Operator`s manual
9-9
To view the average value of samples received from the sensor press the <NEXT> key again.
Level 3 – Room 74
Average Value = 75 / Alarm level = 135
This is the present average of the last 2048 samples received from the sensor. The Alarm
Level is the binary value that is used to determine alarm conditions. This value will change
over time as the panel compensates for environmental conditions. The alarm value will be
different for each of the (7) sensitivity levels.
To view the last binary value that was received from the sensor press the <NEXT> key again.
Level 3 – Room 74
Value = 75 / 6% of Alarm / 0.1% Smoke
This value is displayed as a % of alarm and a % of smoke obscuration per foot.
Press the <NEXT> key again to view the highest binary value that was received and stored
from the sensor since power-up.
1- Clear PEAK Value
PEAK = 106 / 51% of Alarm / 1.0% Smoke
The peak is displayed as a % of alarm and a % of smoke obscuration per foot. Through the
use of a system pseudo point all new peak values per sensor can be stored in the history fault
log and printed on the optional 4100ES-S1 system printer. Printing of peak values is done at
the time the peak value is received at the FIP. This peak value is helpful in determining if a
sensor should be made more or less sensitivity.
Displaying IDNet & Mapnet Device Status, Continued
TrueAlarm Sensor
Display Values,
(continued)