SIMPLEX Fault Assistance Guide RevA
29 April 2009
1.1.3.7 Alarm Verification Tally Exceeded
NOTE: This fault could indicate a faulty detector in the field. Check for previous
faults and note in the Log book the time and date this fault occurred.
1. Log in at Level 4
2. Select P214
3. Force Point ON
4. Reset CPU (use button on CPU – refer to Page 7) to clear Simplex®
Service Fault
1.1.3.8 Detector LED Operation
Off
Detector is not communicating with the Panel
Two Detectors on the same address
The Head is not fitted correctly
Flash
Detector is communicating with the panel
Flash speed does not provide any information
On
Detector is in ALARM or FAULT
If no Head fitted then EXTRA DEVICE fault.
Detector LED may become latched on if multiple faults occur to the same
detector. To Reset the LED warm boot the fire panel