User Manual

P/N 150972
5880 LED I/O Module
Installation Instructions
The 5880 provides a way to customize your
remote annunciator when used with a
compatible addressable fire alarm control panel
(FACP). For more detailed information, refer to
the FACP installation manual.
Note: Installation and wiring of this device must be done in
accordance with NFPA 72 and local ordinances.
Specifications
Mounting the 5880
Enclosure
The 5880 comes in a plastic enclosure which
must be mounted inside the annunciator or
accessory cabinet.
To mount the 5880 plastic enclosure into the
appropriate cabinet:
1. Remove the 5880 cover. Use a small screw
driver if necessary.
2. Remove the 5880 circuit board from the base
by pushing outward on the base snap
retaining tabs and lifting the circuit board
out.
Figure 1: 5880 Circuit Board And Plastic Base
3. Mount the plastic base into the appropriate
accessory cabinet.
4. Replace the circuit board in the plastic base.
Note: It may be necessary to connect the wiring to the circuit
board before the board is replaced into the base.
Wiring the 5880 to the FACP
Terminate the wiring as shown in Figure 2 and
Table 2.
Figure 2: 5880 Connection to the FACP
Table 1: 5880 Specifications
Max. SBUS Voltage 24 VDC
Dry Contacts
(Loop Specs)
Max. Loop Resis-
tance
100 Ω
Max. Loop Voltage 24 VDC
Max. Loop Current 2 mA
Max. Current Alarm 200 mA
Standby 35 mA
Each LED 10 mA
Open Collector PZT Max. Sink Current 100 mA
Operating Temperature 0° to 49° C
(32° to 120° F)
Max Wiring Distance from FACP 6,000 ft
(1,829 m)
Indoor Use Only
Snap
Base
Circuit
Board
Retaining Tabs
FACP
Supervised
Power Limited
5880