Operator`s manual
9-8
Press the <MORE INFO> key to obtain the next display:
Device Address: 3-1
IDNet Device: M1-1
Press the <NEXT> key to obtain the next display:
1-Force on card LED Type: IDNet
IDNet CARD
Pressing key <1> will turn on the LED indicator on the IDNet Card in the FIP control rack
and pressing it again will turn the LED off. Press the <NEXT> key to move onto the next
display.
1-Force on device LED Type: PHOTO
Variable Sensitivity PHOTO
Pressing the <1> key will turn on the LED indicator on the selected smoke detector and
pressing it again will turn it off. Press the <NEXT> key to move onto the next display.
Level 3 - Room 74
Smoke Detector ON-LINE
Press the <NEXT> key to move onto the next display to verify correct device type.
Level 3 - Room 74
Smoke Detector Correct Device
Press the <NEXT> key to display the current selected sensitivity.
Level 3 - Room 74
Present Sensitivity Selected - 3.7% Smoke
Note: Sensitivity displayed is in % obscuration per foot.
Table 9-1. Smoke Obscuration conversion chart.
%Obs/Ft
%Obs/m
%Obs/Ft
%Obs/m
0.2%
0.6%
2.0%
6.5%
0.5%
1.6%
2.5%
8.2%
1.0%
3.3%
3.0%
9.8%
1.5%
5.0%
3.7%
12.1%
Continued on next page
Displaying IDNet & Mapnet Device Status, Continued
TrueAlarm Sensor
Display Values,
(continued)