Unit installation
WAVENET RADIO NETWORK 3065 
Page 18 
7.5 Central nodes 
WaveNet central nodes can be used 
•  If there is a computer network (LAN) or Internet/Intranet installed at the 
customer’s premises. Any transmission media may be selected. The central 
nodes  WN.CN.S(X)  or WN.CN.U(X) are connected to the PC. Communication 
node software (CommNode) is installed on this PC. This allows the central node 
to be addressed from any location (GUI = G
raphic User Interface) in the network. 
A central node can of course also be connected ‘locally’ to a PC. 
7.6  LockNode with RS485 interface 
WaveNet LockNodes with integrated RS485 interface allow you to create a ‘wired’ 
WaveNet. For the cable type, select CAT 5 or higher. As a connection is provided for 
an external power supply (max. 24 V DC), the LockNodes are not
 battery-operated 
(see 7.9). Up to 250 LockNodes can be administered in each segment. To expand a 
segment you always need a WN.RN.CC. The maximum cable length per segment is 
900 m. If the cable length is exceeded, you will need a WN.RP.CC. This high-speed 
repeater serves to forward signals in both directions (up/down link). The repeater 
does not
 expand the segment. 