Specifications
6-2
Devices can be added individually to the Install Mode list.
NOTE: this requires being logged in at Level 3. Refer to the Operator Manual, if
necessary, to do this.
1. Press the <Fault Ack> key and step through the list with the Next/Previous
arrows to find the device.
2. Press the <More Info> key.
3. Step through the list of options with the Next/Previous arrows to find the Add to
Install Mode? option.
4. Press <Enter> to select this. The action happens immediately.
If this is the first item being added to the Install Mode list, the Fault light will start
flashing. Pressing the <Fault Ack> key will show the Fault List, now with a single fault
point INSTALL MODE ACTIVE entry.
Where there are many missing devices, or devices not connected to field wiring, all
producing faults, there are simple ways to quickly add these to the Install Mode list in
bulk.
NOTE: this requires being logged in at Level 3. Refer to the Operator Manual, if
necessary, to do this.
1. Press the <Menu> key.
2. Use the Next/Previous arrows to step through the menu to the Diagnostic
Functions? option. Press <Enter> to select this.
3. Use the Next/Previous arrows to step through the menu to the View/Modify
Install Mode List? option. Press <Enter> to select this.
4. Step through to either the Move NO ANSWER devices to install mode list
option or the Move ALL OPEN CIRCUITS to install mode option.
5. Press <Enter> to select.
The panel will take a few seconds to search for all the selected devices and add them to
the Install Mode list. The single remaining fault is the Install Mode fault.
Adding Devices to Install Mode
Adding a Single
Device to Install
Mode
Adding Multiple
Devices to Install
Mode