5.6 WIP Line Fault
The WIPS2000 must connect to a WTRM2000 termination module. The WIPS9004 must
connect to a WTRM9007 termination module. Do not swap them over.
NOTE: WIP Line fault LEDs will flash (whilst un-acknowledged) when a WIP Line fault is
detected in its corresponding Zone. For example, a flashing WIP Line Fault LED on Zone 2 will
indicate a WIP Line fault associated with that Zone.
A WIPS Module Fault may be present if one or more WIP Line Fault LEDs are active. The
zones in fault will indicate will indicate which WIP Module may be having issues/problems, as
the lines in fault will be connected to this module.
If a WIP Line Fault is detected, you will need to check the wiring configuration (as above) and
ensure the correct EOL (end of line) resistor has been installed. A WIP Line fault indicator LED
will be located on the ECP in its corresponding Zone, depicting which WIP connection to focus
on.