SIMPLEX Fault Assistance Guide RevA
29 April 2009
4. Measure the voltage on the battery leads. You may have to power down & up
again to reset the power supply. If the voltage is correct, power down, re-connect
the power & comms harnesses & return the system to normal.
5. If the voltage is not correct, repeat steps 1 & 2.
Depending on the site implementation of the Power Supply (vertical orientation shown below),
it may be difficult to locate or view the Trim pot and it is then recommended that the panel be
powered down and the power supply dismounted from the panel and reconnected (and made
live) on a non conductive surface as you will need to monitor the voltage across the Terminal
Strip B connections.