Installation manual

Page x SIMPLEX 4100 FIRE INDICATOR PANEL
OPERATOR MANUAL
Document No.: 4100-M001 May 1997 Issue 1.0
SPECIFICATION
GENERAL
System Capacity 1,000 points of addressable input / output devices or
conventional zones.
Cabinet Size(mm) Dependent on system configuration
Cabinet Material 1.5mm Mild grade steel
Cabinet Finish Powder coated
Cabinet Colour Magnolia Ripple
Mounting Wall mount
Mains Input 240V AC, +6%,-10%, 50Hz
Internal Power Supply 24V DC @ 6.5A
Standby Battery 24V sealed lead acid up 110Ah
Battery Charger 27.6V DC (nominal) @ 3.5A,
PSU Supervision Charger high/low, Battery low/fail
Temperature -5 C to 45 C
Humidity 10% to 90% RH non-condensing.
EXPANSION MODULES
Maximum Number 119 modules
4100 - 5002 Conventional zone module
Eight zone circuits per module
Supports standard 20V detectors plus normally open
contact devices
4100 - 3003 Eight CPU controlled auxiliary relays per module
SPDT contacts rated for 3 amps @ 24VDC or 30VAC
4100 - 0113 RS-232 / 2120 Communications Module
Provides two RS-232-C outputs for remote printers
and/or CRT
Five RS-232-C ports maximum per 4100 system
Can be configured for communication with a host 2120
system
Can be configured as a Computer Port for
communications to a remote system i.e. BMS or BAS
Systems