Connecting the SKE-V70 to the 
Main Control Panel
Connect the SKE-V70 to the main control panel 
using the supplied wire harness. See Figure 3.
Note: Speaker outputs of the SKE-450 must not be used with the 
SKE-V70 because supervision will not be provided at the 
SKE-450.
Figure 3: Wire Harness Connection From the Main 
Control to the SKE-V70
Connecting the SKE-V70 to the 
SKE-ZN4 or -ZN6
If the optional SKE-ZN4 or -ZN6 zone splitter is 
used in the system connect the wire harnesses as 
described below.
Note: Speaker outputs of the SKE-450 and SKE-V70 must not 
be used when using either the SKE-ZN4 or SKE-ZN6 in 
combination with the SKE-V70 because supervision will 
not be provided at the SKE-450 and the SKE-V70.
1. Connect one harness from the main control 
to the SKE-V70 connector marked “FROM 
CONTROL”. See Figure 3.
2. Connect the other harness from the SKE-
V70 connector marked “TO SPLITTER” to 
the connector on the SKE-ZN4 or -ZN6 as 
shown in Figure 3.
Class B (Style Y)
Figure 4 illustrates how to wire speakers to the 
SKE-V70 using Class B (Style Y) supervision.
Figure 4: Class B (Style Y) Speaker Configuration
Class A (Style Z)
Figure 5 illustrates how to wire speakers to the 
SKE-V70 using Class A (Style Z) wiring. 
Figure 5: Class A (Style Z) Speaker Configuration
Electrical Specifications
Ground Fault Impedance To Any Terminal: 0 Ω
Standby Input Power: 27.4 VDC @ 10 mA
Alarm Input Power: 27.4 VDC @ 70 mA
Supervised
Power Limited
15 k
Ω EOL
UL Listed
Model 7630
Supervised
Power Limited