Owner manual

(+) SLC
(+) SLC
NO 1
NO 2
NC 2
COMM 2
COMM 1
NC 1
(–) SLC
(–) SLC
(–) POWER
(+) POWER
U.L. LISTED COMPATIBLE
CONTROL PANEL
OPTIONAL SOUNDER INTERCONNECT*
NOT
USED
SLC +
EXT –
EXT +
RA
SLC –
NOT
USED
SLC +
EXT –
EXT +
RA
SLC –
(+) SLC
(–) SLC
SUP (–)
SUP (+)
* GROUPING OF UP TO 6 MODEL B200SR SOUNDER BASES
INTELLIGENT
MONITOR MODULE
INTELLIGENT
RELAY MODULE†
FIRST
SOUNDER
BASE
LAST
SOUNDER
BASE
†THIS IS A STANDARD RELAY
MODULE CONFIGURED TO
REVERSE THE POWER
UL LISTED
EOL
RESISTOR
47k
UL LISTED 24V
POWER SUPPLY
END OF LINE RELAY
(EOLR-1 OR EQUIV
ALENT)
FIGURE 4: WIRING DIAGRAM
FIGURE 5: WIRING DIAGRAM
SS-450-001 3 I56-3392-003R
(+) SLC
(–) SLC
(–) POWER
(+) POWER
U.L. LISTED COMPATIBLE
CONTROL PANEL
OPTIONAL SOUNDER INTERCONNECT*
CLASS A OPTIONAL WIRING
CLASS A OPTIONAL WIRING
NOT
USED
SLC +
EXT –
EXT +
RA
SLC –
NOT
USED
SLC +
EXT –
EXT +
RA
SLC –
(+) SLC
(–) SLC
SUP (–)
SUP (+)
* GROUPING OF UP TO 6 MODEL B200SR SOUNDER BASES
INTELLIGENT
MONITOR MODULE
FIRST
SOUNDER
BASE
SECOND
SOUNDER
BASE
LAST
SOUNDER
BASE
UL LISTED
EOL
RESISTOR
47k
NOT
USED
SLC +
EXT –
EXT +
RA
SLC –
UL LISTED 24V
POWER SUPPLY
END OF LINE RELAY
(EOLR-1 OR EQUIVALENT)
C0970-09
C0970-10
DETECTOR ACTIVATES SOUNDER BASE(S) - (COMPLIES WITH UL268)
UL has approved grouping for up to six B200SR sounder bases. When wired as a group, any detector in the group that has been activated by the panel will cause
other B200SR units in the group to sound. This type of “local” grouping is accomplished by wiring the grouped devices together using terminal 6, Sounder Base
Interconnect, as shown in the diagram. This interconnect can also be used to attach B200SR devices to System Sensor B501-Series sounder bases. Some Fire
Alarm Control Panels (FACP) support the grouping of sounder bases via software in lieu of the Sounder Base Interconnect.
NOTE: A local grouping of horns via the sounder base interconnect is not supervised, therefore the groups can only be used as a supplementary evacuation
system. It is not acceptable to group horns via the sounder base interconnect for primary alarm signaling. Sounder bases which are grouped via software are not
subject to this limitation and may be used as part of the primary alarm signaling.
DETECTOR ACTIVATES SOUNDER BASE(S);
INTELLIGENT RELAY MODULE ACTIVATES ALL SOUNDER BASES - (COMPLIES WITH UL 268 AND UL 464) ADDITIONAL AUDIBLE VISIBLE
DEVICES ARE SYNCHRONIZED TO THE SOUNDER BASE OUTPUT
UL has approved grouping for up to six B200SR sounder bases. When wired as a group, any detector in the group that has been activated by the panel will
cause other B200SR units in the group to sound. This type of “local” grouping is accomplished by wiring the grouped devices together using terminal 6, Sounder
Base Interconnect, as shown in the diagram. Some Fire Alarm Control Panels support the grouping of sounder bases via software in lieu of the Sounder Base
Interconnect.
NOTE: A local grouping of horns via the sounder base interconnect is not supervised, therefore the groups can only be used as a supplementary evacuation
system. It is not acceptable to group horns via the sounder base interconnect for primary alarm signaling. Sounder bases which are grouped via software
are not subject to this limitation and may be used as part of the primary alarm signaling.