1.2 Basic Interface Commands
The table shown below includes some general front panel commands for quickly
navigating through system components. In addition output points can be controlled by
following the below steps then commanding the point via the On/Off/Auto keys. Manually
controlling output points will create a fault on the LCD display, and to clear these faults
each manually altered output will need to be set back to its AUTO state or press the CPU
Reset (Warm Start).
Press
These Keys to Select Points
Enter
Point Data
ZONE+ Number + Enter
(4100A Only)
Enter the number of a zone. After pressing
enter, use the Previous/Next keys to scroll
through the zone points.
SIG+ Number + Enter
Enter the number of a signal circuit
AUX+ Number + Enter
Enter the number of an auxiliary relay point
FB+ Number + Enter
Enter the number of a feedback point
IO+ Number + Enter
Enter the number of a 24-Point I/O point
IDNet (4100U) / Mapnet (earlier 4100) +
Channel-Device + Enter
For Channel (loop), enter the number of the
IDNet, MAPNET, or VESDA channel. Insert
a dash using the NET key. Enter the number
of the addressable device.
P + Number + Enter Enter the number of a digital pseudo point
A + Number + Enter Enter the number of an analog pseudo point
L + Number + Enter Enter the number of a list pseudo point
NET + Number + Enter Enter the number of the network node. When
the screen prompts you to select the type of
point (Zone, Signal, etc.), press the Entry
Keypad key corresponding to that type of
point, enter the number of the point, and
press Enter.
ADDR + Card-Point-Subpoint + Enter Enter the number of the card, insert a dash
(using the NET key), and enter the number
of the subpoint.