Installation manual
16 of 72
SIMPLEX Fault Assistance Guide RevA
29 April 2009
1.1.3.1 No Answer
Description:
The panel has a device programmed at the address displayed that is not responding.
Possible causes:
1. Device is not fitted.
2. Addressable loop is not working correctly (loop is broken)
3. Faulty base or device
Suggested solutions:
NO
YES
Check
device
Check Loop is
powered at device
(
30V
)
Is device LED
flashin
g
?