Operator`s manual
4100ES-S1 Fire Indicator Panel Operator’s Guide
Fire detectors in the building are grouped into zones (searchable areas).
Zones can be Isolated by pressing the zone’s isolate pushbutton on the panel – this prevents an
alarm from activating the panel outputs.
When a non-isolated detector detects an alarm, the fire panel rings the bell, calls the fire brigade,
activates the Warning or Evacuation System (EWS) and any other programmed functions.
The fire panel display consists of two sections – the operator interface (upper section) and the Zone
Isolate pushbutton switches & indicators (lower section).
The operator interface indicates common Alarm, Fault & Isolation Status on LEDs, and point
(detector) status on the LCD.
When an Alarm, Fault or Isolation occurs, the buzzer will operate until the corresponding
acknowledge (Ack) key is pressed.
The panel is reset by pressing <SYSTEM RESET>. If the alarm won’t reset the point may still be
activated. Press <FIRE ALARM ACK> when the point alarm is displayed, then press <DISABLE>,
<ENTER>. Press <FAULT ACK> (to acknowledge the fault caused by disabling a point), then press
<SYSTEM RESET> again. The disabled detector must be re-enabled when the condition is cleared.
OUTPUT ISOLATES DISABLE FIRE ALARM ACK ISOLATE ACK FAULT ACK SYSTEM RESET ENTER
Silence the Bell: Press the <EXT BELL ISOLATE>
key.
Isolate signals to Evacuation System: Press the
<WARN SYS ISOLATE> key. This will turn off warning
sounders powered by the Fire Panel.
Isolate a Zone: Press the appropriate Zone Isolate
pushbutton and the Zone Isolated LED will turn on.
Acknowledge an Isolation: Press the <ISOLATE
ACK> key.
Acknowledge an Alarm: Press the <FIRE ALARM
ACK> key.
Acknowledge a Fault: Press the <FAULT ACK> key.
Zone Isolate
Pushbuttons
Operator Interface