Unit installation
LON – Network 3065 
Page 30 
LPI-10 (Version: Compact)     
 Input quantities    
  Nominal input voltage 
U
E
AC 120 / 230V 
  Input voltage range  AC 85 to 264V   
 Nominal frequency 
range 
50/60Hz, 47 to 63Hz 
  Power failure buffering 
> 50 ms at U
E
=195V 
  Nominal input current 
I
E
0.8 / 0.5A 
 Making current 
impulse 
≤30mA 
Efficiency η  ≥ 75% in operation at nominal 
value at 230 V AC 
 Recommended  
circuit breaker 
(IEC898) in the power 
supply lead 
from 6A Char. D 
from 10A Char. C 
from 16A Char. B 
 Output quantities    
  Nominal output voltage
U
A
DC 41.5 V ±2% 
  Residual ripple  < 100mV
ss
 at 10kHz < f < 200KHz 
 Spikes  
(switching peaks) 
< 200mV
ss
 at 200KHz < f < 1MHz 
 Nominal output 
current I
A
1A at U
E
 85 to 195V 
1.3A (1.5A max. permitted continuous 
current from U
E
 195V 
  Overload protection 
typically at 
1.6A; continuous short-circuit-proof with 
pulsating restart attempt 
 Overvoltage protection 
typically at 
54 V 
  Start and restart time  5s < t < 10s 
 Environmental Conditions 
 During  
transport/storage 
-40° C to +70° C (-40° F to +158° F) 
  During operation  0° C to +40° C (32° F to +104° F) 
  Rel. air humidity  5 to 95%, w/o moisture condensation 
 Security  
  Degree of protection to 
EN 60529 
IP20 