1.1.3.2 Head Missing
Description:
The panel is seeing the base at the displayed address but is not seeing the head (Sensor).
Possible causes:
Head is not installed.
Head is not fully twisted onto the base
Detector terminals on the base are loose
Faulty Head
Faulty Base
Suggested solutions:
NO
NO
YES
Replace Head
Adjust terminals to
make better contact
with head
Is base LED
flashing?
Replace Base