Owner's manual
P/N 151305
SILENT
KNIGHT
®
by Honeywell
SKE-V70 Module Installation
Instructions
The SKE-V70 converts the speaker circuit 
voltage from 25 Vrms to 70.7 Vrms. The 
following describe how to install and wire the 
SKE-V70.
Mounting
Follow these steps to install the SKE-V70 
module into the main control panel cabinet:
1. Unlock and open the cabinet door.
2. Remove the two cover plate retaining 
screws, then open the control panel cover 
plate. See Figure 1.
Figure 1: View of Cabinet With Cover Plate in Place
Note: The control panel cover plate can be remove by removing 
the Hinge screw.
3. Run all wire needed to install the system at 
this time.
4. Mount the module into the cabinet as shown 
in Figure 2.
Figure 2: Main Control Board Mounting Location
5. Connect wiring as described in Section .
Wiring Connections
Each SKE-V70 supplies one NAC (Notification 
Appliance Circuit) for speaker connection. The 
speaker circuit can be supervised and wired 
Class B (Style Y) or Class A (Style Z). The 
speaker circuit is capable of 50 watts of power 
70.7 Vrms (using the SKE-V70 Module).
Note: When the SKE-V70 Module is installed, all speaker 
wiring must be separated by a minimum of 1/4” from the 
low voltage wiring, and must exit the cabinet through its 
own opening.
Control Panel
Cover Plate
Control Panel
Cover Plate
Zone Splitter
Access Plate
Retaining Screws
Hinge Screw
SKE-V70 
Cabinet 
Mounting 
Screws