SIMPLEX Fault Assistance Guide RevA
29 April 2009
5.5 BGA or FIP Fault
A 10V Zener Diode type BZT03-C10 (Normally open input type only) is required as Input End-
of-Line. The Zener diode is required to maintain Line Monitoring. The diode must be connected
with the cathode (i.e. the end marked with a band) to the positive input (Please see
‘Termination Points and Example Wiring’ figure shown below).
Inputs that are programmed as General Purpose (GP) inputs do not need the zener diode end
of line.
Cables should have a wire gauge of at least 0.75mm
2
and should not be longer than 1000m.
Table 5: DIP Switch Settings
The FIB8910 Fire Indicator Panel/Break Glass Alarm Master Module has only a single Status
Indicator LED which indicates 24V Power Supply to the card.