SIMPLEX Fault Assistance Guide RevA
29 April 2009
1.1.3.3 Wrong Device
Description:
The panel is getting a response from the displayed address that does not match the device
programmed to that address.
Possible causes:
Incorrect device installed (Relay with T-Sense fitted instead of standard Relay)
Incorrect head installed (Photo instead of Heat)
Detector head not making good contact with base
Suggested solutions:
NO
YES
Replace Device /
Sensor
Retrieve the part number from the
device (409x-xxxx)
Device or Program
change will be required
Replace Base
Contact the Programmer
to confirm device
matches Program