SIMPLEX Fault Assistance Guide RevA
29 April 2009
1.1.3.6 Output Abnormal
Description:
Observed when the output of a Relay, Sounder or Isolator base is not responding
correctly.
Possible causes:
ISOLATOR Base
A Short circuit has occurred on the addressable loop and the Isolator Base has not
been able to reset correctly
SOUNDER or RELAY Base
24 Volt supply to Sounder base is not present
Suggested solutions:
ISOLATOR Base – If short circuit fault has been corrected press ‘CPU RESET’
(Warm Start) to reinitialise the isolator base
SOUNDER or RELAY Base - Check wiring and 24V fused distribution board in
panel