter the number of the circuit or point you wish to edit. Refer to Table 7-6 for available selections. 7. Press ENTER. 8. Select the type by pressing the 9.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Table 7-6: Menu choices for Internal/External Power Module Choices Type Selections Function Selections for each Type Comments Enter Point UNUSED B NOTIF NOTIF OUT A NOTIF CTRL CKT CONSTANT AUX PWR Constant auxiliary power. RESETTABLE Resettable auxiliary power. DOOR Door holder auxiliary power.
LS10061-001SK-E 7.5.3 Programming Point Programming For 5880, 5865, EVS-50W, EVS-INT50W, EVS-100W, EVS-125W and EVS-CE4 Modules To program 5880, 5865, EVS-50W, EVS-INT50W, EVS-100W, EVS-125W, or EVS-CE4 module points: 1. Enter the installer code. The panel will automatically go to the main menu. 2. Select 7 for Program Menu. 3. Press 4 to enter point menu. 4. Press the 5. Press ENTER. or arrows to select the desired module. Refer to Section 7.5.3 for available choices.
Model 5820XL / 5820XL-EVS Installation Manual 10. Press the or LS10061-001SK-E arrows to select the function. 11. Press ENTER. 12. Use the or arrows to modify and remaining options and use ENTER to move to the next field. 13. Edit module name. See Section 7.2.1.1. or, Press the right arrow to skip module name edit. 14. Repeat Steps 1 through 13 for all points.
LS10061-001SK-E 7.6 Programming System Options This section of the manual explains how to customize software options that affect general operation of the system. This includes such items as: AC loss reporting delay, system clock options, telephone and reporting account options. Refer to each individual subsection for complete instructions. 7.6.1 Reporting Account Up to four reporting accounts can be used with the control panel. Events in accounts are reported by zone.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Edit Account Number Enter an up-to-6-digit number for each account to identify the account to the central station. See Figure 7-12 for location of this option on the screen. The account number should be compatible with the reporting format used. For example, the Contact ID format transmits up to four digits only. 7. Enter the desired account number (up to 6-digits), then press ENTER.
LS10061-001SK-E Programming Telephone Number Enter up to 24 characters for phone number for this account. Figure 7-13 Edit Phone Number The following special characters are available: Table 7-8: Special Character for Dialing # Pound (or number) key on the telephone * Star key on the telephone , Comma (character for 2-second pause) 12. Use the number buttons on the annunciator or the up- and down-arrow keys to select special characters. Characters begin displaying after “9”.
Model 5820XL / 5820XL-EVS Installation Manual 5. LS10061-001SK-E Select the phone line to be edited (1 or 2) by pressing the or arrow, then press ENTER. Figure 7-14 Phone Lines Editing Screen 7.6.2.1 Dialing Prefix Enter up to 9 characters to be used for such things as PBX dial-out codes, a pause, and so on.
LS10061-001SK-E Dial Option Description TT/PL TouchTone alternating with pulse. If this option is selected, the dialer will first attempt to use TouchTone. It will switch to pulse if TouchTone is not successful on the first attempt. It will continue to alternate between TT and pulse for additional attempts. 7.6.2.4 9. Programming Rotary Format Press the or arrow to select the pulse ratio for rotary dialing option, then press ENTER. Options are: 7.6.2.5 U U.S. standard format.
Model 5820XL / 5820XL-EVS Installation Manual 7.6.3.1 LS10061-001SK-E Trouble Events You can map certain system trouble events to an output group. To access the screen for selecting output groups and cadence patterns for system trouble events. 5. Press 1 for Trouble Events. A screen similar to the one in Figure 7-15 will display. Select a group and a cadence pattern for each event as needed for your application. The U: field is for a user-specified trouble condition.
LS10061-001SK-E Programming required for your application. Figure 7-16 Special Cadence Patterns for Fire Drill and Auxiliary Alarm Events 7.6.4 Time Options Through this programming option you can set the water flow delay time, Alarm Verification, low AC report delay, AMPM/Military time and AC Frequency. To change time options, follow these steps. 1. Enter the installer code. The panel will automatically go to the main menu. 2. Select 7 for Program Menu. 3. Select 5 for System Options. 4.
Model 5820XL / 5820XL-EVS Installation Manual 7.6.4.3 LS10061-001SK-E Low AC Report Delay Note: You must select 1-3 hours in UL central station installations and UL remote signaling installations. You can adjust the number of hours before a low AC report will be sent to the central station. To program low AC report delay, follow these steps: Low AC Report Delay in Hours (00 - 30) Figure 7-18 Low AC Report Delay Programming Screen 8.
LS10061-001SK-E Programming Note: See Section 7.3.1.4 for more information about Synchronization protocol choices. 7.6.5.2 Auto Display Oldest Event When this feature is programmed Y (Yes) then the oldest un-acknowledge event will automatically display on the control panel and remote annunciators after there has been no activity on any system touchpad for two minutes. 7. Press the 8. Press the right arrow or ENTER to make your selection and move to the next programming option. 7.6.5.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E values for the DST Start and End options reflect the August 8, 2005 DST law that goes into effect in 2007: DST Start: The second Sunday in March DST End: The first Sunday in November To set the start and end for Daylight Saving Time: 1. Press the or arrow to select the week (1st, 2nd, etc.) Daylight Saving Time starts, then press ENTER to make your selection and move to the month setting. 2.
LS10061-001SK-E 7. Programming When done, press ENTER to move to line two of the custom banner. Repeat step 6 and 7. 7.6.8 SLC Family The 5820XL / 5820XL-EVS supports SD protocol SLC devices or Intelligent Device Protocol (SK) SLC devices. You must configure the 5820XL / 5820XL-EVS to accept the protocol of the devices you are installing. You cannot mix SLC devices of different protocols. 1. Enter the installer code. The panel will automatically go to the main menu. 2. Select 7 for Program Menu.
Model 5820XL / 5820XL-EVS Installation Manual 7.8 LS10061-001SK-E Computer Account An installer at the panel site can initiate communications between the panel and a computer running the 5660 SKSS (see also Section 8.5.17). In order for this communication to function properly both the computer (running the software) and the control panel must have matching computer account numbers and computer access codes.
LS10061-001SK-E Programming panel functions can not be edited. Table 7-9 lists the panel functions that can be selected for each user profile.
Model 5820XL / 5820XL-EVS Installation Manual 7.9.1 LS10061-001SK-E Profile Edit Menu From the Profile Edit Menu you can change the users name, access code, and the panel functions that the user will have access to with their code. Note: Profile 1 (Fire Fighter’s Key) the user name and access code can not be edited. Profile 2 (Installer) the user name and panel functions can not be edited. 7.9.1.1 Edit Name 6. Select each character of a word by pressing the next character. 7.
LS10061-001SK-E Programming 7.3.1.4 do not apply. For voice output groups, one of seventeen system wide voice commands will activate instead of the cadence pattern. Which command is determined by the event type selected for that zone. This menu option allows you to program, the message to be used, the tone used, repeats, and message delays, for each of the seventeen commands. Table 9-3 lists the seventeen different commands and the associated event type. See also Section 7.3.1 for more information. 1.
Model 5820XL / 5820XL-EVS Installation Manual 6. Press the 7.10.3.2 or LS10061-001SK-E arrow to toggle this selection between Yes or No, then press ENTER. Edit Command Priority 1. Select 7 for Program Menu. 2. Select 9 for Voice Options. 3. Select 3 for EVS System Options. 4. Then select 2 for Edit Cmd Priority. 5. Press 6. Press ENTER on the blinking command message to move. 7. Press the 8. Pressing ENTER will lock the message into its location. 9.
LS10061-001SK-E 7. 8. Programming To edit Auto Reset: • Press 1 for Auto Reset EC 0. • Press 2 for Auto Reset EC 1. • Press 3 for Auto Reset EC 2. • Press 4 for Auto Reset EC 3. • Press 5 for Auto Reset EC 4. • Press 6 for Auto Reset EC 5. • Press 7 for Auto Reset EC 6. • Press 8 for Auto Reset EC 7. • Press 9 for Auto Reset EC 8. Press the or to select Never/Timer/Event Disabled, then press ENTER. (If timer is selected, a range of 0 to 240 minutes is allowed.
LS10061-001SK-E Section 8 System Operation Operation of the control panel is simple. Menus guide you step-by-step through operations. This section of the manual is an overview of the operation menus. Please read this entire section carefully before operating the panel. Press ENTER to view Main Menu: Select the desired menu option. Enter your access code if prompted. Note: See Section 7.9 for information on how to modify user access code profiles. 8.
LS10061-001SK-E System Operation the internal (default) message. See Section 7.6.7 for information on customizing the banner. Figure 8-2 Banner Display Examples 8.3 Key Operation The key on the control panel board assembly is for accessing the Main Menu. The key is activated when it is turned once to the right (clockwise). If the key has been used to activate the menu, it must be turned counterclockwise to exit the menu. Figure 8-3 Using a Key to Access the Main Menu 8.
Model 5820XL / 5820XL-EVS Installation Manual 8.4.1 LS10061-001SK-E Main Menu Overview The chart below is a brief overview of the Main Menu. These options are described in greater detail throughout this section of the manual. Main Menu Options Description 1- System Tests Access to Fire Drill, Indicator Test, Walk Tests, Dialer Test, Clear History Buffer, and Manual Dialer Reset. 2- Point Functions Enable/disable points, Point Status, Set SLC Address, Device Locator, and I/O Point Control.
LS10061-001SK-E System Operation 8.5.2.1 Disable / Enable NACs by Template 1. Press 1 for Disable NACs by Template, press 2 to Enable NACs by Template. 2. Use the 8.5.3 or arrow to move through the list of templates. Press ENTER to select the current template. Disable / Enable NACs by Group 1. Select 1 for Disable/Enable Pt. 2. Select 3 to Disable NACs by group or 4 to Enable NACs by group. 3. Use the or arrow to move through the list of groups. Press ENTER to select the group highlighted.
Model 5820XL / 5820XL-EVS Installation Manual • LS10061-001SK-E All four lines of the LCD are not full. This test takes approximately 15 seconds to complete. You can press any key to end manually while the test is still in progress. When the test ends, you will be returned to the . 8.5.8 1. Conduct a Walk Test From the Main Menu, press 1 for System Tests.
LS10061-001SK-E 8.5.12 System Operation Check Detector Sensitivity Through Point Status The control panel constantly monitors smoke detectors to ensure that sensitivity levels are in compliance with NFPA 72. If sensitivity for a detector is not in compliance, the panel goes into trouble, generating a CAL TRBLE condition. A detector enters a CAL MAINT state to indicate that it is approaching an out of compliance condition (but is currently still in compliance).
Model 5820XL / 5820XL-EVS Installation Manual 8.5.13 LS10061-001SK-E View Status of a Point 1. From the Main Menu, select 2 for Point Status. 2. From the list that displays, press ENTER to select the module where this point is located. Next, enter the point to display. The screen that displays will show you if the point has a trouble and will provide sensitivity compliance information. (See Section 8.5.12 for complete information about detector sensitivity compliance.) 8.5.
LS10061-001SK-E System Operation If the phone number you will be calling is already displayed, press ENTER. Continue with step 4. If the phone number you will be calling is not already displayed, enter the number and press ENTER. A phone number can be up to 40 digits long and can contain the following special characters.
Model 5820XL / 5820XL-EVS Installation Manual 8.5.18 LS10061-001SK-E Working with a Printer If you are using the Model 5824 serial/parallel interface module, several printing options are available. See Section 4.7 for information about installing the 5824. 1. From the Main Menu, select 5 Printer Options. 2. From the next screen, select the 5824 module where the printer is connected. 3.
LS10061-001SK-E 8.6 System Operation Operation Mode Behavior Table 8-1 Operation Mode Normal Occurs When No alarm or trouble condition exists and menus are not in use. System Behavior SYSTEM POWER LED is on. The All Systems Normal display indicates that the system is in normal mode. 8-10 In This Mode You Can Enter the appropriate code to activate the User or Installer Menu, or rotate the key to activate the User Menu.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Table 8-1 Operation Mode Occurs When Alarm System Behavior In This Mode You Can Press the down arrow to view the alarm. A The dialer seizes control of the phone line screen similar to this one displays. and calls the central station. The on-board annunciator sounds a loud, steady beep (any . notification devices attached to the system will also sound). GENERAL ALARM LED flashes. The LCD displays a screen similar to this one.
LS10061-001SK-E System Operation Table 8-1 Operation Mode Occurs When The system detects a supervisory condition. System Behavior The dialer seizes control of the phone line and calls the central station. The on-board annunciator sounds a loud, pulsing beep in the sequence one second on, one second off. SUPERVISORY LED flashes. The LCD displays a screen similar to this one. In This Mode You Can Press down arrow to view the supervisory condition.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Table 8-1 Operation Mode Occurs When A system trouble condition occurs. System Behavior The dialer seizes control of the phone line and calls the central station. The on-board annunciator sounds a loud, pulsing beep in the sequence one second on, nine seconds off. SYSTEM TROUBLE LED flashes. The LCD displays a screen similar to this one. In This Mode You Can Press down arrow to view the trouble, A screen similar tot his one display.
LS10061-001SK-E System Operation Table 8-1 Operation Mode Occurs When A single detector trips in a 2-Count zone. (2- Count means two detectors must trip before an alarm is reported.) System Behavior Touchpad PZT beeps. The LCD displays a screen similar to this one. In This Mode You Can Press down arrow to view the prealarm. A screen similar to this one displays. Prealarm All system operations are available in this mode.
Model 5820XL / 5820XL-EVS Installation Manual 8.7 LS10061-001SK-E Releasing Operations The control panel supports two types of releasing, Double Interlock Zone, and Single Interlock Zone. The Double Interlock Zone operation requires an interlock switch input in the system, and the Single Interlock zone does not. An interlock switch is typically a dry-contact pressure switch.
LS10061-001SK-E 8.7.1 System Operation Single Interlock Zone Releasing A single interlock zone utilizes a minimum of two addressable detectors and a designated manual release switch. Important! Only addressable detectors can be used. No conventional detectors can be used. Each Single Interlock Zone input requires at least one manual release switch. Conditions Required for an Pre-Alarm Output Activation If any single addressable detector is activated, the “Pre-Alarm” output will activate.
Model 5820XL / 5820XL-EVS Installation Manual 8.7.2 LS10061-001SK-E Double Interlock Zone Releasing A Double Interlock Zone uses a minimum of two addressable detectors, a designated manual release switch, and an interlock switch input. An interlock switch is typically a dry-contact pressure switch and will be referred to as an interlock/pressure switch in this document. Important! Only addressable detectors can be used. No conventional detectors can be used.
LS10061-001SK-E 8.8 System Operation Smoke Alarm Verification Figure 8-6 illustrates how the Smoke Alarm Verification cycle operates. Figure 8-6 Smoke Verification Cycle During the Confirmation Period if there is no alarm indication then the system will return to normal operation.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Section 9 Emergency Voice System Operation 9.1 Overview The EVS series control panels and accessories provide features to meet the requirements for Mass Notification Systems as described in NFPA 72 and is compliant with the UL 2572 standard. These features are enabled through a programming option in the fire alarm control panel. EVS (Emergency Voice System) is integrated with the fire alarm and voice evacuation functions of the control panel.
LS10061-001SK-E Emergency Voice System Operation 9.2.1.2 EVS Control LED The EVS Control LED is used to indicate the status of EVS Control in the system. When the LED is on solid, the LOC has EVS Control within the system. When the LED is blinking, another LOC has gained EVS Control in the system. 9.2.1.3 ALL CALL Key Used to deliver your verbal message to all voice groups. 1. Key the microphone, press the All Call Key, wait for the Ready-to-Talk LED to light, and then deliver your verbal message. 9.2.
Model 5820XL / 5820XL-EVS Installation Manual ALL CALL KEY LS10061-001SK-E NON-ACTIVE CALL Key EVS Control Key READY EVS Control LED EVS CONTROL TO TALK Select LEDs Message Keys Message LEDs Select Keys Figure 9-1 EVS Front View 9.2.2 Gaining EVS Control When attempting to gain EVS Control, there are three things that govern whether or not EVS Control can be obtained: 1. LOC Priority. 2. LOC Lockout. 3. User profile access control. 9.2.2.
LS10061-001SK-E Emergency Voice System Operation The LOC lockout timer can be set between immediate and 12 hours in increments of 1 second or it can be set to never expire. The default setting is 30 seconds. The LOC lockout timer is restarted upon any key press at the LOC with EVS control. The LOC lockout timer is cleared when EVS Control is relinquished. 9.2.2.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E microphone. The green LEDs next to the Select Keys will activate or deactivate. 9.2.5 Message Mode In Message Mode, the user is able to press the EVS Message Keys to choose a message and press the Select Keys to activate or deactivate which output areas the message will be played. This will activate or deactivate the green and red LEDs next to the EVS Message Keys and the red LEDs next to the Select Keys. 9.2.
LS10061-001SK-E Emergency Voice System Operation relinquished after a time-out on this screen. When EVS Control is relinquished, the system stays in the Manual EVS State. EVS Control can then be gained by another LOC or again at the same LOC. 9.2.10 EVS Reset An EVS reset is accomplished by pressing the RESET button from an LOC. The user will be prompted to reset either the fire system or emergency system. After an EVS reset, the LOC will automatically exit the LOC EVS interface.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E System, then the system will play the highest event message through all EVS mapped outputs. For example: Emergency 1 Point Alarm is higher priority than Emergency 2 Point Alarm. Emergency 1 Point Alarm has message 1 mapped to through groups 1 and 2. Emergency 2 Point Alarm has message 2 playing through groups 2 and 3.
LS10061-001SK-E Emergency Voice System Operation 1. Enter the installer code. The panel will automatically go to the main menu. 2. Select 7 for Panel Program Menu. 3. Press 1 to enter Module menu. 4. Press 2 to add a module. 5. From the next screen, add either an *EVS-VCM or **EVS-RVM. Note: * Only 1 EVS-VCM may be installed per site. Note: ** Up to 5 EVS-RVMs may be installed per site. The screen will display “Adding module [#]...” for a few moments.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E During JumpStart, the EVS-VCM is automatically associated with the internal annunciator. The association for other LOCs in the system must be performed in programming. 9.7 Amplifier Programming 9.7.1 Adding an Amplifier To add a new amplifier to the system, follow these steps: 1. Enter the installer code. The panel will automatically go to the main menu. 2. Select 7 for Program Menu. 3. Press 1 to enter Module menu. 4.
LS10061-001SK-E 9.8 Emergency Voice System Operation Event Priority This section goes over how event activations are handled by the control panel with regards to priority. 9.8.1 System Control The 5820XL-EVS control panel integrates both a fire and emergency system into one. When events are active from both systems the control panel makes intelligent decisions to determine which system should be controlling outputs. This is called System Control.
Model 5820XL / 5820XL-EVS Installation Manual 9.8.4 LS10061-001SK-E View Active Alarms, Troubles and Supervisory Signals When looking at the LCD display, the screen will display FS for the “Fire System” and EVS for “Emergency Voice System” after the condition. The highest priority event will display first. (See Figure 9-5). Press the down arrow to view location and type of alarm or trouble. After sitting idle for two minutes, events will display on line 4 of display. (See Figure 9-6).
LS10061-001SK-E 9.9.3 Emergency Voice System Operation Fire Page A fire page can only occur when: 1. Only the fire alarm is active. 2. Both fire and EVS are active and the fire alarm is programmed to be of higher priority than the active EVS alarm. • 3. Only the fire alarm is active, the user has gained EVS Control and custom EVS event is a lower priority than the fire alarm. • 4.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E READY TO TALK LED 9.10 Recording Custom Messages The EVS-Series controls come with 15 recordable message slots. (See http://www.silentknight.com/products/ Pages/5820XL-EVS-Voice-Files.aspx for voice message downloads). Message 1-15 can be recorded from the microphone, Aux Input or by using the EVS Message Manager software. All messages can be a maximum of one minute.
LS10061-001SK-E Emergency Voice System Operation While in the Local Record mode, select keys 1-15 will be used to reference message slots 1-15. The associated green Select Key will indicate that a message is currently programmed in the corresponding slot. When there is no message recorded (or the message is erased), the associated green Select Key LED will be off. While recording a particular message, the red Select Key will turn on until recording is completed.
Model 5820XL / 5820XL-EVS Installation Manual 6. LS10061-001SK-E Select option 2 Local Recording. Note: The VCM will light the green Select Key LED for message slots that are occupied. If a message is already stored in the desired slot, then you must erase the message first. (see 9.10.3). 7. Select the amplifier and circuit for the audio to play through during programming. A user would generally pick the audio circuit that is in closest proximity to them. 8.
LS10061-001SK-E 9.10.2 Emergency Voice System Operation Recording Messages 1-15 Using the Microphone Messages can be recorded into the EVS system by using the on board microphone. Follow these steps to use the microphone to record your message: 1. Enter programming mode at main control panel. 2. Select option 9 Voice Options. 3. Select option 2 Local Recording. Note: The VCM will light the green Select Key LED for message slots that are occupied.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Pressing Select Key 5 will start a playback of the recorded message. Press EVS Message Key to enter message slot selection mode Press Select Key 5 to record to this message slot Figure 9-9 Recording with Microphone Example 9.10.3 Erasing User Message To erase the message stored in switch 1-15 memory location follow these steps: 1. Enter programming mode at main control panel. 2. Select option 9 Voice Options. 3.
LS10061-001SK-E 9.10.4 Emergency Voice System Operation Using EVS Message Manager Software The EVS Message Manager software is a software support utility that is used to download recorded messages (in .SKE1 format stored on your PC hard drive) to the various message locations of the EVS-Series controls. Messages can be uploaded from the EVS-Series control, stored, and used again in similar installations. The EVS Message Manger software can also be used to move messages to different message locations.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E 9.11 EVS Priority EVS command priority table will contain the following voice events: Table 9-2: EVS Priority Table Fire Alarm Fire Aux 1 Fire Aux 2 CO Alarm EVS LOC Activations EVS 1 PT Activation EVS 2 PT Activation EVS 3 PT Activation EVS 4 PT Activation EVS 5 PT Activation EVS 6 PT Activation EVS 7 PT Activation EVS 8 PT Activation Emerg Voice Aux 1 Emerg Voice Aux 2 Emerg Voice Aux 3 Emerg Voice Aux 4 Emerg Voice Aux 5 9.11.
LS10061-001SK-E Emergency Voice System Operation 9.12 Defining Output Group Type Each output group is defined as either a voice output group or a non-voice output group. Output points that are audio circuits (all circuits on the EVS-50W, EVS-125W, EVS-100W, EVS-INT50W and EVS-CE4) can only be assigned to voice output groups.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E 9.13 Voice Command Mapping Where an EVS event is playing can be configured automatically or manually. The automatic method is through voice system mapping and the manual method is using output group override. 9.13.1 Voice System Mapping Mapping EVS events to activate output groups is just like mapping events for the fire system. These are located under the voice tab of SKSS. Figure 9-12 Voice System Mapping in SKSS 9.13.
LS10061-001SK-E Emergency Voice System Operation Zone Mapping to Voice Output Groups When a voice output group is selected to be activated by a zone, the cadence pattern choice listed in Section 7.3.1.4 do not apply. For voice output groups, one of 18 plus all “Aux Voice In” system wide voice commands will activate instead of the cadence pattern. Which command is determined by the event type selected for that zone. The voice commands are programmable by the installer (see Section 7.
Model 5820XL / 5820XL-EVS Installation Manual 9.13.3 LS10061-001SK-E Edit Command Mapping Up to 8 groups or templates can be assigned to each voice system event. See Table 9-4.
LS10061-001SK-E Emergency Voice System Operation 9.14 EVS Timer Options 9.14.0.2 Timers include • • EVS Control Lockout • Immediate • Never • Timer. (If timer is selected, a range of 1-720 minutes and 0-59 seconds are allowed. Default is 30 seconds). EVS Event Auto Reset Time (including Custom Emergency Communication 0 and Emergency Communication 1-8). • Event Disabled (the event can not be generated) • Never • Timer (If timer is selected, a range of 0-240 minutes is allowed.
Section 10 Reporting This section lists receivers that are compatible with this control panel and the reporting codes sent by the control panel for SIA and Contact ID formats. 10.1 Receivers Compatible with the Control Panel The below table shows receivers compatible with the control panel. Manufacturer Model Format Model 9800 Silent Knight SIA and Contact ID Model 9000 (SIA formats) SIA Ademco Model 685 (Contact ID ) Contact ID Sur-Gard SG-MLR2-DG (V. 1.
Reporting SIA Reporting Format Event Description Event Family Module ID # (if any) SIA Event Code Parameter (if any) Contact ID Reporting Format Qualifier Event Code Group # Contact # Local Programming begin Trouble LB 0 1 627 00 000 Local Programming ended normally Trouble LS 0 1 628 00 000 Local Programming aborted or ended Trouble with errors LU 0 1 628 00 000 Panel Date has been changed Trouble JD 0 1 625 00 000 Panel Time has been changed Trouble JT 0 1 6
Model 5820XL / 5820XL-EVS Installation Manual SIA Reporting Format Event Family Event Description Module ID # (if any) SIA Event Code Parameter (if any) Contact ID Reporting Format Qualifier Event Code Group # Contact # Voice VBUS Trouble Restore1 Trouble ER Exp. ID 3 332 00 Exp. ID Voice Message Trouble1 Trouble pi message ET ID Exp. ID 1 332 Message Exp. ID ID Voice Message Trouble Restore1 Trouble pi message ER ID Exp. ID 3 332 Message Exp.
Reporting SIA Reporting Format Event Family Event Description Walk test end Test Walk test begin Test Zone Events Module ID # (if any) SIA Event Code Parameter (if any) Contact ID Reporting Format Qualifier Event Code Group # Contact # TE 0 3 607 00 000 TS 0 1 607 00 000 Note: Zone events are reported only when “Report by Zone” is selected.
Model 5820XL / 5820XL-EVS Installation Manual SIA Reporting Format Event Description Event Family Module ID # (if any) SIA Event Code 00 Contact # Trouble ET 0000 1 333 00 000 Status Point Types Trouble Trouble UT 0 1 379 00 000 Status Point Types Trouble Restore Trouble UJ 0 3 379 00 000 Supervisory/Tamper switch trouble restore Trouble FJ Zone # 3 373 00 Zone # Supervisory condition restore Trouble FR Zone # 3 200 00 Zone # Supervisory condition Trouble FS
Reporting SIA Reporting Format Event Family Event Description Point Events Module ID # (if any) SIA Event Code Parameter (if any) Contact ID Reporting Format Qualifier Event Code Group # Contact # Note: Point events are reported only when “Report by Point” is selected. When SK protocol devices are used sensors 1–99 are reported as Pnt #s 1–99, and modules 1–99 are reported as Pnt #s 201-–299. Auxiliary switch input disabled Disable pi Exp. ID UB Point # 1 571 Exp.
Model 5820XL / 5820XL-EVS Installation Manual SIA Reporting Format Contact ID Reporting Format Event Family Module ID # (if any) External Reset/Silence/Fire Drill switch trouble Trouble pi Exp. ID UT Point # 1 373 Exp. ID Point # External Reset/Silence/Fire Drill switch trouble restore Trouble pi Exp. ID UJ Point # 3 373 Exp. ID Point # External Reset/Silence/Fire Drill Switch Disabled Disable pi Exp. ID UB Point # 1 571 Exp.
Reporting SIA Reporting Format Contact ID Reporting Format Event Family Module ID # (if any) Supervisory/Tamper switch or supervisory detector trouble restore Trouble pi Exp. ID FJ Point # 3 373 Exp. ID Point # Supervisory condition restore Trouble pi Exp. ID FR Point # 3 200 Exp. ID Point # Supervisory Condition Trouble pi Exp. ID FS Point # 1 200 Exp. ID Point # Supervisory/Tamper switch or supervisory detector trouble Trouble pi Exp. ID FT Point # 1 373 Exp.
Model 5820XL / 5820XL-EVS Installation Manual SIA Reporting Format Contact ID Reporting Format Event Family Module ID # (if any) Zone-based AUX1 switch alarm restore Restore pi Exp. ID UH Point # 3 140 Exp. ID Point # Zone-based AUX2 switch alarm restore Restore pi Exp. ID UH Point # 3 140 Exp. ID Point # Zone-based AUX1 switch trouble restore Trouble pi Exp. ID UJ Point # 3 373 Exp. ID Point # Zone-based AUX2 switch trouble restore Trouble pi Exp.
LS10061-001SK-E Section 11 Testing and Troubleshooting 11.1 Troubleshooting This section of the manual offers suggestions for troubleshooting hardware problems. Please read this section if you encounter a problem when installing the control panel. If these suggestions do not solve your problem or if you encounter a problem that is not listed here, contact Silent Knight Technical Support at 800-446-6444 for assistance. 11.
LS10061-001SK-E Problem SLC devices are not being recognized (trouble message “Missing” displays on the annunciator). Testing and Troubleshooting Possible Cause / Suggested Actions Check that SLC loop impedance is within the required range. To measure impedance, use the following procedure: 1. Disconnect both wires from the terminal block at the panel (SLC devices can remain connected). 2. Measure the impedance from positive to negative and from negative to positive.
Model 5820XL/5820XL-EVS Installation Manual LS10061-001SK-E 11.3 Periodic Testing and Maintenance To ensure proper and reliable operation, it is recommended that system inspection and testing be scheduled monthly or as required by national and/or local fire codes. Testing should be done by a qualified service representative if a malfunction is encountered. Before Testing: 1. Notify the fire department and/or central alarm receiving station. 2.
LS10061-001SK-E Testing and Troubleshooting A message similar to the one shown in Figure 11-1 will display. Figure 11-1 Shut Down Warning 3. Press the or arrow to toggle NO to YES then press ENTER. If NO is chosen you will exit back to the Point Function menu. If Yes is chosen the system will cease normal operation leaving the premise unprotected. 4. Select the SLC loop. 5. Enter the SLC address of the device you wish to locate. The LED on the selected device will start flashing. 6.
Model 5820XL/5820XL-EVS Installation Manual 11.5.3 LS10061-001SK-E I/O Point Control This feature allows you to toggle any output on or off and trip any input device. This can be useful to test a point’s output mapping. Follow these steps to control a I/O point: 1. Select 2 (Point Functions) from the Main Menu. 2. Select 6 (I/O Point Control). 3. Select the module the point is on. 4. Use the 5. Press ENTER to generate an alarm for an input point or activate an output point. 6.
LS10061-001SK-E 11.5.4 Testing and Troubleshooting Earth Fault Resistance Table 11-1 lists the earth fault resistance detection for each applicable terminal on the FACP.
LS10061-001SK-E Section 12 Installation Records This section of the manual is for you to use if you wish to track of how points, zones, and groups have been programmed. 12.1 Detector and Module Point Record If installing SK SLC devices, use Table 12-1 to record detector points (up to 99 per SLC loop) installed on the on-board SLC loop and make a copy of Table 12-2 to record installed modules (up to 99 per SLC loop).
LS10061-001SK-E Installation Records Table 12-1: Installation Record of Onboard Devices Module Addr Zone / Group Description Module Addr On-board 53 On-board 93 On-board 54 On-board 94 On-board 55 On-board 95 On-board 56 On-board 96 On-board 57 On-board 97 On-board 58 On-board 98 On-board 59 On-board 99 On-board 60 On-board 100 On-board 61 On-board 101 On-board 62 On-board 102 On-board 63 On-board 103 On-board 64 On-board 104 On-board 65 On-board 10
Model 5820XL/ 5820XL-EVS Installation Manual LS10061-001SK-E pages are needed. Table 12-2: Installation Record of Devices Installed on 5815XLs Module Addr Zone / Group Description Module Addr Zone/ Group Description Additional SLC Devices Use the table below to record devices installed on additional 5815XLs.
LS10061-001SK-E Installation Records pages are needed.
Model 5820XL/ 5820XL-EVS Installation Manual Module Addr Zone / Group LS10061-001SK-E Description Module 12-5 Addr Zone/ Group Description
LS10061-001SK-E Installation Records 12.2 Conventional Output Point Record This chart can be used to keep track of how conventional output points (circuits) have been configured.
LS10061-001SK-E Appendix A Compatible Device A.1 Notification Appliances For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on each loop. All supervised notification appliances used with the control panel must be polarized. Note: Not all devices can use the Sync feature, be sure to check Table A-1 to ensure the device you have chosen will work with this feature. This control is UL listed for panel wide Synchronization.
LS10061-001SK-E Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual 446 Vibrating Bell 476 Vibrating Bell 477 Single Stroke Bell 2700 -M.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Table A-1: Compatible Notification Appliances Manufacturer Faraday (cont.
LS10061-001SK-E Table A-1: Compatible Notification Appliances Manufacturer Faraday (cont.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Table A-1: Compatible Notification Appliances Manufacturer FCI (cont.
LS10061-001SK-E Table A-1: Compatible Notification Appliances Manufacturer Model WGEC24-75W Gentex (cont.
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Table A-1: Compatible Notification Appliances Manufacturer System Sensor (cont.
LS10061-001SK-E Table A-1: Compatible Notification Appliances Manufacturer Model Audio Type AH-12 x Horn AH-24 x Horn AH-12WP x Horn Weatherproof AH-24WP x AMT-241575W x Horn Weatherproof AMT-24MCW x Multi-Tone Horn Strobe x Mutli-Tone Horn Strobe x Multi-Tone Horn Strobe AMT-241575W-NYC x AMT-12/24 x Multi-tone Horn AMT-12/24 NYC x Multi-tone Horn AS-121575W Wheelock Visual x Horn/Strobe NH-12/24 x x Horn AS-241575W x x Horn/Strobe AS-24MCC x x Horn/Strobe
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type MTWPA-2475W x x Multitone Horn Strobe MTWPB-2475W x x Multitone Horn Strobe MTWPG-2475W x x Multitone Horn Strobe MTWPR-2475W x x Multitone Horn Strobe MTWPA-24MCCH x x Multitone Horn Strobe ZNH x NS-121575W x x Horn/Strobe NS-241575W x x Horn/Strobe NS-24MCW x x Horn/Strobe NS-24MCC x x Horn/Strobe NS-24MCCH x x Horn
LS10061-001SK-E Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type RSSWPG-24MCCH x Strobe Weatherproof RSSWPR-24MCCH x Strobe Weatherproof RSSWP-2475W x Strobe Weatherproof RSSWP-2475C x Strobe Weatherproof RSSWP-24MCWH x Strobe Weatherproof ZRS-MCWH x Strobe ZRS-24MCC x Strobe ZRS-24MCCH x MB-G6-24 Strobe Motor Bell MB-G10-24 Motor Bell MB-G6-12 Motor Bell Wheelock MB-G10-12 Motor Bell (cont.
Model 5820XL / 5820XL-EVS Installation Manual A.2 LS10061-001SK-E Two-Wire Smoke Detectors Table A-2 lists two-wire smoke detectors that are compatible with the fire control panel. The table is organized by manufacturer. The columns show the number of detectors per loop that can be used. 5820XL5820XL/ EVS/EVS 24H Identifier Operating Voltage Range 18.5–27.4 VDC Note: The maximum number of smoke detectors per zone is determined by both the current draw and the impedance of the smoke detector.
LS10061-001SK-E Table A-2: Compatible Two-Wire Smoke Detectors Manufacturer ESL Model Name or Number (Base model name or number in parenthesis) Compatibility ID # per Loop Head Base 429C (S10A) N/A S10A 30 / loop 429CRT (S11A) N/A S11A 30 / loop 429CST (S11A) N/A S11A 30 / loop 429CT (S10A) N/A S10A 30 / loop 609U01-11 S10 S00 40 / loop 609U02-11 S10 S00/S03 40 / loop 611U (601U or 602U) S10 S00/S03 40 / loop 611UD (601U or 602U) S10 S00/S03 40 / loop 611UT (601U or 602U
Model 5820XL / 5820XL-EVS Installation Manual A.
LS10061-001SK-E 14
LS10061-001SK-E Appendix B Special Characters Lists This section contains tables of programmable characters that may be used for device, module, and zone names or phone numbers. B.1 Characters used for Naming Table B-1 list the available character and their associated numeric designator. When programming these numbers can be entered as a short cut to using the up or down arrow keys, to select characters when naming a point or zone.
Silent Knight Fire Product Warranty and Return Policy General Terms and Conditions • • All new fire products manufactured by Silent Knight have a limited warranty period of 36 months from the date of manufacture against defects in materials and workmanship. See limited warranty statement for details. This limited warranty does not apply to those products that are damaged due to misuse, abuse, negligence, exposure to adverse environmental conditions, or have been modified in any manner whatsoever.
Manufacturer Warranties and Limitation of Liability Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that the Products manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free, under normal use and service, from defects in material and workmanship for a period of thirty six months (36) months from the date of manufacture (effective Jan. 1, 2009).
IntelliKnight 5820XL Basic Operating Instructions These instructions must be framed and displayed next to the 5820XL panel in accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems. Operation Silence Alarms and Troubles Reset alarms Conduct a fire drill Keystrokes Press silence then rotate the key or enter a code Press reset then rotate the key or enter a code. 1. Rotate the key or Enter the installer code. The panel will automatically go to the main menu. Press 1. 2.
5820XL-EVS Basic Operating Instructions These instructions must be framed and displayed next to the 5820XL-EVS panel in accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems. FS= Fire System Operation EVS = Emergency Voice System Task to Perform Silence Alarms and Troubles (FS and Press SILENCE then rotate the key or enter a code if prompted. Silence LED will light. EVS) Cut Along the Dotted Line Reset Alarms (Fire Press RESET then rotate the key or enter a code. Only) 1. Press RESET.
Integrated Voice Operation ALL CALL Key Ready to Talk LED NON-ACTIVE CALL Key Select LED’s EVS Control Key EVS Status LED Message (1-8) Activate Keys Message LEDS Select Keys Figure 1: EVS-VCM Front View Cut Along the Dotted Line Table 1: LED Conditions LED Color States On The corresponding area is active for the currently playing EVS message. Off The corresponding area is not active. On The corresponding area is active for the microphone.
LS10064-001SK-E
Table 2: EVS Control Request Operation Task Press the EVS Control Key and enter a code if prompted. If EVS Control is available, the EVS Control LED will illuminate. If another LOC has EVS Control, the display will be similar to the one shown. Press 1 to request control. The LOC with EVS Control will then be able to allow or deny the request. Gain EVS Control as EVS Super User at an LOC (only one EVS Super User is allowed EVS Control in the system at a time).
Silent Knight 12 Clintonville Road Northford, CT 06472-1610 203-484-7161 Fax: 203-484-7118 www.silentknight.