Unit installation
LON – Network 3065 
Page 18 
  Routers need a 230 V AC power supply from the customer (outlet). 
  Routers, as they come from the factory, do not have any over voltage 
protection. For this reason, this protection should be already provided for by 
the 
customer. 
  If elevators are to be integrated into the networking, they are not permitted to 
be installed in the backbone. Instead, they must be separated from the 
backbone by a router. 
6.2 Assembly Instructions 
You can attach routers to a DIN rail. Please refer to the following figure for the 
connection assignments: 
  1+2  Input A of network 
  3+4  Additional input A (internal bridges from 1-3 and from 2-4) 
 5 Not used 
  6+7  Supply voltage: power supply connection 
  8+9  Additional supply voltage (internal bridges from 6-8 and from 7-9) 
 10-14 Not used 
  15+16  Output B of network 
  17+18  Additional output B (internal bridges from 15-17 and from 16-18) 
    This output can be used for connecting the LPI-10, for example. 
  Connect the inputs of all routers in parallel. It is very important that you do not 
confuse input A and output B with one another. 