Installation manual
13 of 72
SIMPLEX Fault Assistance Guide RevA
29 April 2009
1.1.2.5 Channel Failure Abnormal
Description:
The Loop card cannot communicate with any device on the loop. Be aware all devices
associated with this loop will indicate a ‘Normal’ state to prevent multiple faults per display.
Possible causes:
The Loop has a Short circuit
The Loop has an Earth fault
The Loop is not connected or incorrectly connected
1.1.2.6 Channel Initialization Abnormal
Description:
This fault typically occurs at startup with IDNet loops and will normally clear after a couple
of minutes if a lot of Isolators are fitted.
Possible causes:
If the fault continually re-appears the loop length maybe too long or too noisy –
Contact you local Simplex® branch for assistance
Possible bad device causing communication errors
- Disconnect devices at half way points until the fault clears to locate
the faulty device
1.1.2.7 Extra Device
Description:
A device is located on the addressable loop that is addressed at a location that is not
programmed.
Possible causes:
The panel has identified a device/card at an address that is not in the panel programming.
Refer to the Extra Device section of Device Faults (Page 20).
A card/device may be incorrectly addressed bringing up an Extra Device fault, but the
programmed device’s address will display “Points defined but not inserted.”